Plan Review Details - Permit 02011041
Plan Review Stops For Permit 02011041
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2002-10-24 Cont ID  
Sent By hpiskura Date 2002-10-24 Time 09:03 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2002-10-24 00:00:00REVISIONS SUBMITTED 9/25/02

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2002-05-13 Cont ID  
Sent By hpiskura Date 2002-05-13 Time 16:04 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2002-04-22 Cont ID  
Sent By hpiskura Date 2002-04-22 Time 13:44 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2002-04-22 00:00:00SEE THE 02/14/02 LIST REGARDING IMPACT
 FEES AND FIRE PROTECTION DESIGN
 REQUIREMENTS.
  
 SHOW THE INFORMATION REQUIRED BY FBC
 1606.1.7.
  
 SHOW THE METHOD OF COMPLIANCE FOR FBC
 1606.1.4.
  
 IF TEST REPORTS AND OR NOTICE OF
 ACCEPTANCE REPORTS FOR THE DOORS,
 WINDOWS AND ROOF COVERING ARE NOT
 INCLUDED AT TIME OF PERMIT APPLICATION,
 SEPARATE PERMITS AND FEES WILL BE
 REQUIRED.
  
 PLEASE COLLATE ALL OF THE PLAN PAGES AND
 INFORMATION INTO TWO CONCISE SETS FOR
 PERMIT APPLICATIONS.REMOVE AND KEEP
 OBSOLETE OR CHANGED PAGES.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-02-14 Cont ID  
Sent By hpiskura Date 2002-02-14 Time 10:25 Rev Time 0.00
Received By hpiskura Date 2002-02-12 Time 11:21 Sent To  
Notes
2002-02-14 00:00:00PLAN REVIEW FOR 2001 FBC:
 ONE STORY, 13,400 +/- SQUARE FEET, GROUP
 M OCCUPANCY, TYPE V, FS CONSTRUCTION
 SHOWN.
  
 THE FIRE PROTECTION PLANS, (SPRINKLERS,
 ALARM, ETC.) MUST BE INCLUDED WITH THE
 PERMIT APPLICATION.SEE FBC 104.3.1.1
 #5
  
 THE PLANS SHOULD CITE THE SPECIFIC
 EDITIONS OF THE CODES AND STANDARDS
 USED IN THE DESIGN.THE FL STATE FIRE
 MARSHALL'S OFFICE HAS INVOKED NFPA
 13-99 AND THE 2000 LIFE SAFETY CODE
 (NFPA 101), AMONGST OTHERS.SEE FBC
 3501 FOR OTHERS.
  
 STRUCTURAL, SPECIFY THE WIND DESIGN
 USED1606.2 OR ASCE 7-98. SHOW THE WIND
 PRESSURES FOR THE WALLS, (COMPONENTS
 AND CLADDING), TO BE USED FOR WINDOWS
 AND DOORS.
  
 INCLUDE A DOOR AND WINDOW SCHEDULE WITH
 THE PERMIT PLANS.
  
 DETAIL 7/S7 IN REFERENCE TO SECTION 1/S7
 IS NOT CLEAR AS TO ITS IMPLEMENTATION.
 HOW ARE THE METAL STUDS FASTENED TO THE
 DOUBLE WOOD PLATE?HOW IS THE NELSON
 STUD CONNECTED TO THE WOOD PLATE?WHY
 IS A TRUSS REFERENCED?
  
 SHEET A2.3 DEPICTS THE EXTERIOR CANOPY,
 SHOW THE DRAFTSTOPPING REQUIRED BY FBC
 2305.2.4.
  
 BEFORE A PERMIT TO CONSTRUCT MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY FOR THE CITY, THE
 PERMIT PLANS STAMPED BY THAT OFFICE AND
 A COPY OF THE PAID RECEIPT ATTACHED TO
 THE PERMIT APPLICATION.

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2002-11-25 Cont ID  
Sent By dpalmer Date 2002-11-25 Time 12:49 Rev Time 0.50
Received By dpalmer Date 2002-11-25 Time 12:49 Sent To  
Notes
2002-11-25 00:00:00SITE LIGHTING REVISION.

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2002-10-01 Cont ID  
Sent By btrobaug Date 2002-11-20 Time 18:00 Rev Time 0.50
Received By dpalmer Date 2002-10-01 Time 08:13 Sent To  
Notes
2002-10-29 00:00:00NEW SHEETS BROUGHT IN.
2002-10-01 00:00:00************* UNSAT ************
  
 1)NOTE: PLEASE NOTE THAT ONLY ONE
 COMPLETE SET SUBMITTED FOR REVISIONS.
  
 PLEASE SUBMIT TWO COMPLETE SETS.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2002-07-30 Cont ID  
Sent By dpalmer Date 2002-07-30 Time 05:56 Rev Time 0.00
Received By dpalmer Date 2002-07-29 Time 16:48 Sent To  
Notes
2002-07-30 00:00:00REVISIONS, ALL PAGES.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2002-05-14 Cont ID  
Sent By dpalmer Date 2002-05-14 Time 12:55 Rev Time 0.00
Received By dpalmer Date 2002-05-14 Time 12:55 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2002-04-02 Cont ID  
Sent By dpalmer Date 2002-04-02 Time 16:38 Rev Time 0.00
Received By dpalmer Date 2002-04-02 Time 16:38 Sent To  
Notes
2002-04-02 00:00:00************* UNSAT ********************
  
 1)NOTE: PLEASE NOTE THAT NOTE #2 FROM
 FIRST REVIEW STILL NEEDS TO BE CLARIFIED
 PLANS ARE STILL SHOWING TWO DIFFERENT
 VOLTAGES FOR SERVICES.
  
 2)NOTE: PLEASE NOTE THAT ALL NEW SHEETS
 NEED TO BE INSERTED IN PLANS TO MAKE
 TWO COMPLETE SETS AND OLD SHEETS NEED TO
 COME OUT AND BE KEPT SEPARATELY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-02-08 Cont ID  
Sent By dpalmer Date 2002-02-08 Time 12:23 Rev Time 0.00
Received By dpalmer Date 2002-02-07 Time 10:16 Sent To  
Notes
2002-02-08 00:00:00************* UNSAT *************
  
 1)NOTE: PLEASE CLARIFY NOT ON E 1.2
 NOTE #6, PLEASE SEE 6'6" TO TOP OF MAIN?
 PLEASE SEE MDP SHOWN ON E 3.2 MAIN SHOWN
 AT BOTTOM OF SWITCH GEAR?
  
 2)NOTE: PLEASE CLARFIY VOLTAGE OF
 SERVICE. 3.2 MDP SHOWS 120/240. PLEASE
 SEE OTHERSHEET,2.1,3.1 ECT OTHER VOLTAGE
 -S SHOWN AT 120/208.PLEASE CLARIFY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 3 Status N Date 2002-07-24 Cont ID  
Sent By mamini Date 2002-07-24 Time 09:27 Rev Time 1.00
Received By mamini Date 2002-07-24 Time 09:27 Sent To  
Notes
2002-07-24 00:00:00N/A :
 1. SEE PERMIT # 02071558 FOR CIVIL /SITE
 WORK REVIEW AND PERMITTING.
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2002-03-26 Cont ID  
Sent By mamini Date 2002-03-26 Time 10:51 Rev Time 3.00
Received By mamini Date 2002-03-26 Time 10:51 Sent To  
Notes
2002-03-26 00:00:00PASSED WITH PROVISOS:
 1. ALL CONNECTIONS TO CITY'S SERVICES
 MUST BE APPROVED AND INSPECTED BY THE
 PUBLIC UTILITIES ENGINEERING SERVICES
 659-8040.
 2. ALL OFF STREET PARKING STALLS MUST BE
 PAINTED WITH DOUBLE 4" WHITE FOR REGULAR
 AND BLUE FOR H.C. PER FLORIDA
 ACCESSIBILITY CODE FOR BUILDING
 CONSTRUCTION.
 3. A SEPARATE PERMIT APPLICATION AND
 FEES FOR UNDERGROUND UTILITIES/SITE
 WORKS WILL BE REQUIRED AT THE TIME OF
 THE ACTUAL PERMITTING.
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2002-01-29 Cont ID  
Sent By mamini Date 2002-01-29 Time 14:31 Rev Time 3.00
Received By mamini Date 2002-01-29 Time 14:31 Sent To  
Notes
2002-01-29 00:00:00FAILED :
 1. PLEASE PROVIDE STORM WATER
 CALCULATION FOR OUR REVIEW AND APPROVAL.
 2. PLEASE PROVIDE PERVIOUS & IMPERVIOUS
 CALCULATIONS FOR THE ENTIRE SITE.
 3. ALL OFF-STREET PARKING MUST BE
 PAINTED WITH DOUBLE 4" WHITE FOR REGULAR
 AND BLUEFOR H.C. PER CITY CODE .
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2002-10-29 Cont ID  
Sent By mcarsill Date 2002-10-29 Time 14:48 Rev Time 0.00
Received By mcarsill Date 2002-10-29 Time 14:48 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2002-08-14 Cont ID  
Sent By mcarsill Date 2002-08-14 Time 10:14 Rev Time 0.00
Received By mcarsill Date 2002-08-14 Time 10:14 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2002-05-17 Cont ID  
Sent By mcarsill Date 2002-05-17 Time 13:24 Rev Time 0.00
Received By mcarsill Date 2002-05-17 Time 13:24 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2002-04-09 Cont ID  
Sent By mcarsill Date 2002-04-09 Time 14:49 Rev Time 0.00
Received By mcarsill Date 2002-04-09 Time 14:49 Sent To  
Notes
2002-04-09 00:00:00A) NO FIRE HYDRANTS SHOWN ON SITE PLAN.
 ONLY ONE HYDRANT IS SHOWN ON THE
 CONCEPTUAL PAVING AND DRAINAGE PLAN.
 PLEASE INDICATE ALL FIRE HYDRANT
 LOCATIONS WITHIN THE VICINITY OF THE
 STORE.
 B) PLEASE INDICATE THE LOCATION OF THE
 FIRE DEPARTMENT CONNECTION FOR THE
 FIRE SPRINKLER SYSTEM. THIS DEVICE
 MUST BE LOCATED WITHIN 150 FEET OF
 A FIRE HYDRANT.
 C) NO FIRE SPRINKLER DRAWINGS OR
 HYDRAULIC CALCULATIONS PROVIDED.
 D) NOT ALL PREVIOUS PLAN REVIEW COMMENTS
 HAVE BEEN ADDRESSED. PLEASE REVIEW
 INFORMATION AND MAKE THE APPROPRIATE
 COMMENTS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-02-08 Cont ID  
Sent By mcarsill Date 2002-02-08 Time 13:17 Rev Time 0.00
Received By mcarsill Date 2002-02-08 Time 13:16 Sent To  
Notes
2002-02-08 00:00:001) PLEASE BE ADVISED THAT MERCANTILE
 OCCUPANCIES ARE LOCATED IN CHAPTER 36
 OF THE FLORIDA FIRE PREVENTION CODE,
 2000 LIFE SAFETY CODE. THE REFERENCES
 TO CHAPTER 24 ARE NO LONGER APPLICABLE.
 2) HOW IS EXIT DISCHARGE ACCOMPLISHED
 THRU THE EXTERIOR TOTE STORAGE.
 3) THE FIRE SPRINKLER SYSTEM RISER
 DOES NOT INDICATE THE LOCATION OF
 THE REQUIRED FIRE DEPARTMENT CONNECTION.
 PLEASE BE ADVISED THAT THIS DEVICE MUST
 BE WITHIN 150 FEET OF A FIRE HYDRANT.
 4) PLEASE PROVIDE COMPLETE FIRE
 SPRINKLER DRAWINGS AND HYDRAULIC
 CALCULATIONS FOR THE FIRE SPRINKLER
 SYSTEM. A SEPARATE PERMIT IS REQUIRED.
 5) PLEASE PROVIDE COMPLETE FIRE ALARM
 SYSTEM DRAWINGS. CUT SHEETS, WIRING
 DIAGRAM AND BATTERY CALCULATIONS ARE
 TO BE PROVIDED. A SEPARATE PERMIT IS
 REQUIRED. A REMOTE ANNUNCIATOR APPEARS
 TO BE NEEDED.
 6) THE FIRE SPRINKLER SYSTEM AND FIRE
 ALARM SYSTEM ARE TO BE MONITORED BY
 A LICENSED UL LISTED CENTRAL STATION.
 7) HOW DOES BALER 31B AFFECT EXITING.
 8) ELECTRONIC SWITCHES,CHAIN AND LOCK
 ARE REQUIRED ON BACKFLOW DEVICE.
 9) AUTOMATIC SLIDING DOORS TO COMPLY
 WITH NFPA 101, THE LIFE SAFETY CODE,
 2000 EDITION, SECTION 7.2.1.9.1.
 10) DIFFERENT NUMBERS ARE PRESENT ON
 PAGE L-1 AND A1.1 WITH REGARDS TO
 SQUARE FOOTAGE OF BUILDING. PLEASE
 CORRECT INFORMATION.
 11) PLEASE INDICATE ALL FIRE HYDRANT
 LOCATIONS NEAR THE SITE FOR THE
 NEW BUILDING.
 12) PLEASE EXPLAIN WHY TWO DIFFERENT
 WALL SYSTEMS EXIST NEAR PHOTO, FOOD
 MART AND GENERAL STORAGE AREAS.
 13) TWO TELEPHONE LINES WILL BE REQUIRED
 TO MONITOR THE FIRE SPRINKLER AND OR
 FIRE ALARM SYSTEMS. SEE NOTE 10 ON
 PAGE E1.5.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-11-20 Cont ID  
Sent By btrobaug Date 2002-11-20 Time 18:00 Rev Time 0.00
Received By btrobaug Date 2002-11-15 Time 18:00 Sent To E
Notes
2002-11-20 00:00:00TO DVP./WRT

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2002-08-01 Cont ID  
Sent By pkrauss Date 2002-08-01 Time 08:53 Rev Time 0.35
Received By pkrauss Date 2002-08-01 Time 08:38 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-04-22 Cont ID  
Sent By pkrauss Date 2002-03-27 Time 11:20 Rev Time 0.45
Received By pkrauss Date 2002-03-27 Time 10:44 Sent To  
Notes
2002-03-27 00:00:00 
 PROVISO:
  
 ADDITIONAL PERMIT REQUIRED FOR WALK-IN
 COOLER/FREEZERS.PROVIDE PLANS AND
 MANUFACTURER SUBMITTAL DATA WITH PERMIT
 APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-02-14 Cont ID  
Sent By pkrauss Date 2002-02-14 Time 12:54 Rev Time 1.45
Received By pkrauss Date 2002-02-14 Time 11:13 Sent To  
Notes
2002-02-14 00:00:00*******************DENIED***************
  
 APPLICABLE CODE - 2001 FLORIDA BUILDING
 CODE, MECHANICAL
  
  
 1.INDICATE HOW EQUIPMENT ON THE ROOF
 IS TO BE ACCESSED FOR SERVICE AND
 MAINTENANCE.AS PER 306.5 AN
 APPROVED PERMANENT MEANS OF ACCESS
 IS REQUIRED FOR EQUIPMENT INSTALLED
 ON ROOFS AT A HEIGHT EXCEEDING 16'.
  
 PLEASE NOTE, ACCESS SHALL NOT
 REQUIRE CLIMBING OVER OBSTRUCTIONS
 GREATER THAN 30".
  
 SEPARATE PERMITS REQUIRED FOR WALK-IN
 COOLERS AND FREEZER.PLEASE PROVIDE
 PLANS AND MANUFACTURER SUBMITTAL DATA
 WITH PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 4 Status P Date 2002-10-12 Cont ID  
Sent By kstevens Date 2002-10-12 Time 12:36 Rev Time 0.00
Received By kstevens Date 2002-10-12 Time 12:36 Sent To  
Notes
2002-10-12 00:00:00REVISION OK - ADD EYE WASH AT SINK P-1
 SEPARATE S.O.V. REQUIRED FOR EYE WASH.

Review Stop P PLUMBING
Rev No 3 Status P Date 2002-07-25 Cont ID  
Sent By kstevens Date 2002-07-25 Time 19:21 Rev Time 0.00
Received By kstevens Date 2002-07-25 Time 19:21 Sent To  
Notes
2002-07-25 00:00:00REVISION OK - CHANGE LAYOUT FOR MEN'S
 AND WOMEN'S TOILET ROOMS - BREAKROOM

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-04-19 Cont ID  
Sent By kstevens Date 2002-04-19 Time 09:27 Rev Time 0.00
Received By kstevens Date 2002-04-19 Time 09:27 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-02-06 Cont ID  
Sent By kstevens Date 2002-02-06 Time 13:41 Rev Time 0.00
Received By kstevens Date 2002-02-06 Time 13:40 Sent To  
Notes
2002-02-06 00:00:00DENIED
 REFERENCE: FBC-2001
  
 1) SHTS P1.1/P2.1 ITEM #15 & WATER HEAT-
 ER DETAIL, ALL DRIP AND INDIRECT TO AN
 APPROVED RECEPTOR. FUNNEL DRAIN AND
 FLOOR DRAIN NOT APPROVED FOR INDIRECT
 WASTE. PLEASE PROVIDE FLOOR SINK FOR ALL
 INDIRECT WASTE. TRAP PRIMER REQUIRED FOR
 WATER HEATER ROOM.
 2) SHT P1.1 BACKFLOW REQUIRED ON WATER
 SERVICE.
 3) BACKFLOW REQUIRED FOR IRRIGATION.
 PLUMBING CONTRACTOR SHALL INSTALL BACK-
 FLOW FOR IRRIGATION CONTRACTOR.
 4) SHT P1.1 PLEASE SUBMIT MANUFACTURE
 INFORMATION FOR TANKLESS WATER HEATERS
 FOR #'S 3 & 16 MOD #'S DCH 10-2/DCH 8-2
 FOR PLAN REVIEW.
 5) SHT P1.1 PLEASE SUBMIT MANUFACTURE
 INFORMATION FOR AUTOMATIC FLUSH SYSTEM
 AT FIXTURE #14 FOR PLAN REVIEW.
 6) SHT A3.1 DETAILS (C-C) & (11), PROVI-
 DE PERMINATE SHIPS LADDER OR PUT W/HEAT-
 ER ON FLOOR TO MAKE HEATER ACCESSIBLE.
 7) SHT P2.1 ELECT. WATER HEATER DETAIL,
 DIELECTRIC UNIONS NOT APPROVED FOR WATER
 PIPING. (GAS FITTING ONLY).
 8) SHT P2.1 WATER HAMMER DETAIL. LOCATE
 WATER HAMMER ARRESTORS NEAR THE FIXTURE
 IN AN "EFFECTIVE RANGE" NOT ON TOP AS
 SHOWN. SUBMIT WATER RISER DIAGRAM WITH
 PIPE SIZES SHOWING CORRECT LOCATION OF
 WATER HAMMER ARRESTORS NEAR FIXTURES.
 SEC 604.9
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 3 Status F Date 2002-08-15 Cont ID  
Sent By sgraham Date 2002-08-15 Time 14:18 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
2002-08-15 00:00:00DENIED,
 1. MUST PROVIDE REVISED LANDSCAPE
 CALCULATIONS
 2. DUMPSTER MUST BE ENCLOSED
 3. LIGHTING-PHOTOMETRICS NEEDS TO BE
 PROVIDED PRIOR TO C.O.

Review Stop Z ZONING
Rev No 2 Status P Date 2002-03-26 Cont ID  
Sent By pkrauss Date 2002-03-26 Time 16:47 Rev Time 0.05
Received By pkrauss Date   Time   Sent To  
Notes
2002-03-26 00:00:00OKAY AS PER JEFF MARSHALL 3/26/02PHK

Review Stop Z ZONING
Rev No 1 Status F Date 2002-01-25 Cont ID  
Sent By sgraham Date 2002-01-25 Time 14:53 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
2002-01-25 00:00:00DENIED, NEED THE APPROVED SITE PLAN
 WITH THE PLANS.