Plan Review Details - Permit 02011614
Plan Review Stops For Permit 02011614
Review Stop E ELECTRICAL
Rev No 5 Status P Date 2002-05-29 Cont ID  
Sent By dpalmer Date 2002-05-29 Time 13:59 Rev Time 0.00
Received By dpalmer Date 2002-05-29 Time 13:59 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2002-05-17 Cont ID  
Sent By rbrown Date 2002-05-28 Time 10:31 Rev Time 0.00
Received By dpalmer Date   Time   Sent To M
Notes
2002-05-17 00:00:00WAITING FOR ARCH TO CALL BACK,
 PLANS NEEDS SOME CORRECTIONS.
 PLANS STILL SHOW A POOL PANEL AND NOT
 AS OPT.,ALSO NOT ON RISER.
 GFI IN BATH NEEDS TO BE MOVED TO CENTER
 OF SINK.
 THERE ARE SOME OUTLETS THAT MORETHAN
 MEET 210-52. IF SHOWN ON PLANS THEN THEY
 WILL BE REQ`D TO BE INSATLLED, KITCHEN,
 BED RM.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
  
 ** CALLED ARCH OFFICE AT 6:30AM FRIDAY
 5/17/02. LEFT MESSAGE ON VOICE MAIL OF
 CHARLIE K.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2002-04-18 Cont ID  
Sent By dpalmer Date 2002-04-18 Time 06:38 Rev Time 0.00
Received By dpalmer Date 2002-04-18 Time 06:38 Sent To B
Notes
2002-04-18 00:00:00****************** UNSAT ***************
  
 1)NOTE: PLEASE NOTE, LOAD CALCUALTIONS
 STILL DO NOT CORRELATE WITH NEC ART 220.
  
 2)NOTE: PLEASE NOTE THAT POOL PANEL IS
 SHOWN ON PANEL SCHEDULE AS 1-POLE 20A
 W/ #12. PLEASE NOTE ON RISER AS 30A W/
 #6 AWG. STILL NO NEUTRAL FOR POOL LIGHT?
  
 3)NOTE: PLEASE NOTE THAT POOL PUMP IS
 SHOWN COMING FROM PANEL IN GARAGE ALSO??
 PLEASE CLARIFY IF POOL PANEL IS EVEN
 NEEDED IF EQUIPMENT IS GOING TO BE FED
 FROM MAIN PANEL.
  
 4)NOTE: PLEASE NOTE 5KW DRYER SHOWN AS
 1-POLE 20A W/#12 AWG???
  
 5)NOTE: PLEASE NOTE THAT CODE FOR
 KITCHEN OUTLETS IN NOTES IS STILL REF.
 WRONG ART. PLEASE ALSO NOTE MISSING
 OUTLET ON KITCHEN COUNTERSPACE PER
 210-52C. THE ART REF FOR KITCHEN IS THE
 ART FOR BATHS??
  
 6)NOTE: PLEASE NOTE THAT THE ARC FAULT
 PROETCTION FOR BEDROOMS IS STILL NOT
 LISTED ON PANEL SCHEDULE. 210-12
  
 7)NOTE: PLEASE NOTE THAT RISER IS SHOW-
 -ING 3/0`S FOR 150A SERVICE. PLEASE NOTE
 THAT IF 3/0` ARE SHOWN ON PLANS, THEN
 THEY WILL BE REQ`D TO BE INSTALLED. THIS
 IS JUST A NOTE. 3/0`S CAN STILL BE USED
 IF SO DESIRED.
  
