| Plan Review Stops For Permit 02010651 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2002-03-29 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2002-03-29 |
Time |
11:21 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2002-03-29 |
Time |
11:21 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2002-03-27 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2002-03-27 |
Time |
10:58 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2002-03-27 |
Time |
10:58 |
Sent To |
|
|
| Notes |
| 2002-03-27 00:00:00 | BUILDING PLAN REVIEW | | | ******PROVISO******* | | | ROBERT BROWN(561) 659 8096 EXT 8499 | | | | | | SBC = STANDARD BUILDING CODE 1997 | | | SBC*= STANDARD BUILD'G CODE (CITY AMEND) | | | | | | --PROVISO-- | | | A RECORDED COPY OF THE NOTICE OF | | | COMMENCEMENT MUST BE SUBMITTED BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | --PROVISO-- | | | SBC* 104.1.1A SEPARATE ROOFING PERMIT | | | APPLICATION IS REQUIRED. | | | | | | --PROVISO-- | | | SBC* 104.1.1SEPARATE SHUTTER AND | | | WINDOW/DOOR PERMIT APPLICATIONS ARE | | | REQUIRED. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2002-03-15 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2002-03-15 |
Time |
14:53 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2002-03-15 |
Time |
14:53 |
Sent To |
|
|
| Notes |
| 2002-03-15 00:00:00 | BUILDING PLAN REVIEW | | | *******DENIED******* | | | ROBERT BROWN(561) 659 8096 EXT 8499 | | | | | | SBC = STANDARD BUILDING CODE 1997 | | | SBC*= STANDARD BUILD'G CODE (CITY AMEND) | | | FL ACC CODE = FLORIDA ACCESSIBILITY CODE | | | | | | FOR CONSISTENCY, THE FOLLOWING COMMENTS | | | ARE NUMBERED AS PER THE BUILDING PLAN | | | REVIEW OF 1/30/02: | | | | | | 1) A RECORDED COPY OF THE NOTICE OF | | | COMMENCEMENT MUST BE SUBMITTED BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | 2) IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY, PLANS STAMPED BY THEM AND | | | COPY OF RECEIPT SUBMITTED TO CITY OF | | | WEST PALM BEACH BUILDING DEPARTMENT, | | | BEFORE A BUILDING PERMIT CAN BE ISSUED. | | | | | | 3) --PROVISO--SBC* 104.1.1A SEPARATE | | | ROOFING PERMIT APPLICATION IS REQUIRED. | | | | | | 4) --PROVISO--SBC* 104.1.1A SEPARATE | | | SHUTTER AND WINDOW/DOOR PERMIT | | | APPLICATION IS REQUIRED. | | | | | | 5) SBC* 104.2.1SHEET A1, FLOOR PLAN | | | AND COOLER SECTION.THIS COMMENT HAS | | | NOT BEEN ADDRESSED.THERE IS STILL NO | | | DESCRIPTION OF THE WALL CONSTRUCTION | | | AROUND THE NEW CHILLER.ALSO, THE | | | 'DUMPSTER DETAILS' DO NOT REFLECT THE | | | DUMPSTER LAYOUT OR THE VERTICAL REBAR | | | SPACING INDICATED ON THE FLOOR PLAN. | | | | | | 6) SBC 2405.2.1.SAFETY GLASS.THIS | | | COMMENT HAS NOT BEEN ADDRESSED.THE | | | DOOR SCHEDULE AND FRONT ELEVATION HAVE | | | NOT BEEN ADEQUATELY ANNOTATED TO SHOW | | | COMPLIANCE WITH THE REQUIREMENT FOR | | | 'SAFETY GLASS'. | | | | | | 7) FL ACC CODE 4.1.5SHEET C1, | | | ACCESSIBLE TOILET.ON THE PLAN AND | | | ELEVATION, THE GRAB BAR ADJACENT THE W.C | | | SHALL BE MIN. 42" LONG (NOT 36").THE | | | GRAB BAR BEHIND THE W.C. MAY BE MIN. 36" | | | LONG.ON THE W.C. ELEVATION, THE 18" | | | DIMENSION BETWEEN THE WALL AND THE W.C. | | | CENTRELINE IS INCORRECTLY SHOWN AS BEING | | | MEASURED BETWEEN THE WALL AND THE W.C. | | | FLUSH TANK.CORRECT THE DIMENSION TO | | | SHOW COMPLIANCE WITH FIGURES 28 AND 29. | | | | | | 8) FL ACC CODE 5.0SEATING.THE | | | MAXIMUM TABLE HEIGHT AND MINIMUM KNEE | | | CLEARANCE FOR THE ACCESSIBLE SEAT SHALL | | | BE IN ACCORDANCE WITH FL ACC CODE 4.32.3 | | | AND 4.32.4 | | | | | | **QUOTE PERMIT# ON ALL CORRESPONDENCE** | | | | | | END OF REVIEW COMMENTS | | | THE CODE REFERENCES GIVE ADDITIONAL INFO | | | IF YOU HAVE ANY QUERIES PLEASE CALL: | | | ROBERT BROWN(561) 659 8096 EXT 8499 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2002-01-30 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2002-01-30 |
