Plan Review Details - Permit 02011080
Plan Review Stops For Permit 02011080
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-02-15 Cont ID  
Sent By rbrown Date 2002-02-15 Time 12:38 Rev Time 0.00
Received By rbrown Date 2002-02-15 Time 12:38 Sent To  
Notes
2002-02-15 00:00:00BUILDING PLAN REVIEW
 ******PROVISO*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 --PROVISO--
 SUBJECT TO CONSULTATION WITH ELECTRICAL
 PLAN REVIEW ABOUT THE SCOPE OF
 DEVICE RELOCATION, A SEPARATE ELECTRICAL
 PERMIT APPLICATION MAY BE REQUIRED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-02-12 Cont ID  
Sent By rbrown Date 2002-02-12 Time 13:12 Rev Time 0.00
Received By rbrown Date 2002-02-12 Time 13:12 Sent To  
Notes
2002-02-12 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 THE PLANS DO NOT MAKE REFERENCE TO
 STANDARD BUILDING CODE 1997 AND HAVE
 THUS BEEN REVIEWED FOR COMPLIANCE WITH
 FLORIDA BUILDING CODE 2001.
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) FBC* 104.1.1A SEPARATE ELECTRICAL
 PERMIT APPLICATION IS REQUIRED.
  
 3) FBC* 104.2THE FIRST FLOOR PLAN
 SHOWS A PORCH WITH SCREENED/GLAZED SIDES
 THE NORTH (FRONT) ELEVATION DOES NOT
 REFLECT THIS.ANNOTATE THE PLAN TO
 RESOLVE THIS DISCREPANCY AND AVOID
 CONFUSION ABOUT THE EXTENT OF THE WORK.
  
 4) FBC 411.2.5GARAGE FLOOR SURFACE.
 PARKING SURFACES SHALL BE OF CONCRETE OR
 SIMILAR NONCOMBUSTIBLE AND NONABSORBENT
 MATERIALS.ANNOTATE THE PLAN TO
 DESCRIBE THE GARAGE FLOOR CONSTRUCTION.
  
 5) SBC 1707.4EXTERIOR DOOR ASSEMBLIES.
 THE SUBMITTED 'WINDSOR DOOR' GARAGE DOOR
 LITERATURE IS FOR A 'MODEL 576'.THIS
 MODEL IS NOT REFERENCED BY THE SUBMITTED
 SBCCI EVALUATION REPORT OR THE SUBMITTED
 'WINDSOR DOOR' DRAWING NO. 99-B-043
 SHEETS 1 AND 2.ANNOTATE THE PLAN, OR
 SUBMIT DETAILS, TO SHOW WHICH GARAGE
 DOOR MODEL IS TO BE USED, AND ENSURE
 THAT THE SUPPORTING DOCUMENTATION
 CORRESPONDS TO THE PROPOSED MODEL.
  
 6) FBC 13-603.1.ABC.1 & 13-202THERMAL
 INSULATION OF DOORS.IS THE BUILDING
 EITHER HEATED OR COOLED (OR BOTH) BY
 MECHANICAL MEANS.IF SO, IT IS
 CONSIDERED AS 'CONDITIONED SPACE'. THEN,
 DEPENDING WHETHER THE GARAGE IS ALSO
 'CONDITIONED SPACE', EITHER THE NEW
 GARAGE DOOR IS CONSIDERED AN 'EXTERIOR'
 DOOR OR THE NEW INTERNAL DOOR FROM THE
 GARAGE IS CONSIDERED AN 'ADJACENT' DOOR.
 ALL EXTERIOR AND ADJACENT DOORS SHALL BE
 SOLID CORE WOOD, WOOD PANEL OR INSULATED
 DOORS.HOLLOW CORE DOORS SHALL NOT BE
 USED IN EITHER 'EXTERIOR' OR 'ADJACENT'
 WALLS.ANNOTATE THE PLAN TO DESCRIBE
 THE MEANS OF HEATING/COOLING AND THE
 DOOR TYPES ASSOCIATED WITH THE GARAGE TO
 SATISFY THIS REQUIREMENT.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUERIES PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499

Review Stop Z ZONING
Rev No 1 Status P Date 2002-01-31 Cont ID  
Sent By sgraham Date 2002-01-31 Time 08:56 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***