Plan Review Details - Permit 02011641
Plan Review Stops For Permit 02011641
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-03-05 Cont ID  
Sent By rbrown Date 2002-03-05 Time 16:28 Rev Time 0.00
Received By rbrown Date 2002-03-05 Time 16:28 Sent To  
Notes
2002-03-05 00:00:00BUILDING PLAN REVIEW
 ******PROVISO*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 --PROVISO--
 A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-02-12 Cont ID  
Sent By rbrown Date 2002-02-12 Time 19:04 Rev Time 0.00
Received By rbrown Date 2002-02-12 Time 19:00 Sent To  
Notes
2002-02-12 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 FL ENERGY CODE = FLORIDA ENERGY
 EFFICIENCY CODE FOR BUILD'G CONSTR'N
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) UNTIL MARCH 1, 2002 EITHER STANDARD
 BUILDING CODE 1997 OR FLORIDA BUILDING
 CODE 2001 MAY BE USED.NEITHER CODE IS
 REFERENCED ON THE PLANS.STATE WHICH
 CODE THE WORK IS TO BE CONSTRUCTED TO.
  
 3) FL ACC CODE 4.1.3(12)(A)SHEET 1,
 'A.D.A CLEARANCES'.THE MAXIMUM HEIGHT
 OF ACCESSIBLE SHELVING AND RAILS IS
 SHOWN AS 54".THIS SHOULD READ 48" MAX,
 AS SHOWN ON FIGURE 38.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUERIES PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2002-04-24 Cont ID  
Sent By dpalmer Date 2002-04-24 Time 11:09 Rev Time 0.00
Received By dpalmer Date 2002-04-24 Time 11:09 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-03-08 Cont ID  
Sent By dpalmer Date 2002-03-08 Time 06:02 Rev Time 0.00
Received By dpalmer Date 2002-03-08 Time 06:02 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-02-06 Cont ID  
Sent By dpalmer Date 2002-02-06 Time 20:24 Rev Time 0.00
Received By dpalmer Date 2002-02-06 Time 20:18 Sent To  
Notes
2002-02-06 00:00:00***************** UNSAT *************
  
 1)NOTE: PLEASE NOTE THAT PLANS NEED TO
 BE SEALED BY THE ENGINEER OF RECORD.
 471.025
  
 2)NOTE: PLEASE SEE FIRE REVIEW COMMENTS
 FOR EXIT AND EMERGENCY LIGHTING.
  
 3)NOTE: PLEASE CLARIFY CONDUCTOR SIZES
 FOR "NOTE 4" ON RISER NOTES.
  
 4)NOTE: PLEASE CLARIFY GROUNDING FOR
 TRANSFORMER 250-24 ,,,
  
 5)NOTE: PLEASE NOTE THAT MEANS OF
 DISCONNECT FOR TRANSFORMER ABOVE CEILING
 MUST MEET 110-26.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-03-07 Cont ID  
Sent By mcarsill Date 2002-03-07 Time 12:16 Rev Time 0.00
Received By mcarsill Date 2002-03-07 Time 12:16 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-02-06 Cont ID  
Sent By mcarsill Date 2002-02-06 Time 09:43 Rev Time 0.00
Received By mcarsill Date 2002-02-06 Time 09:43 Sent To  
Notes
2002-02-06 00:00:001) ADDITIONAL EXIT SIGNS ARE REQUIRED
 TO DIRECT PERSONS TO THE EXIT SIGNS
 THAT WERE SHOWN ON THE PLANS.
 2) PLEASE INDICATE LOCATIONS OF
 EMERGENCY LIGHT FIXTURES.
 3) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATION INFORMATION FOR WALLS
 AND CEILINGS.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-03-12 Cont ID  
Sent By pkrauss Date 2002-03-12 Time 13:12 Rev Time 0.35
Received By pkrauss Date 2002-03-12 Time 13:02 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-02-14 Cont ID  
Sent By pkrauss Date 2002-02-14 Time 08:22 Rev Time 0.40
Received By pkrauss Date 2002-02-14 Time 08:22 Sent To  
Notes
2002-02-14 00:00:00 
  
 INDICATE ON PLANS WHICH CODE THE PLANS
 ARE DESIGNED TO.
 1997 STANDARD BUILDING CODEOR
 2001 FLORIDA BUILDING CODE
  
 1.PROVIDE OUTSIDE AIR CALCULATIONS AS
 PER ASHRAE 62-89.
  
 2.PLAN SHEET 9 LEGEND INDICATES
 EXISTING WATER COOLED HEAT PUMPS.
 AC-2 LOOKS TO BE A NEW HEAT PUMP.
 PROVIDE MANUFACTURER INFORMATION FOR
 ANY NEW EQUIPMENT BEING INSTALLED.
  
 3.INDICATE CONDENSTATE LINE AND
 TERMINATION POINT ON THE PLAN.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-03-19 Cont ID  
Sent By kstevens Date 2002-03-19 Time 08:48 Rev Time 1.00
Received By kstevens Date 2002-03-19 Time 08:48 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-02-13 Cont ID  
Sent By kstevens Date 2002-02-13 Time 10:41 Rev Time 1.00
Received By kstevens Date 2002-02-13 Time 10:41 Sent To  
Notes
2002-02-13 00:00:00DENIED
  
 1) PLEASE INDICATE WHICH CODE PLAN WAS
 DESIGNED FOR.
 2) PLEASE NOTE THAT PLANS SHALL BE SEAL-
 ED BY ENGINEER OF RECORD. 471.025
 3) AIR CHAMBERS ARE APPROVED WITH VALVES
 FOR RECHARGING AND ACCESS PANELS. WATER
 HAMMER ARRESTORS SHALL BE LOCATED NEAR
 FIXTURE AND NOT AT TOP OF DROP AND IF
 APPROVED ACCESS PANEL NOT REQUIRED.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377