Plan Review Details - Permit 02011035
Plan Review Stops For Permit 02011035
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2002-07-15 Cont ID  
Sent By rbrown Date 2002-07-15 Time 15:19 Rev Time 0.00
Received By rbrown Date 2002-07-15 Time 15:19 Sent To  
Notes
2002-07-15 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 SBC = STANDARD BUILDING CODE 1997
 SBC*= STANDARD BUILD'G CODE (CITY AMEND)
 FL ACC CODE = FLORIDA ACCESSIBILITY CODE
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEW OF 2/6/02:
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) SBC* 104.2STOREFRONT.THIS COMMENT
 HAS NOT BEEN ADDRESSED.SEE PREVIOUS
 REVIEW.THE 'PROJECT SUMMARY' STILL
 CONTRADICTS THE 'DEMOLITION KEY'. AMEND
 THE PLANS TO CLARIFY THE SCOPE OF WORK.
  
 3) SBC* 104.2'NEW SLAB'.THIS COMMENT
 HAS NOT BEEN ADDRESSED.SEE PREVIOUS
 REVIEW.THE 'PROJECT SUMMARY' STILL
 REFERS TO INSTALLATION OF A NEW SLAB ON
 GRADE.SHEETS A1.1 AND A1.3 DO NOT SHOW
 ANY DETAILS OF THIS.AMEND THE PLANS TO
 CLARIFY THE SCOPE OF WORK.
  
 4) SBC* 104.2CT SCAN, LEAD SHIELDING.
 THIS COMMENT HAS NOT BEEN ADDRESSED.
 SEE PREVIOUS REVIEW.WHILST THE CT SCAN
 ROOM WALLS HAVE BEEN DESIGNED WITH LEAD
 SHIELDING, NO LEAD SHIELDING HAS BEEN
 SPECIFIED FOR THE WALL IN FRONT OF THE
 STOREFRONT GLAZING.SUBMIT DETAILS FROM
 THE CT SCANNER SUPPLIER TO DESCRIBE THE
 MANUFACTURER'S SAFETY REQUIREMENTS FOR
 THE INSTALLATION SITE.
  
 5) FL ACC CODE 4.16.4TOILET GRAB BAR.
 THIS COMMENT HAS NOT BEEN ADDRESSED.
 SEE PREVIOUS REVIEW.THE HEIGHT OF THE
 GRAB BAR BEHIND THE W.C. EXCEEDS THE
 MAXIMUM ALLOWABLE OF 36" ABOVE FLOOR
 LEVEL.AMEND THE PLANS TO SHOW
 COMPLIANCE.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-02-06 Cont ID  
Sent By rbrown Date 2002-02-06 Time 08:16 Rev Time 0.00
Received By rbrown Date 2002-02-06 Time 08:16 Sent To  
Notes
2002-02-06 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 THE PLANS MAKE REFERENCE TO THE STANDARD
 BUILDING CODE 1997 AND HAVE THEREFOR
 BEEN REVIEWED FOR COMPLIANCE WITH THAT
 CODE
  
 SBC = STANDARD BUILDING CODE 1997
 SBC*= STANDARD BUILD'G CODE (CITY AMEND)
 FL ACC CODE = FLORIDA ACCESSIBILITY CODE
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) SBC* 104.2THE PROJECT SUMMARY ON
 SHEET A0.1 REFERS TO THE INSTALLATION OF
 NEW STOREFRONT DOORS & GLAZING.THIS IS
 NOT IN AGREEMENT WITH THE DEMOLITION
 PLAN ON SHEET A1.1 WHICH SHOWS THE
 EXISTING STOREFRONT TO REMAIN.AMEND
 THE PLANS TO CLARIFY THE SCOPE OF WORK.
  
 3) SBC* 104.2THE PROJECT SUMMARY ON
 SHEET A0.1 REFERS TO THE INSTALLATION OF
 A NEW SLAB ON GRADE.SHEETS A1.1 & A2.1
 DO NOT SHOW ANY DETAILS OF THIS.AMEND
 THE PLANS TO CLARIFY THE SCOPE OF WORK.
  
