| 2002-01-29 00:00:00 | 1) WET FIRE HYDRANTS ARE REQUIRED PRIOR |
| | TO,DURING AND AFTER CONSTRUCTION. |
| | 2) FIRE HYDRANTS ARE REQUIRED BETWEEN |
| | 300-500 FEET APART. |
| | 3) A FIRE HYDRANT IS REQUIRED UPON |
| | APPROACH TO THE CLUBHOUSE. |
| | 4) CLEARANCES OF 7 1/2 FEET TO THE SIDES |
| | AND FRONT OF FIRE HYDRANTS ARE |
| | REQUIRED. A MINIMUM OF AT LEAST 4 FEET |
| | ARE REQUIRED TO THE REAR OF THE FIRE |
| | HYDRANTS. |
| | 5) THE ENTRYWAY NEAR THE CLUBHOUSE DOES |
| | NOT MEET MINIMUM FIRE CODE REQUIREMENTS. |
| | A MINIMUM WIDTH OF 20 FEET IS TO BE |
| | PROVIDED. VERTICAL CLEARANCES FOR FIRE |
| | APPARATUS TO PASS UNDERNEATH MUST BE |
| | AT LEAST 13 FEET 6 INCHES HIGH. FIRE |
| | DEPARTMENT ACCESS IS TO BE PROVIDED |
| | THRU ANY SECURITY FEATURES PLANNED. |
| | PLEASE INDICATE HOW THIS WILL BE |
| | ACCOMPLISHED. |
| | 6) ELECTRONIC SWITCHES WILL BE REQUIRED |
| | ON THE OS&Y VALVES FOR SUPERVISION |
| | PURPOSES. |
| | 7) ALL BUILDINGS SHALL HAVE AT LEAST |
| | ONE ELEVATION ACCESSIBLE TO FIRE AND |
| | PARAMEDICAL EQUIPMENT AND PROVIDE A |
| | LOAD OF AT LEAST 32 TONS. |
| | 8) VALVES ON THE FIRE LINE SHALL BE |
| | POST INDICATOR TYPE VALVES EXCEPT VALVES |
| | USED FOR SECTIONING. |
| | 9) PORTACACHERE FOR THE ALF MUST PROVIDE |
| | A VERTICAL CLEARANCE OF AT LEAST 13 FEET |
| | 6 INCHES HIGH. |
| | |