Plan Review Details - Permit 02011116
Plan Review Stops For Permit 02011116
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-03-29 Cont ID  
Sent By rbrown Date 2002-03-29 Time 15:35 Rev Time 0.00
Received By rbrown Date 2002-03-29 Time 15:35 Sent To  
Notes
2002-03-29 00:00:00BUILDING PLAN REVIEW
 ******PROVISO*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 FL ACC CODE = FLORIDA ACCESSIBILITY CODE
  
 --PROVISO--
 FL ACC CODE 4.19 THE WASH BASIN/LAVATORY
 SHALL HAVE CLEARANCES AND FIXTURE HEIGHT
 TO COMPLY WITH FL ACC CODE, FIG. 31 & 32
 (ATTACHED)

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-02-06 Cont ID  
Sent By rbrown Date 2002-02-06 Time 10:59 Rev Time 0.00
Received By rbrown Date 2002-02-06 Time 10:59 Sent To  
Notes
2002-02-06 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 THE PLANS MAKE REFERENCE TO THE STANDARD
 BUILDING CODE 1997 AND HAVE THEREFOR
 BEEN REVIEWED FOR COMPLIANCE WITH THAT
 CODE
  
 SBC = STANDARD BUILDING CODE 1997
 SBC*= STANDARD BUILD'G CODE (CITY AMEND)
 FL ACC CODE = FLORIDA ACCESSIBILITY CODE
  
 1) THE PLANS DO NOT STATE THE LAST USE
 OF THIS UNIT.THE PLANS SHOULD BE TAKEN
 TO PALM BEACH COUNTY TO DETERMINE IF
 IMPACT FEES MUST BE PAID, PLANS STAMPED
 BY THEM AND A COPY OF THE RECEIPT
 SUBMITTED TO THE CITY WEST PALM BEACH
 DEPARTMENT OF CONSTRUCTION SERVICES
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) SBC* 104.2THE PLANS SHOW SEATING
 AND TABLES EVENTHOUGH THE DEPARTMENT OF
 PROFESSIONAL REGULATION, DIVISION OF
 HOTELS AND RESTAURANT PLAN REVIEW
 APPROVAL LETTER, DATED 12/21/2001,
 INCLUDES A PROVISO THAT NO SEATING SHALL
 BE PROVIDED (TAKEOUT ONLY).CLARIFY
 PROPOSALS.
  
 4) FL ACC CODE 4.19 & 4.16 THE LAVATORY/
 SINK IN THE ACCESSIBLE TOILET SHALL HAVE
 CLEARANCES AND FIXTURE HEIGHT AS SHOWN
 IN FIGURES 31 AND 32.ALSO, THE
 DIMENSIONS ON THE WATER CLOSET AND GRAB
 BAR DETAILS ARE TOO SMALL TO BE LEGIBLE.
 AMEND THE PLANS TO DEMONSTRATE
 COMPLIANCE.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUERIES PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-02-01 Cont ID  
Sent By dpalmer Date 2002-02-01 Time 12:51 Rev Time 0.00
Received By dpalmer Date 2002-02-01 Time 12:51 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-03-28 Cont ID  
Sent By mcarsill Date 2002-03-28 Time 16:11 Rev Time 0.00
Received By mcarsill Date 2002-03-28 Time 16:11 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-01-23 Cont ID  
Sent By mcarsill Date 2002-01-23 Time 12:26 Rev Time 0.00
Received By mcarsill Date 2002-01-23 Time 12:26 Sent To  
Notes
2002-01-23 00:00:001) PLEASE PROVIDE INTERIOR FINISH
 CLASSIFICATION INFORMATION FOR THE
 WALLS AND CEILINGS.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2002-02-07 Cont ID  
Sent By pkrauss Date 2002-02-07 Time 11:35 Rev Time 0.45
Received By pkrauss Date 2002-02-07 Time 11:35 Sent To  
Notes
2002-02-07 00:00:00 
 NO MECHANICAL PLANS SUBMITTED WITH THIS
 PERMIT.PLEASE PROVIDE PLANS WITH
 MECHANICAL PERMIT APPLICATION.
  
 PLEASE NOTE:
  
 ADDITIONAL PERMITS REQUIRED FOR HOOD,
 FIRE SUPRESSION, GAS, AND WALK-IN
 COOLERS.PROVIDE PLANS AND MANUFACTURE
 SUBMITTAL DATA WITH PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 3 Status P Date 2002-05-03 Cont ID  
Sent By kstevens Date 2002-05-03 Time 11:42 Rev Time 0.00
Received By kstevens Date 2002-05-03 Time 11:42 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2002-04-19 Cont ID  
Sent By kstevens Date 2002-04-19 Time 10:12 Rev Time 0.00
Received By kstevens Date 2002-04-19 Time 10:12 Sent To  
Notes
2002-04-19 00:00:00DENIED
 REFERENCE: SPC-94-FACBC-97
  
 1) PLANS SHALL BE REVIEWED BY DEPT. OF
 BUSINESS REGULATION HOTEL AND RESTURANT
 DIVISION. PLANS SHALL BE STAMPED AND
 REVIEW SHEETS SHALL BE ATTACHED TO PLANS
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-02-02 Cont ID  
Sent By kstevens Date 2002-02-02 Time 09:11 Rev Time 1.25
Received By kstevens Date 2002-02-02 Time 09:11 Sent To  
Notes
2002-02-02 00:00:00DENIED
 REFERENCE: SPC-94 - SGC-97 - FACBC-97
  
 1) SHT AF-1 GREASE TRAP. PLEASE CONTACT
 RODNEY COMPO, ENVIRONMENTAL COMPLIANCE
 (561) 837-4074 FOR GREASE TRAP SIZE.
 WASTE ORD. #2938-96
 2) SEPARATE PERMIT REQUIRED FOR GREASE
 TRAP. PROVIDER OF GREASE TRAP NOT PLUMB-
 ING CONTRACTOR TO APPLY FOR PERMIT.
 3) SHT PG-1 DRAIN ISOMETRIC/DRAIN LAYOUT
 HUB DRAINS NOT APPROVED. ALL INDIRECT
 WASTE TO DRAIN TO FLOOR SINKS. SPC SEC
 804.1 & 804.5
 4) SHT PG-1 FLOOR DRAIN WITH TRAP PRIMER
 REQUIRED IN PUBLIC TOILET ROOM. SPC SEC
 409.4.1.1.
 5) BACKFLOW REQUIRED ON WATER SERVICE.
 6) SHT AF-1 PLEASE SHOW CLEAR FLOOR
 SPACE AND TURNING RADIUS IN PLUBLC REST
 ROOM.
 7) LETTER FROM DEPT. OF BUSINESS AND PRO
 FESSIONAL REGULATION STATES IN NOTE #2
 NO SEATING, TAKE OUT ONLY. PLANS STATE
 "SALES - SEATING AREA" AND SHOW SEATING.
 PLEASE CLARIFY.
 8) SEPARATE GAS PERMIT REQUIRED. SEE
 SUBSECTIONS FOR GAS PERMIT APPLICATION
 REQUIREMENTS.
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER STANDARD
 GAS CODE.
 3. TYPE OF GAS, (LP OR NATURAL)
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 THE STANDARD GAS CODE SEC. 305.4(I).
 7. INDICATE THE DELIVERY PRESSURE (PSI)
 PER STANDARD GAS CODE SEC. 305.2. IF
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 8. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER THE STANDARD GAS CODE SECS
 602 THRU 612.
 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 STANDARD GAS CODE SEC. 402.
 10. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 11. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
 12. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
 9) PLANS SUBMITTED FOR PLAN REVIEW DO
 NOT HAVE DBPR DIV. OF HOTELS AND RESTUR-
 ANTS APPLICATION ATTACHED NOR ARE THE
 PLANS STAMPED "FOOD SERVICE PLAN APPROV-
 ED"PLEASE SUBMIT STAMPED PLANS WITH
 PLAN REVIEW APPLICATION FROM DIV. OF
 HOTELS AND RESTURANTS
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377