 4) SBC* 104.2THE CT SCAN ROOM HAS LEAD
 SHIELDING IN THE WALLS, YET THERE IS NO
 PROTECTION SPECIFIED AT THE EXISTING
 EXTERIOR GLAZED WALL.SUBMIT DETAILS
 FROM THE CT SCANNER SUPPLIER TO
 DESCRIBE THE MANUFACTURER'S SAFETY
 REQUIREMENTS FOR THE INSTALLATION SITE.
  
 5) FL ACC CODE 4.16.4THE HEIGHT OF THE
 GRAB BAR BEHIND THE W.C. EXCEEDS THE
 MAXIMUM ALLOWABLE OF 36" ABOVE FLOOR
 LEVEL.AMEND THE PLANS TO SHOW
 COMPLIANCE.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUERIES PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-07-01 Cont ID  
Sent By dpalmer Date 2002-07-01 Time 07:15 Rev Time 0.00
Received By dpalmer Date 2002-07-01 Time 07:15 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-02-01 Cont ID  
Sent By dpalmer Date 2002-02-01 Time 13:10 Rev Time 0.00
Received By dpalmer Date 2002-02-01 Time 13:10 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-06-19 Cont ID  
Sent By mcarsill Date 2002-06-19 Time 17:45 Rev Time 0.00
Received By mcarsill Date 2002-06-19 Time 17:45 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2002-01-22 Cont ID  
Sent By mcarsill Date 2002-01-22 Time 09:02 Rev Time 0.00
Received By mcarsill Date 2002-01-22 Time 09:02 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2002-06-22 Cont ID  
Sent By pkrauss Date 2002-06-22 Time 10:01 Rev Time 0.40
Received By pkrauss Date 2002-06-22 Time 09:56 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-06-13 Cont ID  
Sent By pkrauss Date 2002-06-13 Time 11:10 Rev Time 0.35
Received By pkrauss Date 2002-06-13 Time 11:10 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-02-06 Cont ID  
Sent By pkrauss Date 2002-02-06 Time 11:24 Rev Time 0.35
Received By pkrauss Date 2002-02-06 Time 11:18 Sent To  
Notes
2002-02-06 00:00:00 
 PROVIDE OUTSIDE AIR CALCULATIONS AS PER
 ASHRAE 62-89.
  
 INDICATE LOCATION AND TERMINATION OF THE
 CONDENSATE.
  
 UNITS GREATER THAN 3 TON SHALL
 TERMINATE:
  
 - INTO AN APPROVED DRYWELL
 - INTO STORM DRAIN.
 (AS PER COUNTYWIDE AMENDMENTS 1994 SPC
 804.3 #2)
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT6 59-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 2 Status F Date 2002-07-15 Cont ID  
Sent By kstevens Date 2002-07-01 Time 08:42 Rev Time 0.00
Received By kstevens Date 2002-07-01 Time 08:42 Sent To  
Notes
2002-07-01 00:00:00DENIED
 REFERENCE: SPC-94-FACBC-97
  
 1) PROVIDE MANUFACTURE INFORMATION FOR
 INSTA HOT & WATER FILTER. INSTA HOT MUST
 SHOW LISTINF FROM APPROVED TESTING AGEN-
 CY, AND FILTER MUST BE NSF APPROVED.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-02-02 Cont ID  
Sent By kstevens Date 2002-02-02 Time 07:12 Rev Time 0.50
Received By kstevens Date 2002-02-02 Time 07:12 Sent To  
Notes
2002-02-02 00:00:00DENIED
 REFERENCE: SPC-94-FACBC-97
  
 1) PLEASE SHOW CLEAR FLOOR SPACE AND
 TURNING RADIUS FOR RESTROOMS. SHT A1.1
 2) IF DOOR SWINGS INTO CLEAR FLOOR SPACE
 OR TURNING RADIUS THEN DOORS WILL HAVE
 TO SWING OUT.
 3) PLEASE GIVE DIMENSIONS FOR RESTROOMS.
  
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377