  
  
 ********* NOTE ********** NOTE*******
 PLEASE NOTE THAT THIS IS THE 3RD TIME
 THE PLANS HAVE BEEN REVIEWED FOR THIS
 MODEL. PLEASE NOTE THAT UNDER THE FLA
 ADMINISTRATIVE CODE SEC.553-80. PLANS
 REVIEW/DENIED FOR THE SAME ITEMS FOR 3
 OR MORE TIMES ARE SUBJECT TO 4X THE FEE
 FOR PLAN REVIEW.
 PLEASE NOTE THAT ALL ITEMS NEED TO BE
 ADDRESSED.
 ****************************************
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2002-03-19 Cont ID  
Sent By hmoser Date 2002-04-16 Time 18:06 Rev Time 0.00
Received By dpalmer Date 2002-03-19 Time 18:00 Sent To P
Notes
2002-03-19 00:00:00*************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE LOAD CALCULATIONS
 NEED TO BE REDONE, LOAD TAKEN FOR A/C
 IS MORETHAN 65% AND LOAD TAKEN AFTER
 FIRST 10,000 IS MORETHAN 40%.
 PLEASE CORRECT.
  
 2)NOTE: PLEASE NOTE ONLY TWO "HOTS"
 GOING TO POOL PANEL. NEUTRAL? EQUIPMENT
 GROUND? 250-122
  
 3)NOTE: PLEASE NOTE THAT POOL PUMP IS
 LISTED ON 150A PANEL SCHEDULE, PLEASE
 LIST THE POOL PANEL AS SHOWN ON RISER
 DIAGRAM.
 PLEASE SHOW PANEL LOCATION ON PLANS,
 EVEN IF OPT.
  
 4)NOTE: PLEASE LIST THE REQ`D ARC FAULT
 CIRCUITS FOR BEDRROMS. 210-12
  
 5)NOTE: PLEASE NOTE OUTLET SPACING STILL
 NEEDS TO MEET 210-52. PLEASE NOTE A FEW
 MISSING LOCATIONS.
  
 6)NOTE: PLEASE NOTE THAT ART REF FOR
 KITCHEN CIRCUITS SHOULD BE 210-52B.
  
 7)NOTE: PLEASE CLARIFY TWO A/C
 DISCONNECTS SHOWN ON RISER DIAGRAM.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-03-06 Cont ID  
Sent By pkrauss Date 2002-03-05 Time 15:08 Rev Time 0.00
Received By dpalmer Date 2002-03-06 Time 06:56 Sent To  
Notes
2002-03-06 00:00:00***************** UNSAT ***************
  
 1)NOTE: PLEASE NOTE THAT RISER SHOWS AN
 EQUIPMENT GROUNDING CONDUCTOR FROM
 METER TO MAIN DISC? PLEASE NOTE THAT
 THIS PARALLELING THE NEUTRAL.
  
 2) NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
  
 3) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 4)NOTE: PLEASE NOTE MISSING GFI OUTLET
 FOR PENINSULAR IN KITCHEN. 210-52-C-3
  
 5)NOTE: PLEASE NOTE MISSING EGRESS LIGHT
 -ING IN MANY LOCATIONS. PER 210-70
 PLEASE CLARIFYIF THERE IS AN ATTIC
 ACCESS IN MASTER BEDROOM CLOSET? IF YES,
 THEN A LT IS REQ`D PER 210-70.
  
 6)NOTE: PLEASE NOTE THAT A DEDICATED
 CIRCUIT IS SHOWN ON PANEL SCHEDULE FOR
 WHIRLPOOL AND LOCATION OF REC IS NOT
 SHOWN ON PLANS? PLEASE SHOW.
  
 7)NOTE: PLEASE NOTE THAT DERATING OF
 A/C AHU HEAT IS TAKEN TWICE AT 65%,
 PLEASE NOT ONLY ONE DEDUCTION IS
 PERMITTED.
  
 8)NOTE: PLEASE NOTE THAT PLANS SHOW
 VOLTAGE BEING 120V? PLEASE NOTE THAT
 SERVICE SHOULD BE 120/240V.
 PLEASE NOTE THAT LOAD SHOWN EXCEEDS
 200A RATING OF PANEL.
  
 9)NOTE: PLEASE LIST THE REQ`D ARC FAULT
 PROTECTION PER 210-12. LIST ON PANEL
 SCHEDULE.
  
 10)NOTE: PLEASE SHOW GROUNDING ELECTRODE
 GOING TO BUILDING STEEL AND COLD WATER
 PER 250-50.
 MISSING BLDG/FOOTER STEEL.
  
 11)NOTE: PLEASE VERFIY CODE ARTS SHOWN
 IN NOTES. PLEASE NOTE THAT BATH ART IS
 SHOWN FOR KITCHEN NOTE AND ART FOR BATH
 NOTE SHOULD BE 210-11-C-3.
 PLEASE CORRELATE..
  
 PLEASE SUBMIT THE ABOVE INFORMAITON FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2002-06-11 Cont ID  
Sent By hmoser Date 2002-06-11 Time 18:12 Rev Time 0.33
Received By hmoser Date 2002-06-11 Time 18:12 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2002-05-20 Cont ID  
Sent By pkrauss Date 2002-05-20 Time 12:18 Rev Time 0.35
Received By pkrauss Date 2002-05-20 Time 12:09 Sent To  
Notes
2002-05-20 00:00:00PROVISO:
  
 CONDENSATE SHALL DISCHARGE A MINIMUM OF
 12" AWAY FROM THE BUILDING STRUCTURE AS
 PER 2001 FBC 1503.4.4.
  
 MINIMUM OF 10 FT SEPARATION BETWEEN
 DRYER EXHAUST & O.A. INTAKE.
  
 EXHAUST & INTAKE OPENINGS SHALL BE
 LOCATED A MINIMUM OF 10 FT FROM LOT
 LINES OR BUILDINGS ON THE SAME LOT.
 2001 FBC(M) 401.5.
  
 BALANCING DAMPERS OR OTHER MEANS OF
 SUPPLY AIR ADJUSTMENT SHALL BE PROVIDED
 IN THE BRANCH DUCTS OR AT EACH
 INDIVIDUAL DUCT REGISTER, GRILLE OR
 DIFFUSER. 2001 FBC(M) 603.15
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2002-04-16 Cont ID  
Sent By dpalmer Date 2002-05-17 Time 06:42 Rev Time 0.50
Received By hmoser Date 2002-04-16 Time 18:07 Sent To  
Notes
2002-04-16 00:00:00PLAN DENIED
 NO ENERGY CALCS
 PLAN REVIEW BY HAROLD MOSER 04/16/02

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2002-03-27 Cont ID  
Sent By pkrauss Date 2002-03-21 Time 13:07 Rev Time 0.35
Received By pkrauss Date 2002-03-21 Time 12:16 Sent To  
Notes
2002-03-21 00:00:00 
 MECHANICAL PLANS WERE NOT RESUBMITTED
 FOR REVIEW.
  
 FRESH AIR INTAKE INDICATED ON PLAN
 SHEETA-03.PLEASE NOTE INTAKE OPENINGS
 THAT TERMINATE OUTDOORS SHALL BE
 PROTECTED WITH CORROSION RESISTANT
 SCREENS, LOUVERS OR GRILLES. OPENINGS IN
 LOUVERS, GRILLES AND SCREENS SHALL BE
 SIZED IN ACCORDANCE WITH TABLE 401.6.
 (2001 SBC, MECH 401.6)
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-03-05 Cont ID  
Sent By pkrauss Date 2002-03-05 Time 14:12 Rev Time 1.45
Received By hmoser Date 2002-03-05 Time 13:23 Sent To E
Notes
2002-03-05 00:00:00MODEL A "MASTER" - PLANS REVIEWED UNDER
 THE 2001 FLORIDA BUILDING CODE,
 MECHANICAL.
  
  
  
 1.SHOW COMPLIANCE WITH TABLE 403.3 OF
 THE 2001 FBC, MECHANICAL, REQUIRED
 OUTSIDE AIR FOR PRIVATE DWELLING
 SINGLE & MULTIPLE LIVING AREAS.
  
 2.INDICATE LOCATION, SIZE AND MATERIAL
 OF OUTSIDE AIR DUCT.
  
 3.AIR TRANSFER REQUIRED FOR BEDROOM
 2 FOR COMPLIANCE WITH 2001 FBC, MECH
 601.4 (BALANCED AIR RETURN).
  
 4.PLAN SHEET E-1 INDICATES A 5 TON
 A/C AND HVAC PLAN INDICATES A 3 1/2
 TON A/C.PLEASE CORRELATE PLANS.
  
