Plan Review Details - Permit 02011609
Plan Review Stops For Permit 02011609
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-05-17 Cont ID  
Sent By btrobaug Date 2002-05-17 Time 13:13 Rev Time 0.00
Received By btrobaug Date 2002-05-17 Time 12:53 Sent To R
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-02-12 Cont ID  
Sent By btrobaug Date 2002-02-12 Time 17:28 Rev Time 0.00
Received By btrobaug Date 2002-02-12 Time 17:08 Sent To R
Notes
2002-02-12 00:00:00*****************UNSAT!*****************
 PLEASE SHOW RISER DIAGRAM COMPLETE WITH
 A.I.C.RATING,GROUNDING,MEANS AND RATING
 OF MAIN DISCONNECT.
 ALSO NOTE THE 4/0 ALUMINUM SHOWN ON PG
 7 OF 25 IS RATED FOR 180 AMPS.
  
 PLEASE PROVIDE THIS INFORMATION AND
 RESUBMIT.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 (561) 659-8096 EXT.8392

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2002-02-09 Cont ID  
Sent By hmoser Date 2002-02-09 Time 09:30 Rev Time 0.33
Received By hmoser Date 2002-02-09 Time 09:30 Sent To  
Notes
2002-02-09 00:00:00PERMIT IS REQUIRED FOR AIRCONDITIONING
 NEED TO KNOW LOCATION OF CONDENSOR
 PLAN REVIEW BY HAROLD MOSER
 [561]659-8096 EXT.8390

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-02-02 Cont ID  
Sent By jleech Date 2002-02-02 Time 06:44 Rev Time 0.33
Received By jleech Date 2002-02-02 Time 06:43 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2002-09-20 Cont ID  
Sent By btrobaug Date 2002-05-17 Time 13:14 Rev Time 1.00
Received By nleiva Date 2002-05-16 Time 17:27 Sent To  
Notes
2002-09-20 00:00:00OK LUIS MARTINEZ
2002-05-16 00:00:00APPROVED WITH PROVISO:
 1-PROVIDE HANDRAILS AT OUTSIDE STEPS AS
 REQUIRED BY SEC. 1007.5 SBC 1997.
  
 2-ENGINEER OF RECORD, GORDON F. BUCK, TO
 PROVIDE DETAIL/SPECS FOR CONNECTION OF
 HOUSE TO INTERIOR FOUNDATION PIERS.
 SEC. 104.2.2 CITY AMENDMENTS TO SBC/97
  
 3-ENGINEER OF RECORD TO PROVIDE DETAIL/
 SPECS AT CONNECTION OF PORCH POSTS TO
 FOUNDATION. SEC. 104.2.2 CITY
 AMENDMENTS TO SBC 1997..
  
 4-IF ENGINEER OF RECORD IS DESIGNING
 FOUNDATION ACCORDING TO THE 2001 FBC,
 THEN SPECIFY ON DRAWINGS THAT HIS
 CALCULATIONS ARE FOR 140MPH.
  
  
 **NOTE**
 PROVIDE ALL THIS INFORMATION FOR
 REVIEW PRIOR TO CONSTRUCTION TO AVOID
 DELAYS OR CONFLICTS.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2002-04-29 Cont ID  
Sent By jgomez Date 2002-04-29 Time 14:26 Rev Time 2.00
Received By jgomez Date 2002-04-29 Time 14:26 Sent To  
Notes
2002-04-29 00:00:00CHECKLIST:
 1-LOCAL ENGINEER, GORDON F. BUCK IS
 MIXING AND MATCHING DIFFERENT CODES.
 BUILDING WAS NOT DESIGNED BY FBC 2001
 FOR 140 MPH. REVISE ACCORDINGLY.
 2-FRONT PORCH DETAILS AND SPECS SHEET
 WAS NOT SIGNED BY ANYBODY AND WAS NOT
 REVIEWED BY THE AGENCY IN CHARGE OF
 REVIEWING MANUFACTURED HOMES. CLARIFY,
 WHO IS RESPONSIBLE FOR DESIGN AND
 REVIEW OF THESE DRAWINGS?.
 3-PROVIDE HANDRAIL DETAILS AND SPECS AT
 STAIRS. SEC. 1007.5.1(3).
 4-SOIL TEST REPORT ENGINEER'S FAILURE TO
 SIGN, SEAL AND DATE DOCUMENT AS
 REQ'D BY CHAPTER 471 FLORIDA STATUTES.
 5-PROVIDE COMPLETE INFORMATION FOR STORM
 SHUTTERS OR MISSILE IMPACT GLAZING.
 6-PAY IMPACT FEES TO PALM BEACH COUNTY.
 BRING BACK PAID RECEIPT AND STAMPED
 DRAWINGS.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2002-03-12 Cont ID  
Sent By btrobaug Date 2002-02-12 Time 17:28 Rev Time 3.50
Received By jgomez Date 2002-03-12 Time 16:05 Sent To  
Notes
2002-03-12 00:00:00CHECKLIST:
 1-PAY IMPACT FEES TO PALM BEACH COUNTY.
 BRING PAID RECEIPT & STAMPED DRAWINGS.
 2-PROVIDE COMPLETE SITE SPECIFIC
 ENGINEERED INFORMATION FOR FOUNDATION
 PLANS AND ATTACHMENT OF MANUFATURED
 HOUSE TO THE FOUNDATION.
 3-PROVIDE COMPLETE DETAILS AND SPECS FOR
 FRONT PORCH COLUMNS AND CONNECTIONS.
 4-PROVIDE COMPLETE DETAILS AND SPECS FOR
 STAIRS AND GUARDRAIL AT ENTRY PORCH.
 SEC. 1007 AND SEC. 1015 SBC 1997.
 5-PROVIDE PRODUCT APPROVAL FOR EXTERIOR
 SIDING. (BY PURCHASER SEE PLANS).
 6-SOIL TEST REPORT CALLS FOR HOUSE ON
 STEM WALL AND CONCRETE SLAB ON GRADE.
 THIS IS A MANUFATURED HOME WITH FLOOR
 JOISTS & CRAWL SPACE. REVISE AS REQ'D.
 7-PROVIDE INFORMATION REGARDING THE
 PROTECTION OF EXTERIOR GLAZED OPENINGS
 AS REQUIRED BY SECTION 1606.4 OF CITY
 AMENDMENTS TO SBC 1997. (STORM SHUTTER
 OR MISSILE IMPACT GLAZING).
 8-DECLARED VALUE WAS TOO LOW. VALUE WAS
 UPDATED AND OWES $183.59 AND INCLUDES
 RADON FEES.
 9-SEE COMMENTS BY THE OTHER TRADES.
 10-DEPARTMENT OF COMMUNITY AFFAIRS
 RENEWAL LETTER FOR MANUFACTURED HOMES
 IS EXPIRED. PROVIDE UPDATED ONE.

Review Stop Z ZONING
Rev No 1 Status P Date 2002-01-31 Cont ID  
Sent By sgraham Date 2002-01-31 Time 15:45 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***