Plan Review Details - Permit 02011399
| Plan Review Stops For Permit 02011399 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2002-07-25 |
|
|
Cont ID |
|
| Sent By |
lsmith |
Date |
2002-07-25 |
Time |
09:24 |
Rev Time |
0.50 |
| Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2002-06-18 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-07-17 |
Time |
18:03 |
Rev Time |
0.75 |
| Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-06-18 00:00:00 | ***************FAILED REVISION********* | | | | | | 1. REVISED DRAWINGS NEED TO BE CLOUDED | | | OR TRIANGLE TO SHOW CHANGES. | | | | | | 2. VALUE OF PERMIT NEEDS TO BE ADJUSTED | | | TO SHOW ADDITION OF HEATER & NEW WORK. | | | FEES NEED TO BE PAID TO REFLECT CHANGES | | | | | | 3. SEE ELECTRICAL NOTES ATTACHED FOR | | | FAILED ELECTRICAL REVIEW. | | | | | | ANY QUESTIONS PLEASE CALL: | | | LEA SMITH, BUILDING PLAN EXAMINER | | | 659-8096 EXT. 8394 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2002-02-06 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-05-22 |
Time |
11:44 |
Rev Time |
0.75 |
| Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2002-07-17 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-07-17 |
Time |
18:03 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2002-07-17 |
Time |
17:50 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2002-05-22 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-05-22 |
Time |
11:44 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2002-05-22 |
Time |
11:43 |
Sent To |
B |
|
| Notes |
| 2002-05-22 00:00:00 | UNSAT | | | ~~~~~ | | | PLEASE PROVIDE A LOAD CALCULATION FOR | | | THE SERVICE THAT IS TO FEED THE | | | ADDITIONAL EQUIPMENT,ALONG WITH WIRE | | | AND OCP SIZE OF THE BRANCH CIRCUIT | | | SUPPLYING SAME,AND A TOTAL CALCULATION | | | INCLUDING THE ADDED LOAD. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL; | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | 561/659-8096 EXT. 8392 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2002-02-05 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-02-05 |
Time |
07:36 |
Rev Time |
0.25 |
| Received By |
btrobaug |
Date |
2002-02-05 |
Time |
07:29 |
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2002-02-03 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-02-05 |
Time |
07:37 |
Rev Time |
1.00 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-02-03 00:00:00 | PLUMBING PLAN REVIEW, FBC 2001.PES |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2002-01-30 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2002-01-30 |
Time |
11:18 |
Rev Time |
0.25 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
|