 5.OVERFLOW PROTECTION REQUIRED.SHOW
 COMPLIANCE WITH 2001 FBC, MECH
 307.2.3 OR 307.2.4.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 3 Status P Date 2002-04-13 Cont ID  
Sent By jleech Date 2002-04-13 Time 11:33 Rev Time 0.50
Received By jleech Date 2002-04-13 Time 11:33 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2002-03-27 Cont ID  
Sent By rbrown Date 2002-03-21 Time 18:41 Rev Time 0.00
Received By kstevens Date 2002-03-27 Time 16:31 Sent To  
Notes
2002-03-27 00:00:00DENIED
 REFERENCE: FBC-2001
  
 1) SHT A-02 FROM PREVIOUS REVIEW, BATH
 #2 EVERY DRY VENT CONNECTING TO A HORI-
 ZONTAL DRAIN SHALL CONNECT ABOVE THE
 CENTERLINE OF THE HORIZONTAL PIPE. SEC
 904.5.3
 2) SHT A-02 FROM PREVIOUS REVIEW, WASH
 MACHINE - "S" TRAP NOT APPROVED. DRY
 VENT SEC 904.5.3
 3) SHT A-02 DRY VENT AT M/BATH SHOWER.
 SEC 904.5.3
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-03-05 Cont ID  
Sent By rbrown Date 2002-03-04 Time 17:45 Rev Time 1.00
Received By kstevens Date 2002-03-05 Time 08:49 Sent To  
Notes
2002-03-05 00:00:00DENIED
 REFERENCE: FBC-2001
  
 1) PLEASE INDICATE CODE PLAN ARE DESIGN-
 ED FOR ON PLANS.
 2) SHT A-02 BATH #2, EVERY DRY VENT CON-
 NECTING TO A HORIZONTAL DRAIN SHALL CON-
 ECT ABOVE THE CENTERLINE OF THE HORIZON-
 TAL PIPE. SEC 904.5.3
 3) SHT A-02 BATH #2,3" PIPE NOT ALLOW-
 ED IN BLOCK WALL - TIE BEAM. FBC-2001
 SEC 1907.3.5.
 4) SHT A-02 BATH #2, LAV NOT VENTED.
 5) SHT A-02 WASHING MACHINE, TRAP UNDER-
 GROUND? DRY HORIZONTAL VENT SEC 904.5.3
 6) SHT A-02 MASTER BATH SHOWER NOT VENT-
 ED.
 7) SHT A-02 MASTER BATH, 3" PIPE NOT
 ALLOWED IN BLOCK WALL - TIE BEAM. FBC
 SED 1907.3.5
 8) SHT A-02 KITCHEN DRY HORIZONTAL VENT
 SEC 904.5.3
 9) SHT A-02 KITCHEN, "S" TRAPS NOT APPRO
 VEN.
 10) SHT A-02 KITCHEN, DISHWASHER NOT
 TRAPPED.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop R ROOF PLAN REVIEW
Rev No 5 Status P Date 2002-06-14 Cont ID  
Sent By rbrown Date 2002-06-14 Time 17:22 Rev Time 0.00
Received By rbrown Date 2002-06-14 Time 17:22 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 4 Status P Date 2002-05-28 Cont ID  
Sent By rbrown Date 2002-05-28 Time 10:29 Rev Time 0.00
Received By rbrown Date 2002-05-28 Time 10:29 Sent To E
Notes
2002-05-28 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEW OF 4/12/02:
  
 1) RESPONSE LETTER OF 4/22/02 IS NOTED.
 A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) RESPONSE LETTER OF 4/22/02 IS NOTED.
 IMPACT FEES MUST BE PAID TO PALM BEACH
 COUNTY, THE PLANS STAMPED BY THEM AND A
 COPY OF THE RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) FBC* 104.2.4SITE SURVEY.CONTRARY
 TO THE LETTER OF RESPONSE DATED 4/22/02,
 THE SIGNED AND SEALED SURVEY DRAWING WAS
 NOT SUBMITTED.
  
 4) RESPONSE LETTER OF 4/22/02 IS NOTED.
 FBC* 104.2.1.1ROOF COVERING PRODUCT
 APPROVAL SHALL BE SUBMITTED FOR THE ROOF
 COVERING SYSTEM TO BE USED (FBC 1504.3)
  
 5) FBC* 1804.2.2THE GEOTECHNICAL
 REPORT WAS SUBMITTED AS REQUIRED, BUT
 THE FOUNDATION/STRUCTURAL PLANS WERE NOT
 RESUBMITTED FOR CORRELATION CHECKS TO BE
 CARRIED OUT.RESUBMIT ALL DOCUMENTS.
  
 7) RESPONSE LETTER OF 4/22/02 IS NOTED.
 FBC 1606.1.4WINDOW AND DOOR PRODUCT
 APPROVALS.SUBMIT PRODUCT APPROVALS FOR
 THE EXTERIOR DOOR AND WINDOW SYSTEMS TO
 BE USED.
  
 9) FBC 13-103THREE COPIES OF THE HVAC
 LOAD ANALYSIS WERE RECEIVED BUT
 COMPLIANCE MUST BE DEMONSTRATED BY
 SUBMITTAL OF APPROPRIATE ENERGY CODE
 COMPLIANCE FORMS.
  
 11) FBC 1019.1.1 EXIT FROM ASSEMBLY RMS
 SHEET LS-105, SECOND FLOOR.THE LETTER
 OF RESPONSE DATED 4/22/02 IS NOTED.ADD
 PAINTED STRIPES WITH WARNING: FIRE
 EGRESS KEEP CLEAR, BETWEEN DOOR G22 AND
 THE STEPS/RAMP, ON SHEETS LS-103 & A-103
  
 16) FBC 1003.1 OCCUPANCY OF 'UNASSIGNED'
 ROOM, SHEET LS-106.IF THE EGRESS
 CAPACITY HAS BEEN CALCULATED BASED ON
 OFFICE USE AS STATED, THEN CHANGE THE
 ROOM NAME FROM 'UNASSIGNED' TO 'OFFICE'.
  
 17) FROM THE LETTER OF RESPONSE, IT IS
 NOTED THAT STAIR #3 IS NOT AN EXIT. WITH
 REFERENCE TO SHEET LS-106, THE COMMON
 PATH OF TRAVEL (FBC 202 & 1020.6) FROM
 COMMUNITY CONFERENCE ROOM (3-003) AND
 THE RECEPTION (3-002) MAY EXCEED 100 FT.
 SHOW THE PROPOSED FURNITURE IN THESE
 ROOMS ON THE LIFE SAFETY PLAN AND SHOW
 THAT THE COMMON PATH OF TRAVEL TO THE
 NORTH SECTION OF CORRIDOR 3-010 DOES NOT
 EXCEED 100 FT.ALTERNATIVELY, AMEND THE
 EGRESS SIGNS AND DOOR LOCKS TO PROVIDE A
 SECOND EGRESS PATH VIA CORRIDOR 3-024.
  
 21) FBC 104.2.1EXTERIOR ALUMINUM
 CLADDING PANELS.THIS COMMENT HAS NOT
 BEEN PROPERLY ADDRESSED.THE REVISION
 TO DETAIL 8/A-705 DOES NOT SHOW THE
 MEANS OF ATTACHING THE ALUMINUM-FACED
 PLYWOOD PANELS TO THE BUILDING FACADE.
  
 23)
2002-05-22 00:00:00BUILDING PLAN REVIEW
 ******PROVISO*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 PARADISE BAY-MASTER MODEL A
  
 --PROVISO--
 HURRICANE MISSILE IMPACT PROTECTION
 SHUTTERS.THE ROBICO SHUTTERS INC.
 DRAWINGS SUBMITTED DO NOT FORM PART OF A
 PRODUCT APPROVAL.SUBMIT A PRODUCT
 APPROVAL NOTICE OF ACCEPTANCE WITH
 ASSOCIATED DRAWINGS FOR THE PROPOSED
 SHUTTERS.

