Plan Review Details - Permit 02020081
Plan Review Stops For Permit 02020081
Review Stop E ELECTRICAL
Rev No 5 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By btrobaug Date 2003-01-02 Time 06:49 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2002-12-18 Cont ID  
Sent By btrobaug Date 2002-12-18 Time 17:39 Rev Time 0.50
Received By btrobaug Date 2002-12-18 Time 17:28 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2002-09-12 Cont ID  
Sent By btrobaug Date 2002-09-12 Time 11:44 Rev Time 0.25
Received By btrobaug Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-04-26 Cont ID  
Sent By dpalmer Date 2002-04-26 Time 13:52 Rev Time 0.00
Received By dpalmer Date 2002-04-26 Time 13:52 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-02-26 Cont ID  
Sent By dpalmer Date 2002-02-26 Time 07:22 Rev Time 0.00
Received By dpalmer Date 2002-02-26 Time 07:22 Sent To B
Notes
2002-02-26 00:00:00***************** UNSAT **************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
  
 3)NOTE: PLEASE LIST THE REQ`D ARC FAULT
 PROTECTION PER 210-12
  
 4) NOTE: PLEASE SHOW ALL OUTLET SPACING
 TO MEET 2`,6`,12` RULE PER 210-52.
 MISSING DINING ROOM.
  
 5)NOTE: PLEASE NOTE THAT GFI FOR A/C
 COND UNIT IS SHOWN AS OPTIONAL? PLEASE
 NOTE THAT THE GFI OUTLET IS REQ`D PER
 MECH CODE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-12-26 Cont ID  
Sent By pkrauss Date 2002-12-26 Time 10:39 Rev Time 0.30
Received By pkrauss Date 2002-12-26 Time 10:24 Sent To  
Notes
2002-12-26 00:00:00MECH REV PERMIT 02020086

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-02-23 Cont ID  
Sent By hmoser Date 2002-02-23 Time 10:13 Rev Time 0.50
Received By hmoser Date 2002-02-23 Time 10:13 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status P Date 2002-07-16 Cont ID  
Sent By pschmitz Date 2002-07-16 Time 13:34 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2002-07-16 00:00:00PLBG PLAN REVIEW REVISION, PES

Review Stop P PLUMBING
Rev No 3 Status F Date 2002-06-20 Cont ID  
Sent By kstevens Date 2002-06-20 Time 14:19 Rev Time 0.00
Received By kstevens Date 2002-06-20 Time 14:19 Sent To  
Notes
2002-06-20 00:00:00REVISION DENIED - FLOOR PLAN SHOWS A
 SHOWER IN BATH #3, BUT SANT. RISER DIA-
 GRAM SHOW NONE. PLEASE CLAIRFY.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-05-02 Cont ID  
Sent By jleech Date 2002-05-02 Time 13:00 Rev Time 0.33
Received By jleech Date 2002-05-02 Time 13:00 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-02-09 Cont ID  
Sent By dpalmer Date 2002-04-26 Time 13:52 Rev Time 0.33
Received By jleech Date 2002-02-09 Time 13:22 Sent To  
Notes
2002-02-09 00:00:00DENIED;
 PAGE A-7. PLUMBING RISER NOT TO CODE.
 UNVENTED FIXTURES AND MAJOR FIXTURES
 OVER MINER FIXTURES.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT. 8369

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2002-05-06 Cont ID  
Sent By lhatten Date 2002-05-06 Time 19:58 Rev Time 1.25
Received By lhatten Date   Time   Sent To  
Notes
2002-05-07 00:00:00RESUB OKED ! BUT STILL NO ADDRESS FOR
 HOUSE05/07/2002

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2002-04-03 Cont ID  
Sent By lhatten Date 2002-04-03 Time 21:33 Rev Time 2.50
Received By lhatten Date 2002-03-09 Time 21:31 Sent To  
Notes
2002-04-03 00:00:00REVIEW & STAMPED PLANS - PROVISO WINDOW
 AND EXTERIOR DOORMUST BE SIGNED &
 SEALED BY ARCHITECT IN SPACE PROVIDED
 03/09/2002
 PLAT NOT RECORDED YET !

Review Stop Z ZONING
Rev No 1 Status P Date 2002-02-08 Cont ID  
Sent By sgraham Date 2002-02-08 Time 08:21 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy