Plan Review Details - Permit 02011428
Plan Review Stops For Permit 02011428
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-03-11 Cont ID  
Sent By rbrown Date 2002-03-11 Time 09:54 Rev Time 0.00
Received By rbrown Date 2002-03-11 Time 09:54 Sent To  
Notes
2002-03-11 00:00:00BUILDING PLAN REVIEW
 ******PROVISO*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 --PROVISO--
 A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-02-11 Cont ID  
Sent By rbrown Date 2002-02-11 Time 11:17 Rev Time 0.00
Received By rbrown Date 2002-02-11 Time 11:17 Sent To  
Notes
2002-02-11 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 THE PLANS MAKE REFERENCE TO STANDARD
 BUILDING CODE 1997 AND HAVE THEREFOR
 BEEN REVIEWED FOR COMPLIANCE WITH THAT
 CODE.
  
 SBC = STANDARD BUILDING CODE 1997
 SBC*= STANDARD BUILD'G CODE (CITY AMEND)
 FL ACC CODE = FLORIDA ACCESSIBILITY CODE
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) SBC 1004.1.2THE REAR DOOR (NO. 12)
 MAY BE REQUIRED AS AN EXIT IF THE TRAVEL
 DISTANCE WOULD OTHERWISE EXCEED 75' (SEE
 COMMENT 5, BELOW).IF SO, THE EXIT MUST
 NOT BE OBSTRUCTED BY FURNITURE, AS IS
 IMPLIED BY THE ROOM 112 LAYOUT.ALSO,
 EXIT SIGNS WOULD BE REQUIRED IN ORDER TO
 SUIT THE PROVISON OF AN ADDITIONAL EXIT.
  
 3) SBC 1012.1.7MEANS OF EGRESS DOORS.
 WITH REFERENCE TO COMMENT (2) ABOVE,
 DOORS 02, 03 AND 06 SHALL BE OPENABLE
 WITHOUT THE USE OF A KEY IN ORDER TO
 PROVIDE ACCESS TO THE REAR EXIT DOOR
 (NO. 12).
  
 4) SBC* 104.2 NEW SLAB, SHEETS A-1 & P-1
 SUBMIT DETAILS TO DESCRIBE THE SUBGRADE
 MAKE-UP UNDER THE AREA OF NEW FLOOR SLAB
 AT THE REAR OF THE PREMISES.
  
 5) FL ACC CODE 4.1.6(1)(A) AND 4.13(1).
 SHEET A-1, FLOOR PLAN.WHAT IS
 REPRESENTED BY THE TWO CONCENTRIC LINES
 WHICH ARE APPROXIMATELY MIDWAY BETWEEN
 R4'-11" AND R10'-4"?A MINIMUM CLEAR
 WIDTH OF 36" IS REQUIRED BETWEEN THE
 CHAIRS/TABLES, SHOWN EACH SIDE OF THE
 RECEPTION DESK, AND THE NEAREST
 OBSTRUCTION.ANNOTATE PLANS TO CLARIFY.
  
 6) FL ACC CODE 4.15.2DRINKING FOUNTAIN
 SPOUT HEIGHT.THE DIMENSIONS ON
 SHEET A-3 STATE THAT THE SPOUT HEIGHT IS
 36" MIN. ABOVE FLOOR, THIS SHOULD READ
 36" MAX. AS SHOWN ON FIGURE 27.
  
 7) FL ACC CODE 4.19.3CLEAR FLOOR SPACE
 AT SINK.THE DIMENSIONS ON SHEET A-3
 SHOW THE FRONT EDGE OF THE SINK AND THE
 EXTENT OF THE REQUIRED FLOOR SPACE AS
 BEING 19" MAX. AND 48" MIN. RESPECTIVELY
 MEASURED FROM THE WALL.THE DIMENSIONS
 SHOULD BE MEASURED FROM THE KNEE
 CLEARANCE LIMIT AS SHOWN ON FIGURE 32.
 ALSO, THE TOE CLEARANCE AND KNEE
 CLEARANCEARE SHOWN AS 8" MAX. AND
 6" MIN. RESPECTIVELY.THESE DIMENSIONS
 SHOULD BE 6" MAX. AND 8" MIN. AS SHOWN
 ON FIGURE 31.
  
 8)FL ACC CODE 4.16.4WATER CLOSET
 GRAB BARS.THE DIMENSIONS AN SHEET A-3,
 FOR THE GRAB BAR BEHIND THE W.C., SHALL
 BE AMENDED TO SHOW 12" MIN. BETWEEN THE
 CENTER LINE OF THE W.C. AND THE ENDS OF
 THE GRAB BAR AS SHOWN ON FIGURE 29.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUERIES PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2002-06-24 Cont ID  
Sent By btrobaug Date 2002-06-24 Time 13:08 Rev Time 0.00
Received By btrobaug Date 2002-06-24 Time 12:43 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2002-05-14 Cont ID  
Sent By btrobaug Date 2002-05-14 Time 16:55 Rev Time 0.00
Received By btrobaug Date 2002-05-14 Time 16:54 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-03-07 Cont ID  
Sent By dpalmer Date 2002-03-07 Time 16:55 Rev Time 0.00
Received By dpalmer Date 2002-03-07 Time 16:55 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-02-06 Cont ID  
Sent By dpalmer Date 2002-02-06 Time 19:45 Rev Time 0.00
Received By dpalmer Date 2002-02-06 Time 19:41 Sent To  
Notes
2002-02-06 00:00:00**************** UNSAT **************
  
 1)NOTE: PLEASE CLARIFY SHOW WINDOW
 OUTLETS PER 210-62. /220-12A
  
 2)NOTE: PLEASE NOTE MISSING LOAD
 CALCULATIONS PER 220-3,220-10,220-11,
 220-13 AND THEN CONTINUOUS LOADS AT 125%
  
  
 3)NOTE: PLEASE SHOW TRACK LIGHTING LOAD
 CALCUALTIONS PER 220-12B
  
 4)NOTE: PLEASE CLARIFY IF SERVICE IS
 NEW OR EXISITNG? PLEASE NOTE THAT NOTE
 ON RIGHT HAND CORNER OF RISER DIAGRAM
 SAYS "EXISTING" SERVICE? PLEASE CLARIFY.
  
 5)NOTE: PLEASE NOTE MISSING EQUIPMENT
 GROUNDING CONDUCTOR BETWEEN MAIN
 DISCONNECT AND PANEL. 250-122
  
 6)NOTE: PLEASE CLARIFY 320' SHOWN FROM
 METER TO PANEL FOR VOLTAGE DROP.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-03-07 Cont ID  
Sent By mcarsill Date 2002-03-07 Time 11:30 Rev Time 0.00
Received By mcarsill Date 2002-03-07 Time 11:30 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-02-13 Cont ID  
Sent By mcarsill Date 2002-02-13 Time 14:50 Rev Time 0.00
Received By mcarsill Date 2002-02-13 Time 14:50 Sent To  
Notes
2002-02-13 00:00:001) PLEASE INDICATE RATING OF DEMISING
 WALLS ON PLANS.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-03-18 Cont ID  
Sent By pkrauss Date 2002-03-18 Time 13:28 Rev Time 0.35
Received By pkrauss Date 2002-03-18 Time 13:14 Sent To  
Notes
2002-03-18 00:00:00MECHANICAL PERMIT 02011430

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-02-13 Cont ID  
Sent By pkrauss Date 2002-02-13 Time 13:42 Rev Time 0.40
Received By pkrauss Date 2002-02-13 Time 13:40 Sent To  
Notes
2002-02-13 00:00:00*******************DENIED***************
  
  
 1.PROVIDE OUTSIDE AIR CALCULATIONS AS
 PER ASHRAE 63-89.
  
 2.FAN SHUTDOWN BY DUCT SMOKE DETECTOR
 WITH NOTIFICATION TO ALARM/STROBE IN
 NORMALLY OCCUPIED AREAS AS PER 1997
 SMC 406.1 & NFPA 90A 4-4.4.3.
  
 3.CONDENSATE DRAIN IS NOT ADDRESSED
 ON PLAN.PLEASE INDICATE LINE SIZE,
 MATERIAL AND TERMINATION ON PLAN.
 SHALL COMPLY WITH COUNTYWIDE AMMEND-
 MENTS 1994 SPC 804.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 3 Status P Date 2002-03-26 Cont ID  
Sent By kstevens Date 2002-03-26 Time 15:00 Rev Time 0.00
Received By kstevens Date 2002-03-26 Time 14:59 Sent To  
Notes
2002-03-26 00:00:00PASSED/PROVISO
 REFERENCE: SPC-94 - FACBC-97
  
 WATER HEATER SHALL BE IN SEPARATE CLOSET
 FROM STORAGE. PER NEC-99 SEC 422.17

Review Stop P PLUMBING
Rev No 2 Status F Date 2002-03-06 Cont ID  
Sent By kstevens Date 2002-03-06 Time 19:53 Rev Time 0.50
Received By kstevens Date 2002-03-06 Time 19:53 Sent To  
Notes
2002-03-06 00:00:00DENIED
 REFERENCE: SPC-94-FACBC-97
  
 1) WATER HEATERS LOCATED IN CEILING OR
 ON A SHELF SHALL HAVE A PERMINATE SHIPS
 LADDER INSTALLED. SEC 501.7
  
 2) HEATER PANS SHALL HAVE A 1" PAN DRAIN
 MINIMUM. SPC SEC 507.8.2
  
 3) SERVICE PLATFORM REQUIRED FOR HEATER
 IN CEILING. MIMIMUM 30"X30"REQUIRED
 AT SERVICE SIDE OF HEATER. SMC-97 SEC
 304.4.1
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-02-11 Cont ID  
Sent By kstevens Date 2002-02-11 Time 16:03 Rev Time 1.25
Received By kstevens Date 2002-02-11 Time 16:03 Sent To  
Notes
2002-02-11 00:00:00DENIED
 REFERENCE: SPC-94-FACBC-97
  
 1) SHT A-3 DRINKING FOUNTAIN DETAIL,
 CHANGE SPOUT HEIGHT TO READ MAX 36" PER
 FACBC SEC 4.15.3
 2) SHT A-3 IF SINGLE DRINKING FOUNTAIN
 PROVISIONS SHALL BE PROVIDED FOR THOSE
 WHO HAVE DIFFICULITY BENDING OR STOOPING
 PER FACBC SEC 4.1.3(10)
 3) SHT P-1 WATER RISER DIAGRAM. PLEASE
 PROVIDE MANUFACTURE INFORMATION SHEETS
 FOR ALL POINT OF USE WATER HEATERS. SHOW
 LISTINGS AND APPROVALS FOR W/HEATERS
 4) SHT A-3 BREAK ROOM SINK. PLEASE SHOW
 COMPLIANCE FOR FACBC SEC 4.24. GIVE DE-
 TAILS FOR ALL SUBSECTIONS OF SECT 4.24
 ON PLANS.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8733