Time |
14:39 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2002-01-30 |
Time |
14:39 |
Sent To |
|
|
| Notes |
| 2002-01-30 00:00:00 | BUILDING PLAN REVIEW | | | *******DENIED******* | | | ROBERT BROWN(561) 659 8096 EXT 8499 | | | | | | SBC = STANDARD BUILDING CODE 1997 | | | SBC*= STANDARD BUILD'G CODE (CITY AMEND) | | | FL ACC CODE = FLORIDA ACCESSIBILITY CODE | | | | | | 1) A RECORDED COPY OF THE NOTICE OF | | | COMMENCEMENT MUST BE SUBMITTED BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | 2) IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY, PLANS STAMPED BY THEM AND | | | COPY OF RECEIPT SUBMITTED TO CITY OF | | | WEST PALM BEACH BUILDING DEPARTMENT, | | | BEFORE A BUILDING PERMIT CAN BE ISSUED. | | | | | | 3) SBC* 104.1.1A SEPARATE ROOFING | | | PERMIT APPLICATION IS REQUIRED.THE | | | PROPOSED NEW AND REPLACED SINGLE PLY | | | ROOFING SHALL COMPLY WITH SBC 1513. | | | | | | 4) SBC* 104.1.1SHUTTER AND WINDOW/DOOR | | | DETAILS WERE NOT SUPPLIED WITH THE | | | APPLICATION.SEPARATE PERMIT | | | APPLICATIONS ARE REQUIRED FOR THE | | | HURRICANE SHUTTERS, WINDOWS AND DOORS. | | | | | | 5) SBC* 104.2.1THE PLANS SHALL BE | | | AMENDED TO ADEQUATELY DESCRIBE THE WALL | | | CONSTRUCTION AROUND THE NEW WALK-IN | | | COOLER. | | | | | | 6) SBC 2405.2.1THE GLAZING IN THE NEW | | | STOREFRONT IS IN A "HAZARDOUS LOCATION". | | | PROVIDE DETAILS TO SHOW COMPLIANCE WITH | | | THE REQUIREMENT FOR 'SAFETY GLASS'. | | | | | | 7) FL ACC CODE 4.1.5SUBMIT TOILET | | | PLANS WITH DIMENSIONS SHOWING COMPLIANCE | | | WITH THE REQUIRED POSITIONING AND HEIGHT | | | OF THE APPLIANCES AND FACILITIES (FL | | | ACC CODE 4.16). | | | | | | 8) FL ACC CODE 5.0DETAILS OF THE | | | SEATING LAYOUT SHALL BE SUBMITTED TO | | | DEMONSTRATE COMPLIANCE WITH THE | | | REQUIREMENTS FOR ACCESSIBILITY. | | | | | | 9) FL ACC CODE 4.5.1GROUND AND FLOOR | | | SURFACES SHALL BE STABLE FIRM AND SLIP | | | RESISTANT.APPENDIX A4.5.1 (ADA ACCESS- | | | IBILITY GUIDELINES COMMENTARY) | | | RECOMMENDS A STATIC COEFFICIENT OF | | | FRICTION OF 0.6 FOR ACCESSIBLE ROUTES | | | AND 0.8 FOR RAMPS.THESE COEFFICIENTS | | | HAVE BEEN MISQUOTED AS 0.06 AND 0.08 | | | RESPECTIVELY ON BOTH SHEET C1 GENERAL | | | NOTES AND SHEET SP1 SITE IMPROVEMENT | | | PLAN. | | | | | | **QUOTE PERMIT# ON ALL CORRESPONDENCE** | | | | | | END OF REVIEW COMMENTS | | | THE CODE REFERENCES GIVE ADDITIONAL INFO | | | IF YOU HAVE ANY QUERIES PLEASE CALL: | | | ROBERT BROWN(561) 659 8096 EXT 8499 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2002-05-01 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-05-01 |
Time |
19:09 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-05-01 |
Time |
19:09 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2002-04-30 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-04-30 |
Time |
20:30 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-04-30 |
Time |
20:30 |
Sent To |
|
|
| Notes |
| 2002-04-30 00:00:00 | CALLED CONT FOR COMMENTS.4/30 | | | | | | MISSING AIC RATINGS FOR MAIN DISC`S | | | PER 110-9 | | | MISSING WALK IN COOLER LTS. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2002-03-13 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-03-13 |
Time |
13:32 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-03-13 |
Time |
