Plan Review Details - Permit 02011673
Plan Review Stops For Permit 02011673
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-02-04 Cont ID  
Sent By btrobaug Date 2002-02-04 Time 13:41 Rev Time 0.25
Received By btrobaug Date 2002-02-04 Time 13:41 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-02-04 Cont ID  
Sent By btrobaug Date 2002-02-04 Time 09:02 Rev Time 0.33
Received By btrobaug Date 2002-02-04 Time 08:43 Sent To  
Notes
2002-02-04 00:00:00*****************DENIED!****************
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION AND RESUBMIT.
  
 1)LOAD CALCULATION OF EXISTING PANEL.
 2)NAMEPLATE RATING OF NEW AHU.
 3)NAMEPLATE RATING OF THE NEW C/U.
 4)CONDUIT & WIRE SIZE FEEDING NEW UNITS.
  
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 (561) 659-8096
 WXT.8392