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status F Date 2002-05-02 Cont ID  
Sent By rbrown Date 2002-05-02 Time 11:44 Rev Time 0.00
Received By rbrown Date 2002-05-02 Time 11:44 Sent To  
Notes
2002-05-02 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEWS OF 3/4/02 AND 3/21/02:
  
 1) THIS COMMENT HAS NOT BEEN ADDRESSED.
 THE SITE SPECIFIC SURVEY DRAWING IS NOT
 APPLICABLE TO A MASTER MODEL PLAN REVIEW
 AND MUST BE REMOVED BEFORE RESUBMITTAL.
  
 2) THIS COMMENT HAS NOT BEEN PROPERLY
 ADDRESSED.THE GENERAL NOTES (SHEET G1)
 STILL REFER TO A BASIC WIND SPEED OF
 110MPH WHICH DOES NOT COMPLY WITH 2001
 FLORIDA BUILDING CODE.THE STATED WIND
 SPEED AND VELOCITY PRESSURE SHALL BE
 AMENDED TO DEMONSTRATE COMPLIANCE.
  
 3) THIS COMMENT HAS NOT BEEN PROPERLY
 ADDRESSED.WITH REFERENCE TO THE
 MASONRY COLUMN ADJACENT TO THE FAMILY
 ROOM PATIO DOOR, SHEET A-02 (FOUNDATION
 PLAN) AND SHEET A-3 (FLOOR PLAN) ARE
 STILL SHOWING DIFFERENT COLUMN TYPES.
 AMEND SHEET A-02 TO RECTIFY.
  
 13) FBC 1606.1.4GARAGE DOOR PRODUCT
 APPROVAL.THE GENERAL NOTES (SHEET G1)
 STATE THAT THE MAXIMUM POSITIVE
 COMPONENT AND CLADDING PRESSURE = 37PSF
 AND THE MAXIMUM NEGATIVE COMPONENT AND
 CLADDING PRESSURE = -42PSF. THESE EXCEED
 THE CAPACITY STATED IN THE GARAGE DOOR
 PRODUCT APPROVAL, IN WHICH TABLE 1 AND
 DRAWING SBC-580-015, STATE AN ALLOWABLE
 POSITIVE TRANSVERSE WIND LOAD OF 31.9PSF
 AND AN ALLOWABLE NEGATIVE TRANSVERSE
 WIND LOAD OF -36.8PSF.THE GARAGE DOOR
 WIND LOAD CAPACITY MUST EXCEED THE
 STATED CLADDING AND COMPONENT PRESSURE.
 RE-SPECIFY TO DEMONSTRATE COMPLIANCE.
  
 14) THIS COMMENT HAS NOT BEEN ADDRESSED.
 THE SUBMITTED PRODUCT APPROVAL NOTICE OF
 ACCEPTANCE NO. 00-0307.04 IS STILL
 MISSING DRAWING SHEETS 1 THROUGH 15
 (INCLUDING SHEET 10A).
  
  
 NOTE:
 CHAPTER 553.80(2)(B) FLORIDA STATUTES
 STATES THAT A LOCAL GOVERNMENT SHALL
 IMPOSE A FEE OF FOUR TIMES THE FEE FOR
 PLAN REVIEW, IF PLANS ARE REJECTED THREE
 OR MORE TIMES FOR REPEATED FAILURE TO
 CORRECT A CODE VIOLATION.
  
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2002-03-21 Cont ID  
Sent By rbrown Date 2002-03-21 Time 17:27 Rev Time 0.00
Received By rbrown Date 2002-03-21 Time 17:26 Sent To P
Notes
2002-03-21 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEW OF 3/04/02:
  
 1) THIS COMMENT HAS NOT BEEN ADDRESSED.
 THE SITE SPECIFIC SURVEY DRAWING IS NOT
 APPLICABLE TO A MASTER MODEL PLAN REVIEW
 AND MUST BE REMOVED.
  