13:32 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2002-01-24 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-01-24 |
Time |
07:06 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-01-24 |
Time |
07:06 |
Sent To |
|
|
| Notes |
| 2002-01-24 00:00:00 | ***************** UNSAT *************** | | | | | | 1)NOTE: PLEASE NOTE, A-7 SHOWS A NEW | | | 3-PHASE SERICE BEING INSTALLED, RISER | | | ALSO SHOWS THE SAME, EXCEPT FOR METER/ | | | RISER? PLEASE CLARFIY SIZE EXSITING | | | SERVICE ENTRANCE CONDUCTORS. PLEASE | | | CLARIFY EXISTING GROUNDING ELECTRODE | | | LOCATIONS OF ATTACHMENT. | | | | | | 2)NOTE: PLEASE CLARFIY LOCATION OF RECEP | | | FOR ROOFTOP ACCU`S. 210-63. | | | | | | 3)NOTE: PLEASE NOTE OUTLET FOR SIGNAGE | | | PER 600-5. CLARIFY IF EXISTING? | | | | | | 4)NOTE: PLEASE NOTE SPACING FOR SHOW | | | WINDOW OUTLETS PER 210-62. PLEASE | | | CLARFIY IF EXISTING? | | | | | | 5)NOTE: PLEASE NOTE AND OR CLARFIY OCP | | | SHOWN FOR ITEMS ON PANEL SCHEDULE THAT | | | SHOW 25A,35A OCP ON #12 AND #10. PLEASE | | | SEE 310-16, SHOW`S "*" #12/#10WHICH | | | REFERS TO 240-3D. PLEASE NOTE 240-3 | | | LIMITS OCP TO 15/20/30AMPS. | | | | | | 6)NOTE: PLEASE CLARIFY CONDUCTOR SIZES | | | BETWEEN MAIN DISC`S AND PANELS AND | | | EQUIPMENT GROUNIDNG CONDCUTORS PER | | | 250-122. | | | | | | PLEASE SUBMIT THE ABOVE INFORMAITON FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT8372 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2002-03-19 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-03-19 |
Time |
09:18 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-03-19 |
Time |
09:18 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2002-01-24 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-01-24 |
Time |
11:05 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-01-24 |
Time |
11:05 |
Sent To |
|
|
| Notes |
| 2002-01-24 00:00:00 | 1) PLEASE BE ADVISED THAT THIS LOCATION | | | IS LOCATED WITHIN THE CITY FIRE LIMITS. | | | PLEASE SEE LOCAL AMENDMENTS, APPENDIX F, | | | CITY OF WEST PALM BEACH. | | | 2) PLEASE PROVIDE INTERIOR FINISH | | | INFORMATION FOR WALLS AND CEILINGS. | | | 3) PROVIDE SEPARATE PLANS AND PERMITS | | | FOR NEW FIRE SUPPRESSION SYSTEM. | | | 4) PLEASE INDICATE ON THE PLANS THAT | | | ONLY SINGLE CYLINDER DEADBOLTS WILL | | | BE USED. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2002-03-18 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-03-18 |
Time |
13:03 |
Rev Time |
0.30 |
| Received By |
pkrauss |
Date |
2002-03-18 |
Time |
10:15 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2002-02-05 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-02-05 |
Time |
12:26 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2002-02-05 |
Time |
12:26 |
Sent To |
|
|
| Notes |
| 2002-02-05 00:00:00 | | | | PROVISO: | | | | | | | | | PRIOR TO CONNECTING TO ANY EXISTING | | | DUCTWORK, CALL FOR AN INSPECTION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2002-04-22 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-04-22 |
Time |
15:02 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2002-04-22 |
Time |
15:02 |
Sent To |
|
|
| Notes |
| 2002-04-22 00:00:00 | REVISION OK - CHANGE SAFE WASTE TO FLOOR | | | SINK (5) |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2002-03-26 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-03-26 |
Time |
09:42 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2002-03-26 |
Time |
09:42 |
Sent To |
|
|
| Notes |
| 2002-03-26 00:00:00 | PASSED/PROVISO - PER PETE RUSSO - AN | | | EXISTING DRYWELL FOR CONDENSATE IS ON | | | SITE. KS |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2002-03-19 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-03-19 |
