Plan Review Details - Permit 02010651
Plan Review Stops For Permit 02010651
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2002-03-29 Cont ID  
Sent By rbrown Date 2002-03-29 Time 11:21 Rev Time 0.00
Received By rbrown Date 2002-03-29 Time 11:21 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2002-03-27 Cont ID  
Sent By rbrown Date 2002-03-27 Time 10:58 Rev Time 0.00
Received By rbrown Date 2002-03-27 Time 10:58 Sent To  
Notes
2002-03-27 00:00:00BUILDING PLAN REVIEW
 ******PROVISO*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 SBC = STANDARD BUILDING CODE 1997
 SBC*= STANDARD BUILD'G CODE (CITY AMEND)
  
 --PROVISO--
 A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 --PROVISO--
 SBC* 104.1.1A SEPARATE ROOFING PERMIT
 APPLICATION IS REQUIRED.
  
 --PROVISO--
 SBC* 104.1.1SEPARATE SHUTTER AND
 WINDOW/DOOR PERMIT APPLICATIONS ARE
 REQUIRED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2002-03-15 Cont ID  
Sent By rbrown Date 2002-03-15 Time 14:53 Rev Time 0.00
Received By rbrown Date 2002-03-15 Time 14:53 Sent To  
Notes
2002-03-15 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 SBC = STANDARD BUILDING CODE 1997
 SBC*= STANDARD BUILD'G CODE (CITY AMEND)
 FL ACC CODE = FLORIDA ACCESSIBILITY CODE
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEW OF 1/30/02:
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) --PROVISO--SBC* 104.1.1A SEPARATE
 ROOFING PERMIT APPLICATION IS REQUIRED.
  
 4) --PROVISO--SBC* 104.1.1A SEPARATE
 SHUTTER AND WINDOW/DOOR PERMIT
 APPLICATION IS REQUIRED.
  
 5) SBC* 104.2.1SHEET A1, FLOOR PLAN
 AND COOLER SECTION.THIS COMMENT HAS
 NOT BEEN ADDRESSED.THERE IS STILL NO
 DESCRIPTION OF THE WALL CONSTRUCTION
 AROUND THE NEW CHILLER.ALSO, THE
 'DUMPSTER DETAILS' DO NOT REFLECT THE
 DUMPSTER LAYOUT OR THE VERTICAL REBAR
 SPACING INDICATED ON THE FLOOR PLAN.
  
 6) SBC 2405.2.1.SAFETY GLASS.THIS
 COMMENT HAS NOT BEEN ADDRESSED.THE
 DOOR SCHEDULE AND FRONT ELEVATION HAVE
 NOT BEEN ADEQUATELY ANNOTATED TO SHOW
 COMPLIANCE WITH THE REQUIREMENT FOR
 'SAFETY GLASS'.
  
 7) FL ACC CODE 4.1.5SHEET C1,
 ACCESSIBLE TOILET.ON THE PLAN AND
 ELEVATION, THE GRAB BAR ADJACENT THE W.C
 SHALL BE MIN. 42" LONG (NOT 36").THE
 GRAB BAR BEHIND THE W.C. MAY BE MIN. 36"
 LONG.ON THE W.C. ELEVATION, THE 18"
 DIMENSION BETWEEN THE WALL AND THE W.C.
 CENTRELINE IS INCORRECTLY SHOWN AS BEING
 MEASURED BETWEEN THE WALL AND THE W.C.
 FLUSH TANK.CORRECT THE DIMENSION TO
 SHOW COMPLIANCE WITH FIGURES 28 AND 29.
  
