| Plan Review Stops For Permit 02020131 |
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2002-02-08 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-02-08 |
Time |
14:23 |
Rev Time |
0.30 |
| Received By |
pkrauss |
Date |
2002-02-08 |
Time |
14:23 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2002-02-08 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-02-08 |
Time |
06:55 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2002-02-08 |
Time |
06:49 |
Sent To |
|
|
| Notes |
| 2002-02-08 00:00:00 | | | | | | | PLEASE CLARIFY THE FOLLOWING: | | | | | | 1.ACCESS FOR THE AHU. | | | | | | 2.RETURN AIR LOCATION. | | | | | | 3.BATHROOM EXHAUST...IS THERE ANY? | | | | | | 4.CONDENSATE LINE IS INDICATED AS 3/8" | | | IS THIS THE LINE SIZE AT THE UNIT? | | | AS PER 1997 SMC 304.8.4, CONDENSATE | | | WASTE & DRAIN LINES SHALL BE NOT | | | LESS THAN THE EQUIPMENT DRAIN LINE | | | SIZE & IN NO CASE SHALL IT BE LESS | | | THAN 3/4 PIPE OR 7/8 TUBING SIZE. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
|