Time |
13:35 |
Rev Time |
2.00 |
| Received By |
kstevens |
Date |
2002-03-19 |
Time |
13:35 |
Sent To |
|
|
| Notes |
| 2002-03-19 00:00:00 | DENIED | | | REFERENCE: SPC-94 - FACBC-97 - SGC-97 | | | | | | 1) FROM PREVIOUS REVIEW. PLEASE SUBMIT | | | AN EXISTING FLOOR PLAN TO DETERMINE THE | | | SCOPE OF REMODELING. | | | 2) FROM PREVIOUS REVIEW. SEPARATE GAS | | | PERMIT REQUIRED. PLEASE SEE ATTACHED GAS | | | PERMIT APPLICATION REQUIREMENTS SHEET & | | | SUPPLY INFORMATION GAS PLAN REVIEW. | | | 3) SEPARATE GAS DEMO PERMIT WILL BE RE- | | | QUIRED. | | | 4) FROM PREVIOUS REVIEW. SHT A-8 CONDEN- | | | SATE A/C NOTE #15 CONDENSATE TO DRAIN TO | | | DRYWELL OR STORM OUTSIDE OF BLDG. CONDEN | | | SATE LINE SHALL HAVE A RELIEF VENT NEAR | | | BLDG.-THIS #15 HAS BEEN CHANGED AND | | | I SEE NO REFERENCE TO CONDENSATE ON THE | | | PAGE IN QUESTION. PLEASE SUBMIT A DETAIL | | | FOR THE CONDENSATE DRAIN. | | | 5) FROM PREVIOUS REVIEW. ROOF PLAN. | | | PLEASE CALCULATIONS FOR PRIMARY AND | | | SECONDARY ROOF DRAINS USING SPC SEC 1108 | | | AND 1109. INCLUDE 1/2 AREA OF ALL VERTI- | | | CAL WALLS. SHOW LOCATIONS FOR PRIMARY | | | AND SECONDARY DRAINS AND SHOW DETAILS | | | FOR SIZE AND SHOW RISER WITH PIPE SIZES. | | | 6) FROM PREVIOUS REVIEW. NEW GREASE TRAP | | | SHALL HAVE TO BE INSTALLED OUTSIDE OF | | | THE BLDG PER CONVERSATION WITH RODNEY | | | COMPO. HE INDICATES THAT THE GREASE TRAP | | | DOES NOT MEET CODE AND THAT THE BAFFLES | | | HAVE BEEN REMOVED. SEPARATE SANITARY AND | | | GREASE LINE SHALL BE REQUIRED. PLEASE | | | INDICATE SEPARATE LINES WHEN RESUBMITT- | | | ING PLANS. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2002-01-30 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-01-30 |
Time |
18:51 |
Rev Time |
1.25 |
| Received By |
kstevens |
Date |
2002-01-30 |
Time |
18:48 |
Sent To |
|
|
| Notes |
| 2002-01-30 00:00:00 | DENIED | | | REFERENCE: SPC-94 - FABCB-97 | | | | | | 1) PLEASE SUBMIT AN EXISTING FLOOR PLAN | | | TO DETERMINE SCOPE OF REMODELING. | | | 2) SEPARATE GAS PERMIT REQUIRED. SEE | | | ATTACHED GAS PERMIT APPLICATION REQUIRE- | | | MENT SHEET AND SUPPLY INFORMATION FOR | | | GAS PLAN REVIEW. | | | 3) SEPARATE GAS DEMO PERMIT REQUIRED. | | | 4) ROUTE PLANS TO DEPT. OF BUSINESS REG- | | | ULATION, HOTEL AND RESTURANT DIV. FOR | | | PLAN REVIEW BEFORE RESUBMITING TO CITY. | | | COUNTYWIDE AMENDMENTS TO SPC SEC 101.4.7 | | | 5) SHT A-5 WATER FILTRATION SYSTEM SHALL | | | BE NSF APPROVED PER SPC SEC 615.1, 615.2 | | | SUBMIT MANUFACTURE INFO | | | 6) SHT A-8 CONDENSATE A/C NOTE #15. CON- | | | DENSATE TO DRAIN TO DRYWELL OR STORM OUT | | | SIDE OF BLDG. CONDENSATE DRAIN LINE | | | SHALL HAVE A RELIEF VENT NEAR BLDG. | | | PLEASE SHOW DETAILS. | | | 7) ROOF PLAN, PLEASE SUBMIT CALCULATIONS | | | FOR PRIMARY AND SECONDARY ROOF DRAINS | | | USING SPC SEC 1108, AND 1109. SHOW LOC- | | | ATIONS FOR PRIMARY AND SECONDARY DRAINS | | | AND SHOW DETAILS FOR SIZE AND SHOW RISER | | | WITH PIPE SIZE. | | | 8) SHT A-3 PLEASE SUBMIT EQUIPMENT SCHED | | | THAT CORRESPONDS TO EQUIPMENT FLOOR PLAN | | | 9) RODNEY COMPO, ENVIRONMENTAL COMPLI- | | | ANCE TO INSPECT GREAS TRAP LOCATED IN | | | BLDG TO DETERMINE IF MAINTENANCE HAS | | | BEEN PROVIDED AND IF IT STILL MEETS CODE | | | IF NOT GREASE TRAP SHALL HAVE TO BE IN- | | | STALLED OUTSIDE BLDG. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2002-01-23 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2002-01-23 |
Time |
12:05 |
Rev Time |
0.25 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|