Plan Review Details - Permit 02010756
Plan Review Stops For Permit 02010756
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-04-29 Cont ID  
Sent By hpiskura Date 2002-04-29 Time 07:49 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2002-01-25 Cont ID  
Sent By hpiskura Date 2002-01-25 Time 15:16 Rev Time 0.00
Received By hpiskura Date 2002-01-25 Time 12:10 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2002-09-23 Cont ID  
Sent By btrobaug Date 2002-09-23 Time 17:01 Rev Time 0.50
Received By btrobaug Date 2002-09-19 Time 17:56 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-04-10 Cont ID  
Sent By dpalmer Date 2002-04-10 Time 12:59 Rev Time 0.00
Received By dpalmer Date 2002-04-10 Time 12:57 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-01-30 Cont ID  
Sent By dpalmer Date 2002-01-30 Time 20:34 Rev Time 0.00
Received By dpalmer Date 2002-01-30 Time 20:34 Sent To  
Notes
2002-01-30 00:00:00***************** UNSAT ***************
  
  
 1)NOTE: PLEASE NOTE THAT PLANS NEED TO
 SHOW THE LOAD CALCULATIONS PER,220-3,
 220-10,220-11,220-13 AND ALL CONTINUOUS
 LOADS AT 125% TO VERFIY PANEL SIZING
 AND OCP.215-3,230-42 .
 LARGEST MOTOR LOAD AT 125%
  
 PLEASE NOTE THAT PER FIRE PLAN REVIEW
 THERE MAY ALSO BE SOME CHANGES TO THE
 ELECTRICAL PLANS. PLEASE CLARFIY ANY
 LOW VOLTAGE DEVICES THAT MAY BE INCLUDED
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-04-11 Cont ID  
Sent By mcarsill Date 2002-04-11 Time 16:41 Rev Time 0.00
Received By mcarsill Date 2002-04-11 Time 16:40 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-01-17 Cont ID  
Sent By mcarsill Date 2002-01-17 Time 17:09 Rev Time 0.00
Received By mcarsill Date 2002-01-17 Time 17:09 Sent To  
Notes
2002-01-17 00:00:001) PLEASE PROVIDE MORE DETAILS ON
 SECURITY DEVICES PLANNED FOR EXIT
 DOORS. ANY SECURITY DEVICES PLANNED
 FOR EXIT DOORS MUST COMPLY WITH
 "SPECIAL LOCKING ARRANGEMENTS" OF THE
 LIFE SAFETY CODE. PLEASE ADVISE.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-04-10 Cont ID  
Sent By pkrauss Date 2002-04-10 Time 10:46 Rev Time 0.50
Received By pkrauss Date 2002-04-10 Time 10:13 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-02-04 Cont ID  
Sent By pkrauss Date 2002-02-04 Time 11:55 Rev Time 1.10
Received By pkrauss Date 2002-02-04 Time 10:11 Sent To  
Notes
2002-02-04 00:00:00********************DENIED**************
  
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 FOR REVIEW.
  
 1.INDICATE SIZE OF DUCT FOR THE BRANCH
 LINES.
  
 2.DUCTS PENETRATING PARTITIONS OR
 WALLS WITH A FIRE RESISTANCE RATING
 OF 1 HOUR OR MORE REQUIRE FIRE
 DAMPERS AS PER 1997 SMC 610.1.2.
  
 IN THE EVENT DUCTS FALL UNDER THE
 EXCEPTION (1997 SMC 610.1.3), SHOW
 COMPLIANCE WITH SUB PARAGRAPH #3,
 ITEMS 1 THROUGH 4.
  
 3.FAN SHUTDOWN BY DUCT SMOKE DETECTOR
 SHALL HAVE NOTIFICATION TO ALARM/
 STROBE IN NORMALLY OCCUPIED AREAS AS
 PER NFPA 90A 4-4.4.3.
  
 FAN SHUTDOWN BY DUCT SMOKE DETECTOR
 IS ALSO REQUIRED FOR UNITS UNDER
 2,000 CFM IF SERVING AN AREA OF
 EGRESS AS PER 1997 SMC 406.2.
 (AHU-INS-6)
  
 4.AIR BALANCE SCHEDULE - THE NOTE AT
 THE BOTTOM OF THE SCHEDULE STATES
 "PROVIDE RELIEF ON SHEET M2.2",
 RELIEF IS INDICATED ON PLAN SHEET
 M2.1.
  
 5.AIR SYSTEM SIZING SHEETS - THE
 FOLLOWING AHU DO NOT MATCH THE
 EQUIPMENT SCHEDULE ON SHEET M0.1.
  
 AHU-INS-3, 7, 9 & VAN-1.
 NO SIZING CALCULATIONS FOR
 AHU-INS-11.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 3 Status P Date 2002-05-18 Cont ID  
Sent By kstevens Date 2002-05-18 Time 09:53 Rev Time 0.00
Received By kstevens Date 2002-05-18 Time 09:53 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2002-04-24 Cont ID  
Sent By kstevens Date 2002-04-24 Time 21:30 Rev Time 0.00
Received By kstevens Date 2002-04-24 Time 21:30 Sent To  
Notes
2002-04-24 00:00:00DENIED
 REFERENCE: SPC-94-FACBC-97
  
 1) SHT P0.1 PLUMBING FIXTURE SCHEDULE.
 FROM PREVIOUS REVIEW - SUBMITTAL FOR 1WH
 AND 1WH-1 NOT APPROVED. DADE COUNTY
 APPROVAL NOT ACCEPTABLE. IT IS ALSO
 OUT OF DATE AS OF 7-18-99 SO IT IS NOT
 VALID. PLEASE SUBMIT MANUFACTURE INFOR-
 MATION FOR THESE WATER HEATERS.
 2) SHTS P2.1 AND P2.2, PLEASE SUBMIT DE-
 TAIL FOR SOAKAGE PIT FOR APPROVAL.
 3) PREVIOUS REVIEW COMMENT #6 NOT REPLY
 NOT SHOWN ON PLAN AS INDICATED. SHT A3.1
 DETAIL D/A1.2 SHOWS NO MEASURMENTS FOR
 URNAL HEIGHT. PLEASE INDICATE HEIGHT FOR
 REVIEW.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-02-01 Cont ID  
Sent By kstevens Date 2002-02-01 Time 18:02 Rev Time 1.50
Received By kstevens Date 2002-02-01 Time 18:01 Sent To  
Notes
2002-02-01 00:00:00DENIED
 REFERENCE: SPC-94-FACBC-97
  
 1) SHT PO.1 CONDENSATE TRAP DETAIL, VENT
 SHALL NOT TERMINATE IN MECHANICAL ROOM
 THAT IS USED AS A PLENUM.
 2) CONDENSATE SHALL BE FULL SIZE FROM
 AHU.
 3) SHT PO.1 PLUMBING FIXTURE SCHEDULE,
 1WH & 1WH-1 PLEASE SUBMIT MANUFACTURE
 CUT SHEET TO CHECK FOR A LISTING APPROV-
 AL.
 4) SHTS P2.1 & P5.1 FUNNEL DRAIN NOT
 APPROVED. CONDENSATE SHALL NOT DRAIN TO
 SANITARY, MUST RUN TO CONDENSATE AT WET
 COLUMN, OUTSIDE TO STORM OR TO A DRYWELL
 OUTSIDE BLDG. SAME FOR SECOND FLOOR COND
 5) SHT P2.2 PER SPC TABLE 407 TWO DRINK-
 ING FOUNTAIN ARE REQUIRED FOR THE SECOND
 FLOOR. ONLY ONE SHOWN.
 6) SHT 3.1 DETAILS B/A1.1 & D/A1.1,
 URNAL TO BE 17" AFF MAX TO LIP. PLEASE
 SHOW ON PLAN.
 SHT P5.1 SANITARY ISOMETRIC, WASTE FOR
 SECOND FLOOR SHALL DRAIN INTO 5" SANT.
 WASTE STACK NOT INTO BRANCH LINE FOR
 FIRST FLOOR.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status P Date 2002-01-17 Cont ID  
Sent By sgraham Date 2002-01-17 Time 12:07 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***