| Plan Review Stops For Permit 02011166 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2002-01-24 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-01-24 |
Time |
17:22 |
Rev Time |
0.33 |
| Received By |
btrobaug |
Date |
2002-01-24 |
Time |
17:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2002-01-24 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-01-24 |
Time |
16:57 |
Rev Time |
0.25 |
| Received By |
btrobaug |
Date |
2002-01-24 |
Time |
16:45 |
Sent To |
|
|
| Notes |
| 2002-01-24 00:00:00 | ****************UNSAT!****************** | | | | | | PLEASE PROVIDE THE A.I.C. RATING AT THE | | | FIRST MEANS OF DISCONNECT,NOT AT THE | | | TRANSFORMER.PLEASE CALCULATE AND | | | RESUBMIT SAME. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | (561) 659-8096 EXT.8392 |
|
|
|