 8) FL ACC CODE 5.0SEATING.THE
 MAXIMUM TABLE HEIGHT AND MINIMUM KNEE
 CLEARANCE FOR THE ACCESSIBLE SEAT SHALL
 BE IN ACCORDANCE WITH FL ACC CODE 4.32.3
 AND 4.32.4
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUERIES PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-01-30 Cont ID  
Sent By rbrown Date 2002-01-30 Time 14:39 Rev Time 0.00
Received By rbrown Date 2002-01-30 Time 14:39 Sent To  
Notes
2002-01-30 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 SBC = STANDARD BUILDING CODE 1997
 SBC*= STANDARD BUILD'G CODE (CITY AMEND)
 FL ACC CODE = FLORIDA ACCESSIBILITY CODE
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) SBC* 104.1.1A SEPARATE ROOFING
 PERMIT APPLICATION IS REQUIRED.THE
 PROPOSED NEW AND REPLACED SINGLE PLY
 ROOFING SHALL COMPLY WITH SBC 1513.
  
 4) SBC* 104.1.1SHUTTER AND WINDOW/DOOR
 DETAILS WERE NOT SUPPLIED WITH THE
 APPLICATION.SEPARATE PERMIT
 APPLICATIONS ARE REQUIRED FOR THE
 HURRICANE SHUTTERS, WINDOWS AND DOORS.
  
 5) SBC* 104.2.1THE PLANS SHALL BE
 AMENDED TO ADEQUATELY DESCRIBE THE WALL
 CONSTRUCTION AROUND THE NEW WALK-IN
 COOLER.
  
 6) SBC 2405.2.1THE GLAZING IN THE NEW
 STOREFRONT IS IN A "HAZARDOUS LOCATION".
 PROVIDE DETAILS TO SHOW COMPLIANCE WITH
 THE REQUIREMENT FOR 'SAFETY GLASS'.
  
 7) FL ACC CODE 4.1.5SUBMIT TOILET
 PLANS WITH DIMENSIONS SHOWING COMPLIANCE
 WITH THE REQUIRED POSITIONING AND HEIGHT
 OF THE APPLIANCES AND FACILITIES (FL
 ACC CODE 4.16).
  
 8) FL ACC CODE 5.0DETAILS OF THE
 SEATING LAYOUT SHALL BE SUBMITTED TO
 DEMONSTRATE COMPLIANCE WITH THE
 REQUIREMENTS FOR ACCESSIBILITY.
  
 9) FL ACC CODE 4.5.1GROUND AND FLOOR
 SURFACES SHALL BE STABLE FIRM AND SLIP
 RESISTANT.APPENDIX A4.5.1 (ADA ACCESS-
 IBILITY GUIDELINES COMMENTARY)
 RECOMMENDS A STATIC COEFFICIENT OF
 FRICTION OF 0.6 FOR ACCESSIBLE ROUTES
 AND 0.8 FOR RAMPS.THESE COEFFICIENTS
 HAVE BEEN MISQUOTED AS 0.06 AND 0.08
 RESPECTIVELY ON BOTH SHEET C1 GENERAL
 NOTES AND SHEET SP1 SITE IMPROVEMENT
 PLAN.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUERIES PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2002-05-01 Cont ID  
Sent By dpalmer Date 2002-05-01 Time 19:09 Rev Time 0.00
Received By dpalmer Date 2002-05-01 Time 19:09 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2002-04-30 Cont ID  
Sent By dpalmer Date 2002-04-30 Time 20:30 Rev Time 0.00
Received By dpalmer Date 2002-04-30 Time 20:30 Sent To  
Notes
2002-04-30 00:00:00CALLED CONT FOR COMMENTS.4/30
  
 MISSING AIC RATINGS FOR MAIN DISC`S
 PER 110-9
 MISSING WALK IN COOLER LTS.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-03-13 Cont ID  
Sent By dpalmer Date 2002-03-13 Time 13:32 Rev Time 0.00
Received By dpalmer Date 2002-03-13 Time 13:32 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-01-24 Cont ID  
Sent By dpalmer Date 2002-01-24 Time 07:06 Rev Time 0.00
Received By dpalmer Date 2002-01-24 Time 07:06 Sent To  
Notes
2002-01-24 00:00:00***************** UNSAT ***************
  
 1)NOTE: PLEASE NOTE, A-7 SHOWS A NEW
 3-PHASE SERICE BEING INSTALLED, RISER
 ALSO SHOWS THE SAME, EXCEPT FOR METER/
 RISER? PLEASE CLARFIY SIZE EXSITING
 SERVICE ENTRANCE CONDUCTORS. PLEASE
 CLARIFY EXISTING GROUNDING ELECTRODE
 LOCATIONS OF ATTACHMENT.
  
