Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-01-22 Cont ID  
Sent By pkrauss Date 2002-01-22 Time 13:04 Rev Time 0.30
Received By pkrauss Date 2002-01-22 Time 12:53 Sent To  
Notes
2002-01-22 00:00:00******************PROVISO***************
  
 FAN SHUTDOWN BY DUCT SMOKE DETECTOR
 WITH NOTIFICATION TO ALARM/STROBE IN
 NORMALLY OCCUPIED AREAS.(1997 SMC
 406.1 & NFPA90A 4-4.4.3)
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.