 2) THIS COMMENT HAS NOT BEEN PROPERLY
 ADDRESSED.THE GENERAL NOTES (SHEET G1)
 AND ROOF FRAMING NOTES (SHEET A-05)
 STILL REFER TO A BASIC WIND SPEED OF
 110MPH WHICH, UNDER THE 1997 STANDARD
 BUILDING CODE, IS BASED ON THE 'FASTEST
 MILE'. UNDER 2001 FLORIDA BUILDING CODE,
 THE BASIC WIND SPEED FOR THE CITY IS
 140MPH, BASED ON A 3 SECOND GUST.AS A
 RESULT OF THIS REVISED METHOD OF
 ASSESSING WIND LOAD, THE BASIC VELOCITY
 PRESSURES WILL CHANGE.AMEND THE NOTES
 TO REFLECT THIS.
  
 3) THIS COMMENT HAS NOT BEEN PROPERLY
 ADDRESSED IN RESPECT OF THE MASONRY
 COLUMNS ON EACH SIDE OF THE PATIO DOOR
 FROM THE LIVING ROOM.SHEET A-02,
 FOUNDATION PLAN AND SHEET A-03, FLOOR
 PLAN ARE STILL SHOWING DIFFERENT COLUMN
 TYPES.AMEND SHEET A-03 TO RECTIFY.
  
 12) THIS COMMENT HAS NOT BEEN ADDRESSED.
 ADD A NOTE TO THE PLANS TO STATE THE
 REQUIREMENT FOR HURRICANE IMPACT
 SHUTTERS.
  
 13) THIS COMMENT HAS NOT BEEN ADDRESSED.
 SUBMIT A PRODUCT APPROVAL FOR THE
 GARAGE DOOR.
  
 14) THIS COMMENT HAS NOT BEEN ADDRESSED.
 THE DRAWING SHEETS 1 THROUGH 15 WHICH
 SHOULD ACCOMPANY THE GARAGE DOOR PRODUCT
 APPROVAL ARE STILL MISSING.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUERIES PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2002-03-04 Cont ID  
Sent By rbrown Date 2002-03-04 Time 17:45 Rev Time 0.00
Received By rbrown Date 2002-03-04 Time 17:45 Sent To P
Notes
2002-03-04 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) THIS IS A PLAN REVIEW FOR A MASTER
 MODEL.REMOVE THE SITE SPECIFIC SURVEY
 DRAWING BEFORE RESUBMITTAL.
  
 2) ALL PERMIT APPLICATIONS REVIEWED WITH
 REFERENCE TO THIS MASTER WILL BE CHECKED
 FOR COMPLIANCE WITH THE CURRENT CODE,
 FLORIDA BUILDING CODE.THE MASTER HAS
 BEEN REVIEWED FOR COMPLIANCE WITH THAT
 CODE, SO ALL REFERENCES TO THE 'STANDARD
 BUILDING CODE' MUST BE REMOVED.ALSO,
 THE GENERAL NOTES (SHEET G1) AND ROOF
 FRAMING NOTES (SHEET A-05) MUST BE
 AMENDED TO REFLECT WIND LOAD ASSESSMENT
 IN ACCORDANCE WITH THE FLORIDA BUILDING
 CODE 2001.
  
 3) SHEET A-02, FOUNDATION PLAN.THE
 MASONRY COLUMNS ON EACH SIDE OF THE
 OVERHEAD GARAGE DOOR AND THE SLIDING
 GLASS PATIO DOOR FROM THE LIVING ROOM
 ARE TYPE C2. THE FLOOR PLAN (SHEET A-03)
 SHOWS C1 COLUMNS IN THESE LOCATIONS.
 AMEND THE PLAN TO CLEAR THIS DISCREPANCY
  
 4) THE KITCHEN WINDOW IS SHOWN AS TYPE H
 ON THE PLANS AND TYPE M ON THE ELEVATION
 PROVIDE THE CORRECT REFERENCE.
  
 5) PLEASE NOTE THAT, FOR THE PERMIT
 APPLICATIONS BASED ON THIS MODEL, THE
 WINDOWS FACING LOT LINES MAY NEED TO BE
 FIRE-RATED IN ACCORDANCE WITH TABLE 600,
 IF CLOSE TO THE COMMON PROPERTY LINE.
  
