Plan Review Details - Permit 02011587
Plan Review Stops For Permit 02011587
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-05-07 Cont ID  
Sent By hpiskura Date 2002-05-07 Time 11:27 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2002-05-07 00:00:00FOR REVISIONS #3 DATED 4/24/02

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2002-02-15 Cont ID  
Sent By hpiskura Date 2002-02-15 Time 08:46 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-02-04 Cont ID  
Sent By dpalmer Date 2002-02-04 Time 06:54 Rev Time 0.00
Received By dpalmer Date 2002-02-04 Time 06:54 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2002-02-04 Cont ID  
Sent By mamini Date 2002-02-04 Time 15:59 Rev Time 2.00
Received By mamini Date 2002-02-04 Time 15:59 Sent To  
Notes
2002-02-04 00:00:00PASSED WITH PROVISOS:
 1. CONTRACTOR MUST NOTIFY THE PUBLIC
 UTILITIES ENGINEERING DEPATMENT PRIOR TO
 DISCONNETING/ CAPPING ANY CITY WATER AND
 SEWER SERVICES.
 2. CONTRACTOR SHALL TAKE MEASURES
 REQUIRED TO PREVENT TRACKING DEBRIS,DUST
 INTO THE PUBLIC R.O.W DURING
 TRANSPORTATIONS OF REMOVED MATERIALS.
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-02-19 Cont ID  
Sent By mcarsill Date 2002-02-19 Time 15:45 Rev Time 0.00
Received By mcarsill Date 2002-02-19 Time 15:45 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-02-06 Cont ID  
Sent By mcarsill Date 2002-02-06 Time 10:18 Rev Time 0.00
Received By mcarsill Date 2002-02-06 Time 10:18 Sent To  
Notes
2002-02-06 00:00:001) PLEASE PROVIDE THIS OFFICE A WRITTEN
 PLAN ON HOW THE BUILDING WILL BE
 DEMOLISHED. SINCE THE BUILDING CONTAINS
 A LARGE AMOUNT OF COMBUSTIBLE MATERIAL
 THE FIRE SPRINKLER SYSTEM IS TO REMAIN
 ACTIVE UNTIL SUCH TIME AS THE
 COMBUSTIBLE MATERIAL IS REMOVED FROM THE
 BUILDING.
 2) THE FIRE SPRINKLER SYSTEM IS NOT TO
 BE DEMOLISHED UNTIL APPROVAL IS GRANTED
 BY THE CITY FIRE MARSHAL AND THE
 DIRECTOR OF CONSTRUCTION SERVICES.
 3) ADEQUATE MEANS OF EGRESS ARE TO BE
 PROVIDED DURING DEMOLITION ACTIVITIES.
 4) DEMOLITION ACTIVITIES ARE TO BE
 CONDUCTED IN ACCORDANCE WITH NFPA 241,
 THE STANDARD FOR SAFEGUARDING,
 CONSTRUCTION, ALTERATION AND DEMOLITION
 OPERATIONS, 1996 EDITION.
 5) NO HOT WORK IS TO PERFORMED IN THE
 BUILDING UNTIL APPROVED BY THE FIRE
 PREVENTION BUREAU IN ACCORDANCE WITH
 NFPA 51 B, THE STANDARD FOR FIRE
 PREVENTION DURING CUTTING, WELDING AND
 OTHER HOT WORK, 1999 EDITION.
 6) PORTABLE FIRE EXTINGUISHERS ARE TO
 REMAIN ON SITE DURING DEMOLITION
 ACTIVITIES.
 7) NO FIRE HYDRANTS ARE TO BE OBSTRUCTED
 BY DEMOLITION MATERIAL OR EQUIPMENT.
 8) NO FUEL TANKS ARE TO BE PLACED ON
 THE SITE WITHOUT APPROVAL OF THE
 FIRE PREVENTION BUREAU.
 9) NO FLAMMABLE LIQUIDS OR GASES ARE
 TO BE STORED WITHIN THE BUILDING
 DURING DEMOLITION ACTIVITIES.
 10) NO SMOKING SIGNS ARE TO BE PLACED
 WITHIN THE BUILDING DURING DEMOLITION
 ACTIVITIES.
 11) COMBUSTIBLE WASTE AND TRASH. THESE
 MATERIALS ARE NOT ALLOWED TO ACCUMULATE
 WITHIN OR OUTSIDE THE BUILDING.
 12) ADEQUATE FIRE WATCH AND SECURITY
 PROTECTION ARE TO BE PROVIDED FOR THE
 SITE.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop HIST HISTORICAL
Rev No 1 Status N Date 2002-02-15 Cont ID  
Sent By lmartine Date 2002-02-15 Time 15:50 Rev Time 1.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-02-14 Cont ID  
Sent By pkrauss Date 2002-02-14 Time 15:33 Rev Time 0.45
Received By pkrauss Date 2002-02-14 Time 15:31 Sent To  
Notes
2002-02-14 00:00:00 
  
 MECHANICAL PERMIT REQUIRED.

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-02-13 Cont ID  
Sent By kstevens Date 2002-02-13 Time 16:15 Rev Time 1.50
Received By kstevens Date 2002-02-13 Time 16:15 Sent To  
Notes
2002-02-13 00:00:00PASSED/PROVISO
  
 SEPARATE PLUMBING PERMIT REQUIRED. -
 DEMO SHEET FROM DEMO CONTRACTOR SHALL
 ACCOMPANY PERMIT APPLICATION - IT WILL
 BE ATTACHED TO PERMIT WHEN ISSUED AND
 INSPECTOR SHALL FILE WHEN INSPECTION
 FINISHED.

Review Stop Z ZONING
Rev No 1 Status P Date 2002-02-04 Cont ID  
Sent By dpalmer Date 2002-02-04 Time 06:54 Rev Time 0.00
Received By dpalmer Date   Time   Sent To  
Notes
2002-02-04 00:00:00OK PER SG. 2/1/02