Plan Review Details - Permit 02020114
Plan Review Stops For Permit 02020114
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-06-12 Cont ID  
Sent By dpalmer Date 2002-06-12 Time 17:14 Rev Time 0.00
Received By dpalmer Date 2002-06-12 Time 17:14 Sent To  
Notes
2002-06-12 00:00:00RESTAMP.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-02-15 Cont ID  
Sent By btrobaug Date 2002-02-15 Time 14:36 Rev Time 0.00
Received By btrobaug Date 2002-02-15 Time 11:02 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-02-23 Cont ID  
Sent By hmoser Date 2002-02-23 Time 12:19 Rev Time 0.33
Received By hmoser Date 2002-02-23 Time 12:19 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-02-23 Cont ID  
Sent By btrobaug Date 2002-02-15 Time 14:36 Rev Time 0.33
Received By jleech Date 2002-02-23 Time 06:51 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2002-06-14 Cont ID  
Sent By rmcdouga Date 2002-06-14 Time 15:32 Rev Time 0.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-06-14 00:00:00RESTAMP PLANS CONTRACTOR LOST FEILD SET

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2002-03-11 Cont ID  
Sent By rmcdouga Date 2002-03-11 Time 17:33 Rev Time 2.00
Received By rmcdouga Date   Time   Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2002-03-05 Cont ID  
Sent By rmcdouga Date 2002-03-05 Time 10:27 Rev Time 4.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-03-05 00:00:00*************BUILDING DENIED************
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) ENERGY CALCULATION FORM IS REQUIRED
 TO BE SIGNED BY THE OWNER/AGENT.
  
 4) THE REVISED SOIL REPORT LETTER STATES
 THAT FOUNDATIONS BEAR 14" BELOW GRADE
 AND THE CITY AMENDMENTS (1804.1.9)
 REQUIRES FLOOR ELEVATION TO BE MINIMUM
 OF 4" ABOVE THE FINISH GRADE. THIS WILL
 REQUIRE AN 18" DEEP FOOTING.THE FOOTINGS
 SHOWN ON S2 ARE ONLY 16" IN DEPTH.
 PLEASE CORRECT.
  
 5) THE 2X8 AT THE TOP OF THE MASONRY
 WALLS BETWEEN UNITS IS REQUIRED TO BE
 FIRE TREATED. (SEE A-3.0, S3)
  
 6) INDICATE THE SPACING OF THE FASTENERS
 FOR THE S.G.D. ON DETAIL 6 ON A-4.0.
 INDICATE THE TYPE FASTENER AND SPACING
 FOR THE S.G.D. JAMB DETAIL 9 ON A-4.0.
  
 7) GARAGE BUCK DETAIL 7 ON A-4.0 REFERS
 TO DETAIL 1 ON A-5 AND IT SHOULD READ
 DETAIL 1 ON A-4. PLEASE CORRECT.
  
 8)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - ROOFING MATERIALS FOR FLAT ROOF
 - CLOPAY GARAGE DOOR (REPORT 9606B HAS
 BEEN UPDATED BY REPORT 9606C)
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop Z ZONING
Rev No 1 Status P Date 2002-02-08 Cont ID  
Sent By sgraham Date 2002-02-08 Time 08:14 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***