 6) SHEET A-05, ROOF FRAMING PLAN. THE
 BEAM OVER THE FRONT ENTRANCE DOOR IS
 REFERENCED AS TYPE 8F81B.THIS
 REFERENCE IS NOT INCLUDED ON THE 'BEAM
 SCHEDULE'.
  
 7) SHEET A-05, ROOF FRAMING PLAN.FOUR
 OF THE TRUSS ANCHOR LABELS/NOTES AT THE
 LEFT ELEVATION HAVE BEEN PARTIALLY
 PRINTED AND ARE NOT LEGIBLE.
  
 8) TRUSS ANCHOR SCHEDULE.
 USP RT161T IS NOT A VALID USP REFERENCE.
 SIMPSON MTT27B IS NOT VALID REFERENCE.
 ALSO, FOR THE USP NFM, STATE THE MINIMUM
 REQUIRED SPECIFICATION/REFERENCE.
  
 9) FBC 2309.7CROSS VENTILATION SHALL
 BE PROVIDED FOR EACH SEPARATE ATTIC
 SPACE.AT LEAST 50% OF THE REQUIRED
 VENTILATION AREA SHALL BE AT A LEVEL NO
 LESS THAN 3FT ABOVE THE EAVES VENTS.
  
 10) THE SUBMITTED ROOF TILE PRODUCT
 APPROVAL FOR INTERLOCKING ROLL CONCRETE
 TILES DOES NOT CORRELATE TO THE
 ELEVATIONS WHICH SHOW "SPANISH S CEMENT
 TILE".SUBMIT AN APPROPRIATE PRODUCT
 APPROVAL.
  
 11) FBC 1606.3.3SPECIFY ROOF TILE
 FASTENINGS.
  
 12) FBC 1606.1.4THE SUBMITTED PRODUCT
 APPROVAL FOR GLASS BLOCK WINDOWS
 REQUIRES THE INSTALLTION OF HURRICANE
 MISSILE IMPACT PROTECTION.ADD A NOTE
 TO THE PLANS STATING THE REQUIREMENT FOR
 HURRICANE IMPACT SHUTTERS.
  
 13) FBC 1606.1.4SUBMIT A PRODUCT
 APPROVAL FOR THE GARAGE DOOR.
  
 14) PRODUCT APPROVAL (ACCEPTANCE
 NUMBER 00-0307.04) FOR THE '20 GAUGE
 GALVANISED STEEL STORM SHUTTER'. DRAWING
 SHEETS 1 THROUGH 15 (INCL SHEET 10A) ARE
 MISSING.
  
 15) THE DOOR SCHEDULE STATES THAT THE
 FRONT ENTRANCE DOOR IS WOOD.THE
 SUBMITTED PRODUCT APPROVAL IS FOR STEEL
 DOORS.IF THIS IS THE CORRECT PRODUCT
 APPROVAL, AMEND THE DOOR SCHEDULE TO
 REFLECT THIS.
  
 16) FBC 13-103.1.2THE ARCHITECT, OWNER
 OR HIS/HER LEGALLY DESIGNATED AGENT
 SHALL SIGN THE SUBMITTED ENERGY CODE
 COMPLIANCE CERTIFICATE.
  
 17) FBC 13-603.1.ABC.1THE GARAGE DOOR
 FALLS WITHIN THE DEFINITION OF AN
 'ADJACENT' DOOR (SECT. 202DEFINITIONS)
 AND SHALL BE SOLID CORE OR INSULATED.
 THE DOOR SCHEDULE REFERENCE MARK GIVEN
 IS '8' WHICH IS SHOWN AS A TYPE F DOOR.
 THE DOOR TYPE ELEVATIONS SHOW TYPE F AS
 BEING A DOUBLE DOOR. CORRECTION REQUIRED
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUERIES PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499

Review Stop Z ZONING
Rev No 1 Status P Date 2002-02-15 Cont ID  
Sent By sgraham Date 2002-02-15 Time 14:25 Rev Time 0.00
Received By sgraham Date 2002-01-30 Time 15:33 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved