| 2002-01-31 00:00:00 | CHECKLIST: |
| | 1-NEED RECORDED NOTICE OF COMMENCEMENT. |
| | 2-TAKE DRAWINGS TO PALM BEACH COUNTY TO |
| | VERIFY IF IMPACT FEES ARE DUE OR NOT? |
| | BRING BACK STAMPED DRWGS & RECEIPT. |
| | 3-ENG'R TO SPECIFY THE DESIGN PRESSURES |
| | CALCULATED AT EXTERIOR OPENINGS. |
| | SECTION 1606 SBC 1997. |
| | 4-PROVIDE PRODUCT APPROVAL AND COMPLETE |
| | INFORMATION FOR STORM SHUTTERS. |
| | SEE ATTACHED CITY SAMPLE. |
| | 5-CONNECTOR SPECIFIED HGA10 IS NOT |
| | DESIGNED FOR WOOD STUDS. SEE SIMPSON |
| | CATALOGUE AND REVISE AS REQUIRED. |
| | 6-SEE PLANS FOR ADDITIONAL COMMENTS. |
| | 7-SPECIFY HOW ARE THE TRIPLE OPENING |
| | STUDS ATTACHED AT TOP AND BOTTOM. |
| | 8-DRAWING 5 OF 7 OF PRODUCT APPROVAL FOR |
| | SLIDING GLASS DOORS IS NOT LEGIBLE. |
| | PROVIDE LEGIBLE DRAWINGS. |
| | -CHECK DESIGN PRESSURES SPECIFIED BY |
| | ENGINEER OF RECORD. |
| | -PROVIDE 2 COPIES OF PRODUCT APPROVALS. |
| | 9-DESIGN CERTIFICATION FOR BUILDING CODE |
| | COMPLIANCE FORM IS FOR PALM BEACH CTY |
| | NOT FOR CITY OF W.P.B. |
| | NOTE: THIS FORM IS NOT REQUIRED TO BE |
| | FILED SEPARATELY. SUCH INFORMATION |
| | SHALL BE INCLUDED IN THE PLANS. |
| | 10-DRAWINGS ARE MISSING THE ELECTRICAL |
| | INFORMATION FOR REVIEW. |
| | -ALSO, PROVIDE INFORMATION FOR A/C |
| | REVIEW. |
| | 11-PROVIDE COMPLETE ENERGY CALCULATIONS |
| | FORM. |