Plan Review Details - Permit 02020085
Plan Review Stops For Permit 02020085
Review Stop E ELECTRICAL
Rev No 7 Status P Date 2003-01-08 Cont ID  
Sent By btrobaug Date 2003-01-08 Time 15:42 Rev Time 0.50
Received By btrobaug Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2003-01-02 Cont ID  
Sent By btrobaug Date 2003-01-02 Time 10:37 Rev Time 0.00
Received By btrobaug Date 2003-01-02 Time 10:37 Sent To  
Notes
2003-01-02 00:00:00UNSAT!
 ~~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 THE REVISION SHEET NUMBERS DO NOT
 CORRELATE WITH THE PERMITED SET.
  
 THE RECEPTACLE SPACING IN THE BREAKFAST
 & FAMILY ROOMS DO NOT MEET THE
 REQUIREMENTS OF 210-52(A)(1),SEE
 REVIEWED PLAN.
  
 THE FEEDERS ON THE RISER DIAGRAM ARE
 INCORRECTLY MARKED(REVERSED).
  
 PLEASE MAKE NECESSARY CORRECTIONS AND
 RESUBMIT FOR REVIEW.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT. 8392

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2002-12-16 Cont ID  
Sent By btrobaug Date 2002-12-16 Time 14:15 Rev Time 0.50
Received By btrobaug Date 2002-12-16 Time 13:59 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2002-09-26 Cont ID  
Sent By btrobaug Date 2002-09-26 Time 17:09 Rev Time 0.25
Received By btrobaug Date 2002-09-26 Time 16:57 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2002-09-12 Cont ID  
Sent By btrobaug Date 2002-09-12 Time 11:39 Rev Time 0.25
Received By btrobaug Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-04-26 Cont ID  
Sent By dpalmer Date 2002-04-26 Time 14:26 Rev Time 0.00
Received By dpalmer Date 2002-04-26 Time 14:26 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-02-25 Cont ID  
Sent By dpalmer Date 2002-02-25 Time 15:32 Rev Time 0.00
Received By dpalmer Date 2002-02-25 Time 15:32 Sent To B
Notes
2002-02-25 00:00:00**************** UNSAT **************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 3)NOTE: PLEASE NOTE THAT GFI SHOWN NEXT
 TO A/C COND UNIT, IS SHOWN AS OPT?
 PLEASE NOTE THAT PER 309.2 (MECH CODE)
 A OUTLET IS REQ`D.
  
 4)NOTE: PLEASE NOTE A FEW MISSING OUTLET
 -S UPSTAIRS PER 2' OF WALL. 210-52
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372
  
 5)NOTE: PLEASE LIST THE REQ`D ARC FAULT
 PROTECTION PER 210-12

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-12-26 Cont ID  
Sent By pkrauss Date 2002-12-26 Time 09:46 Rev Time 0.35
Received By pkrauss Date 2002-12-26 Time 09:03 Sent To  
Notes
2002-12-26 00:00:00MECH REV PERMIT 02020099

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-02-23 Cont ID  
Sent By hmoser Date 2002-02-23 Time 11:03 Rev Time 0.50
Received By hmoser Date 2002-02-23 Time 11:03 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2002-06-20 Cont ID  
Sent By kstevens Date 2002-06-20 Time 13:20 Rev Time 0.00
Received By kstevens Date 2002-06-20 Time 13:20 Sent To  
Notes
2002-06-20 00:00:00REVISION OK - SANT RISER DIAGRAM

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-05-02 Cont ID  
Sent By jleech Date 2002-05-02 Time 12:52 Rev Time 0.33
Received By jleech Date 2002-05-02 Time 12:52 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-02-14 Cont ID  
Sent By dpalmer Date 2002-04-26 Time 14:26 Rev Time 0.33
Received By kstevens Date 2002-02-14 Time 11:25 Sent To  
Notes
2002-02-14 00:00:00DENIED
 REFERENCE: SPC-94
  
 1) RISER DIAGRAM DOES NOT REFLECT FLOOR
 PLAN. BATH #3 HAS TUB ON FLOOR PLAN BUT
 SHOWER ON RISER DIAGRAM. ALSO THIS FIX-
 TURE IS NOT VENTED PROPERLY.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2002-05-06 Cont ID  
Sent By lhatten Date 2002-05-06 Time 20:04 Rev Time 1.25
Received By lhatten Date   Time   Sent To  
Notes
2002-05-07 00:00:00RESUB OKED ! BUT STILL NO ADDRESS TO
 HOUSE 05/07/2002

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2002-04-03 Cont ID  
Sent By lhatten Date 2002-04-03 Time 21:44 Rev Time 2.50
Received By lhatten Date 2002-03-09 Time 21:42 Sent To  
Notes
2002-04-03 00:00:00REVIEW & STAMPED PLANS -- PROVISO
 WINDOW & EXTERIOR DOOR PRODUCT APPROVALS
 MUST BE SIGNED & SEALED BY ARCHITECT
 03/09/2002
 PLAT NOT RECORDED YET!

Review Stop Z ZONING
Rev No 1 Status P Date 2002-02-14 Cont ID  
Sent By kstevens Date 2002-02-14 Time 11:22 Rev Time 0.25
Received By kstevens Date   Time   Sent To  
Notes
***NONE***