Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-02-08 Cont ID  
Sent By pkrauss Date 2002-02-08 Time 14:23 Rev Time 0.30
Received By pkrauss Date 2002-02-08 Time 14:23 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-02-08 Cont ID  
Sent By pkrauss Date 2002-02-08 Time 06:55 Rev Time 0.35
Received By pkrauss Date 2002-02-08 Time 06:49 Sent To  
Notes
2002-02-08 00:00:00 
  
 PLEASE CLARIFY THE FOLLOWING:
  
 1.ACCESS FOR THE AHU.
  
 2.RETURN AIR LOCATION.
  
 3.BATHROOM EXHAUST...IS THERE ANY?
  
 4.CONDENSATE LINE IS INDICATED AS 3/8"
 IS THIS THE LINE SIZE AT THE UNIT?
 AS PER 1997 SMC 304.8.4, CONDENSATE
 WASTE & DRAIN LINES SHALL BE NOT
 LESS THAN THE EQUIPMENT DRAIN LINE
 SIZE & IN NO CASE SHALL IT BE LESS
 THAN 3/4 PIPE OR 7/8 TUBING SIZE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.