Plan Review Details - Permit 02010870
Plan Review Stops For Permit 02010870
Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-01-22 Cont ID  
Sent By pkrauss Date 2002-01-22 Time 12:31 Rev Time 0.40
Received By pkrauss Date 2002-01-22 Time 12:23 Sent To  
Notes
2002-01-22 00:00:00 
 CLARIFY DUCT SIZE GOING DOWN TO 1ST FL,
 PLANS SHOW 2 10 X 6 SIDEWALL BACK TO
 BACK?SIZE OF DUCT PRIOR TO
 SIDEWALL..9 X 9 AFTER.
  
 LOCATION OF AHU?CLOSET OR ATTIC?
  
 ATTIC REQUIRES 22" BY 36" CONTINUOUS
 FROM THE OPENING TO THE EQUIPMENT & ITS
 CONTROLS.
  
 DUCT SIZE IN THE APT.ARE THEY ALL THE
 SAME 46"& 1 4"?