| Plan Review Stops For Permit 02011641 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2002-03-05 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2002-03-05 |
Time |
16:28 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2002-03-05 |
Time |
16:28 |
Sent To |
|
|
| Notes |
| 2002-03-05 00:00:00 | BUILDING PLAN REVIEW | | | ******PROVISO******* | | | ROBERT BROWN(561) 659 8096 EXT 8499 | | | | | | --PROVISO-- | | | A RECORDED COPY OF THE NOTICE OF | | | COMMENCEMENT MUST BE SUBMITTED BEFORE A | | | PERMIT CAN BE ISSUED. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2002-02-12 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2002-02-12 |
Time |
19:04 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2002-02-12 |
Time |
19:00 |
Sent To |
|
|
| Notes |
| 2002-02-12 00:00:00 | BUILDING PLAN REVIEW | | | *******DENIED******* | | | ROBERT BROWN(561) 659 8096 EXT 8499 | | | | | | FL ENERGY CODE = FLORIDA ENERGY | | | EFFICIENCY CODE FOR BUILD'G CONSTR'N | | | | | | 1) A RECORDED COPY OF THE NOTICE OF | | | COMMENCEMENT MUST BE SUBMITTED BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | 2) UNTIL MARCH 1, 2002 EITHER STANDARD | | | BUILDING CODE 1997 OR FLORIDA BUILDING | | | CODE 2001 MAY BE USED.NEITHER CODE IS | | | REFERENCED ON THE PLANS.STATE WHICH | | | CODE THE WORK IS TO BE CONSTRUCTED TO. | | | | | | 3) FL ACC CODE 4.1.3(12)(A)SHEET 1, | | | 'A.D.A CLEARANCES'.THE MAXIMUM HEIGHT | | | OF ACCESSIBLE SHELVING AND RAILS IS | | | SHOWN AS 54".THIS SHOULD READ 48" MAX, | | | AS SHOWN ON FIGURE 38. | | | | | | **QUOTE PERMIT# ON ALL CORRESPONDENCE** | | | | | | END OF REVIEW COMMENTS | | | THE CODE REFERENCES GIVE ADDITIONAL INFO | | | IF YOU HAVE ANY QUERIES PLEASE CALL: | | | ROBERT BROWN(561) 659 8096 EXT 8499 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2002-04-24 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-04-24 |
Time |
11:09 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-04-24 |
Time |
11:09 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2002-03-08 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-03-08 |
Time |
06:02 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-03-08 |
Time |
06:02 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2002-02-06 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-02-06 |
Time |
20:24 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-02-06 |
Time |
20:18 |
Sent To |
|
|
| Notes |
| 2002-02-06 00:00:00 | ***************** UNSAT ************* | | | | | | 1)NOTE: PLEASE NOTE THAT PLANS NEED TO | | | BE SEALED BY THE ENGINEER OF RECORD. | | | 471.025 | | | | | | 2)NOTE: PLEASE SEE FIRE REVIEW COMMENTS | | | FOR EXIT AND EMERGENCY LIGHTING. | | | | | | 3)NOTE: PLEASE CLARIFY CONDUCTOR SIZES | | | FOR "NOTE 4" ON RISER NOTES. | | | | | | 4)NOTE: PLEASE CLARIFY GROUNDING FOR | | | TRANSFORMER 250-24 ,,, | | | | | | 5)NOTE: PLEASE NOTE THAT MEANS OF | | | DISCONNECT FOR TRANSFORMER ABOVE CEILING | | | MUST MEET 110-26. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2002-03-07 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-03-07 |
Time |
12:16 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-03-07 |
Time |
12:16 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2002-02-06 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-02-06 |
Time |
09:43 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-02-06 |
Time |
09:43 |
Sent To |
|
|
| Notes |
| 2002-02-06 00:00:00 | 1) ADDITIONAL EXIT SIGNS ARE REQUIRED | | | TO DIRECT PERSONS TO THE EXIT SIGNS | | | THAT WERE SHOWN ON THE PLANS. | | | 2) PLEASE INDICATE LOCATIONS OF | | | EMERGENCY LIGHT FIXTURES. | | | 3) PLEASE INDICATE INTERIOR FINISH | | | CLASSIFICATION INFORMATION FOR WALLS | | | AND CEILINGS. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2002-03-12 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-03-12 |
Time |
13:12 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2002-03-12 |
Time |
13:02 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2002-02-14 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-02-14 |
Time |
08:22 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2002-02-14 |
Time |
08:22 |
Sent To |
|
|
| Notes |
| 2002-02-14 00:00:00 | | | | | | | INDICATE ON PLANS WHICH CODE THE PLANS | | | ARE DESIGNED TO. | | | 1997 STANDARD BUILDING CODEOR | | | 2001 FLORIDA BUILDING CODE | | | | | | 1.PROVIDE OUTSIDE AIR CALCULATIONS AS | | | PER ASHRAE 62-89. | | | | | | 2.PLAN SHEET 9 LEGEND INDICATES | | | EXISTING WATER COOLED HEAT PUMPS. | | | AC-2 LOOKS TO BE A NEW HEAT PUMP. | | | PROVIDE MANUFACTURER INFORMATION FOR | | | ANY NEW EQUIPMENT BEING INSTALLED. | | | | | | 3.INDICATE CONDENSTATE LINE AND | | | TERMINATION POINT ON THE PLAN. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2002-03-19 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-03-19 |
Time |
08:48 |
Rev Time |
1.00 |
| Received By |
kstevens |
Date |
2002-03-19 |
Time |
08:48 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2002-02-13 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-02-13 |
Time |
10:41 |
Rev Time |
1.00 |
| Received By |
kstevens |
Date |
2002-02-13 |
Time |
10:41 |
Sent To |
|
|
| Notes |
| 2002-02-13 00:00:00 | DENIED | | | | | | 1) PLEASE INDICATE WHICH CODE PLAN WAS | | | DESIGNED FOR. | | | 2) PLEASE NOTE THAT PLANS SHALL BE SEAL- | | | ED BY ENGINEER OF RECORD. 471.025 | | | 3) AIR CHAMBERS ARE APPROVED WITH VALVES | | | FOR RECHARGING AND ACCESS PANELS. WATER | | | HAMMER ARRESTORS SHALL BE LOCATED NEAR | | | FIXTURE AND NOT AT TOP OF DROP AND IF | | | APPROVED ACCESS PANEL NOT REQUIRED. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|