Plan Review Details - Permit 02011349
Plan Review Stops For Permit 02011349
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-03-27 Cont ID  
Sent By rbrown Date 2002-03-14 Time 19:27 Rev Time 0.00
Received By rbrown Date 2002-03-14 Time 19:26 Sent To  
Notes
2002-03-14 00:00:00BUILDING PLAN REVIEW
 ******PROVISO*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 SBC = STANDARD BUILDING CODE 1997
 SBC*= STANDARD BUILD'G CODE (CITY AMEND)
  
 --PROVISO--SBC*104.1.1A SEPARATE
 PERMIT APPLICATION WILL BE REQUIRED FOR
 THE NEW CANOPY

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-02-07 Cont ID  
Sent By rbrown Date 2002-02-07 Time 18:47 Rev Time 0.00
Received By rbrown Date 2002-02-07 Time 18:47 Sent To  
Notes
2002-02-07 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 NIETHER STANDARD BUILDING CODE 1997 OR
 FLORIDA BUILDING CODE 2001 ARE STATED ON
 THE PLANS.THE PLANS HAVE BEEN REVIEWED
 FOR COMPLIANCE WITH STANDARD BUILDING
 CODE 1997 AS PER TELEPHONE CONVERSATION
 WITH MPA ARCHITECTS', RICHARD LOGAN
  
 SBC = STANDARD BUILDING CODE 1997
 SBC*= STANDARD BUILD'G CODE (CITY AMEND)
  
 1) SBC* 104.1.1A SEPARATE PERMIT
 APPLICATION WILL BE REQUIRED FOR THE NEW
 CANOPY.
  
 2) SBC 1012.4HORIZONTAL SLIDING DOORS
 IN A MEANS OF EGRESS.THE AUTOMATIC
 SLIDING ENTRANCE DOORS SHALL COMPLY WITH
 THE REQUIREMENTS, STATED IN THE CODE,
 FOR SLIDING DOORS IN A MEANS OF EGRESS.
  
 3) SBC* 104.2STAIRCASE/ELEVATOR LOBBY.
 SUBMIT DETAILS TO DESCRIBE THE FINISHED
 FLOOR LEVELS, IN THIS AREA, FOLLOWING
 REMOVAL OF THE EXISTING RAMP BETWEEN THE
 STAIRCASE AND THE ELEVATOR LOBBY.
  
 4) SBC* 1606.4 AND SBC 2405NEW STORE-
 FRONT.THE PLANS STATE THAT 1/4" THICK
 TEMPERED GLASS IS TO BE USED BUT, TO
 COMPLY WITH THE CONDITIONS OF THE
 PRODUCT APPROVAL, THE GLASS SHALL BE
 9/16" THICK LAMINATED GLASS (0.09 INTER-
 LAYER BETWEEN TWO LAYERS OF 1/4" THICK
 HEAT STRENGTHENEND GLASS).AMEND THE
 PLANS TO AVOID CONFUSION.
  
 5) SBC 2405SHEET A-6, DOOR SCHEDULE.
 ANY GLAZING IN DOORS, INLUDING THE
 ELEVATOR DOOR AND ADJACENT GLAZED PANEL,
 IS IN A 'HAZARDOUS LOCATION' AND IS
 REQUIRED TO BE SAFETY GLASS SATISFYING
 THE REQUIREMENTS OF THE CONSUMER PRODUCT
 SAFETY COMMISSION 16, CODE OF FEDERAL
 REGULATIONS, PART 1201 (CPSC 16-CFR,
 PART 1201).SUBMIT DETAILS TO
 DEMONSTRATE COMPLIANCE.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUERIES PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2002-07-29 Cont ID  
Sent By dpalmer Date 2002-07-29 Time 06:31 Rev Time 0.00
Received By dpalmer Date 2002-07-29 Time 06:23 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-03-19 Cont ID  
Sent By dpalmer Date 2002-03-19 Time 19:53 Rev Time 0.00
Received By dpalmer Date 2002-03-19 Time 19:53 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-02-05 Cont ID  
Sent By dpalmer Date 2002-02-05 Time 19:09 Rev Time 0.00
Received By dpalmer Date 2002-02-05 Time 19:09 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-03-19 Cont ID  
Sent By mcarsill Date 2002-03-19 Time 17:13 Rev Time 0.00
Received By mcarsill Date 2002-03-19 Time 17:13 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-01-29 Cont ID  
Sent By mcarsill Date 2002-01-29 Time 15:42 Rev Time 0.00
Received By mcarsill Date 2002-01-29 Time 15:42 Sent To  
Notes
2002-01-29 00:00:001) DOOR 100 TO COMPLY WITH THE FLORIDA
 FIRE PREVENTION CODE, NFPA 101, THE
 LIFE SAFETY CODE, 2000 EDITION, SECTION
 7.2.1.9.
 2) PLEASE INDICATE INTERIOR FLOOR FINISH
 IN CORRIDORS AND EXITS.
 3) PLEASE INDICATE LOCATIONS OF PORTABLE
 FIRE EXTINGUISHERS.
 4) NO FIRE SPRINKLER DRAWINGS PROVIDED.
 5) ADDITIONAL EXIT SIGNS REQUIRED TO
 DIRECT PERSONS TO THE REAR EXITS.
 6) NEW CANVAS CANOPY TO BE FIRE
 RETARDANT.
 7) PLEASE INDICATE LOCATIONS OF PORTABLE
 FIRE EXTINGUISHERS.
 8) SEPARATE PLANS AND PERMITS REQUIRED
 FOR FIRE ALARM REMODEL.
 9) BUILDING ADDRESS REQUIRED.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-03-26 Cont ID  
Sent By pkrauss Date 2002-03-26 Time 07:29 Rev Time 0.35
Received By pkrauss Date 2002-03-26 Time 07:29 Sent To  
Notes
2002-03-26 00:00:00MECHANICAL PERMIT 02011381

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-02-14 Cont ID  
Sent By pkrauss Date 2002-02-14 Time 08:59 Rev Time 1.00
Received By pkrauss Date 2002-02-14 Time 08:59 Sent To  
Notes
2002-02-14 00:00:00*******************DENIED***************
  
 PLANS RVIEWED UNDER THE 1997 STANDARD
 MECHANICAL & BUILDING CODE.
  
 1.PROVIDE OUTSIDE AIR CALCULATIONS
 AS PER ASHRAE 62-89.
  
 2.PROVIDE AIR BALANCE SCHEDULE SHOWING
 COMPLIANCE WITH 1997 SMC 501.2.
  
 3.PLEASE INDICATE THE THE FIRE
 RESISTANCE RATING OF THE MECHANICAL
 ROOM.
  
 4.IDENTIFY LOCATION OF ALL FIRE
 DAMPERS ON PLAN AS PER 1997 SMC
 610.6.
  
 NO COMBUSTIBLES ABOVE THE CEILING IN THE
 RETURN AIR PLENUM.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-04-02 Cont ID  
Sent By kstevens Date 2002-04-02 Time 13:01 Rev Time 0.00
Received By kstevens Date 2002-04-02 Time 13:01 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-02-11 Cont ID  
Sent By kstevens Date 2002-02-11 Time 09:39 Rev Time 0.50
Received By kstevens Date 2002-02-11 Time 09:39 Sent To  
Notes
2002-02-11 00:00:00DENIED
 REFERENCE: SPC-94-FACBC-97
  
 1) SHT A-2 DOOR SHALL NOT SWING INTO
 CLEAR FLOOR SPACE OR TURNING RADIUS PER
 FACBC SECS 4.22.2 & 4.22.3
 2) SHT P-1 SANITARY RISER DIAGRAM. DRINK
 ING FOUNTAIN NOT SHOWN ON RISER DIAGRAM.
 3) SHT P-1 PLEASE PROVIDE A WATER RISER
 DIAGRAM. SHOW PIPE SIZE AND LOCATION
 OF WATER HAMMER ARRESTORS. ARRESTORS
 SHALL BE LOCATED NEAR FIXTURES IN AN
 "EFFECTIVE RANGE" AND NOT AT TOP OF DROP
 4) SHT P-1 PLEASE INDICATE HOW CONDEN-
 SATE WILL TERMINATE OUTSIDE OF BLDG. IF
 TIED INTO A DRYWELL OR STORM A RELIEF
 VENT SHALL BE INSTALLED IN DRAIN LINE
 WHERE IT EXITS BLDG. PLEASE SHOW DETAIL
 WITH CONDENSATE RISER DIAGRAM.
  
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377.

Review Stop Z ZONING
Rev No 3 Status P Date 2002-04-05 Cont ID  
Sent By sgraham Date 2002-04-05 Time 13:56 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2002-03-14 Cont ID  
Sent By sgraham Date 2002-03-14 Time 08:27 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
2002-03-14 00:00:00DENIED NO TINT ON WINDOWS AS PER
 J.MINICOZZI

Review Stop Z ZONING
Rev No 1 Status F Date 2002-01-28 Cont ID  
Sent By sgraham Date 2002-01-28 Time 15:38 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
2002-01-28 00:00:00DENIED BY ZONING, NO TINTING OF WINDOWS
 IN DMP 01-28-02JMINICOZZI