Plan Review Details - Permit 02020023
Plan Review Stops For Permit 02020023
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-02-14 Cont ID  
Sent By mcarsill Date 2002-02-14 Time 16:43 Rev Time 0.00
Received By mcarsill Date 2002-02-14 Time 16:43 Sent To  
Notes
2002-02-14 00:00:001) FIRE ALARM CIRCUITS ARE TO BE
 INSTALLED IN ACCORDANCE WITH NFPA 70,
 SECTION 760, NON POWER LIMITED FIRE
 ALARM CIRCUITS.
 2) FIRE ALARM AND FIRE SPRINKLER SYSTEM
 TO BE MONITORED BY A LICENSED UL LISTED
 CENTRAL STATION APPROVED BY THE FIRE
 RESCUE DEPARTMENT.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-02-05 Cont ID  
Sent By mcarsill Date 2002-02-05 Time 13:44 Rev Time 0.00
Received By mcarsill Date 2002-02-05 Time 13:44 Sent To  
Notes
2002-02-05 00:00:001) PLANS ARE NOT SIGNED AND SEALED.
 PLANS CONTAIN ARCHITECTS TITLE BLOCK.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910