Plan Review Details - Permit 02011267
Plan Review Stops For Permit 02011267
Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2002-01-24 Cont ID  
Sent By mcarsill Date 2002-01-24 Time 14:27 Rev Time 0.00
Received By mcarsill Date 2002-01-24 Time 14:27 Sent To  
Notes
***NONE***

Review Stop FS  
Rev No 2 Status P Date 2002-02-22 Cont ID  
Sent By mcarsill Date 2002-02-22 Time 09:05 Rev Time 0.00
Received By mcarsill Date 2002-02-22 Time 09:05 Sent To  
Notes
2002-02-22 00:00:00A) RED LINE ON PLAN INDICATES THAT A
 PORTION OF THE UNDERGROUND FIRE LINE
 WILL BE LOCATED UNDER THE BUILDING. THIS
 IS NOT ALLOWED BY CODE AND WILL NOT
 BE PERMITTED TO BE DONE IN THIS MANNER.
 PLEASE ENSURE THAT THE FIRE LINE IS
 NOT LOCATED UNDER THE BUILDING.
 B) BACKFLOW DEVICE REQUIRED TO HAVE
 TAMPER SWITCHES, LOCKS AND CHAINS.
 C) SPARE SPRINKLER HEAD BOX AND WRENCH
 REQUIRED.
  
 APPROVED PROVISO:
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop FS  
Rev No 1 Status P Date 2002-01-24 Cont ID  
Sent By mcarsill Date 2002-01-24 Time 14:28 Rev Time 0.00
Received By mcarsill Date 2002-01-24 Time 14:27 Sent To  
Notes
2002-01-24 00:00:001) BACKFLOW DEVICE REQUIRES TAMPER
 SWITCHES, CHAIN AND LOCK.
 2) CONTROL VALVE NEEDED FOR RISER.
 3) PROVIDE THRUST BLOCKS WHERE REQUIRED.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2002-01-24 Cont ID  
Sent By mcarsill Date 2002-01-24 Time 14:28 Rev Time 0.00
Received By mcarsill Date 2002-01-24 Time 14:28 Sent To  
Notes
***NONE***