| 2002-02-06 00:00:00 | 1) PLEASE PROVIDE THIS OFFICE A WRITTEN |
| | PLAN ON HOW THE BUILDING WILL BE |
| | DEMOLISHED. SINCE THE BUILDING CONTAINS |
| | A LARGE AMOUNT OF COMBUSTIBLE MATERIAL |
| | THE FIRE SPRINKLER SYSTEM IS TO REMAIN |
| | ACTIVE UNTIL SUCH TIME AS THE |
| | COMBUSTIBLE MATERIAL IS REMOVED FROM THE |
| | BUILDING. |
| | 2) THE FIRE SPRINKLER SYSTEM IS NOT TO |
| | BE DEMOLISHED UNTIL APPROVAL IS GRANTED |
| | BY THE CITY FIRE MARSHAL AND THE |
| | DIRECTOR OF CONSTRUCTION SERVICES. |
| | 3) ADEQUATE MEANS OF EGRESS ARE TO BE |
| | PROVIDED DURING DEMOLITION ACTIVITIES. |
| | 4) DEMOLITION ACTIVITIES ARE TO BE |
| | CONDUCTED IN ACCORDANCE WITH NFPA 241, |
| | THE STANDARD FOR SAFEGUARDING, |
| | CONSTRUCTION, ALTERATION AND DEMOLITION |
| | OPERATIONS, 1996 EDITION. |
| | 5) NO HOT WORK IS TO PERFORMED IN THE |
| | BUILDING UNTIL APPROVED BY THE FIRE |
| | PREVENTION BUREAU IN ACCORDANCE WITH |
| | NFPA 51 B, THE STANDARD FOR FIRE |
| | PREVENTION DURING CUTTING, WELDING AND |
| | OTHER HOT WORK, 1999 EDITION. |
| | 6) PORTABLE FIRE EXTINGUISHERS ARE TO |
| | REMAIN ON SITE DURING DEMOLITION |
| | ACTIVITIES. |
| | 7) NO FIRE HYDRANTS ARE TO BE OBSTRUCTED |
| | BY DEMOLITION MATERIAL OR EQUIPMENT. |
| | 8) NO FUEL TANKS ARE TO BE PLACED ON |
| | THE SITE WITHOUT APPROVAL OF THE |
| | FIRE PREVENTION BUREAU. |
| | 9) NO FLAMMABLE LIQUIDS OR GASES ARE |
| | TO BE STORED WITHIN THE BUILDING |
| | DURING DEMOLITION ACTIVITIES. |
| | 10) NO SMOKING SIGNS ARE TO BE PLACED |
| | WITHIN THE BUILDING DURING DEMOLITION |
| | ACTIVITIES. |
| | 11) COMBUSTIBLE WASTE AND TRASH. THESE |
| | MATERIALS ARE NOT ALLOWED TO ACCUMULATE |
| | WITHIN OR OUTSIDE THE BUILDING. |
| | 12) ADEQUATE FIRE WATCH AND SECURITY |
| | PROTECTION ARE TO BE PROVIDED FOR THE |
| | SITE. |
| | |