 2)NOTE: PLEASE CLARFIY LOCATION OF RECEP
 FOR ROOFTOP ACCU`S. 210-63.
  
 3)NOTE: PLEASE NOTE OUTLET FOR SIGNAGE
 PER 600-5. CLARIFY IF EXISTING?
  
 4)NOTE: PLEASE NOTE SPACING FOR SHOW
 WINDOW OUTLETS PER 210-62. PLEASE
 CLARFIY IF EXISTING?
  
 5)NOTE: PLEASE NOTE AND OR CLARFIY OCP
 SHOWN FOR ITEMS ON PANEL SCHEDULE THAT
 SHOW 25A,35A OCP ON #12 AND #10. PLEASE
 SEE 310-16, SHOW`S "*" #12/#10WHICH
 REFERS TO 240-3D. PLEASE NOTE 240-3
 LIMITS OCP TO 15/20/30AMPS.
  
 6)NOTE: PLEASE CLARIFY CONDUCTOR SIZES
 BETWEEN MAIN DISC`S AND PANELS AND
 EQUIPMENT GROUNIDNG CONDCUTORS PER
 250-122.
  
 PLEASE SUBMIT THE ABOVE INFORMAITON FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-03-19 Cont ID  
Sent By mcarsill Date 2002-03-19 Time 09:18 Rev Time 0.00
Received By mcarsill Date 2002-03-19 Time 09:18 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-01-24 Cont ID  
Sent By mcarsill Date 2002-01-24 Time 11:05 Rev Time 0.00
Received By mcarsill Date 2002-01-24 Time 11:05 Sent To  
Notes
2002-01-24 00:00:001) PLEASE BE ADVISED THAT THIS LOCATION
 IS LOCATED WITHIN THE CITY FIRE LIMITS.
 PLEASE SEE LOCAL AMENDMENTS, APPENDIX F,
 CITY OF WEST PALM BEACH.
 2) PLEASE PROVIDE INTERIOR FINISH
 INFORMATION FOR WALLS AND CEILINGS.
 3) PROVIDE SEPARATE PLANS AND PERMITS
 FOR NEW FIRE SUPPRESSION SYSTEM.
 4) PLEASE INDICATE ON THE PLANS THAT
 ONLY SINGLE CYLINDER DEADBOLTS WILL
 BE USED.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-03-18 Cont ID  
Sent By pkrauss Date 2002-03-18 Time 13:03 Rev Time 0.30
Received By pkrauss Date 2002-03-18 Time 10:15 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-02-05 Cont ID  
Sent By pkrauss Date 2002-02-05 Time 12:26 Rev Time 0.40
Received By pkrauss Date 2002-02-05 Time 12:26 Sent To  
Notes
2002-02-05 00:00:00 
 PROVISO:
  
  
 PRIOR TO CONNECTING TO ANY EXISTING
 DUCTWORK, CALL FOR AN INSPECTION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 4 Status P Date 2002-04-22 Cont ID  
Sent By kstevens Date 2002-04-22 Time 15:02 Rev Time 0.00
Received By kstevens Date 2002-04-22 Time 15:02 Sent To  
Notes
2002-04-22 00:00:00REVISION OK - CHANGE SAFE WASTE TO FLOOR
 SINK (5)

Review Stop P PLUMBING
Rev No 3 Status P Date 2002-03-26 Cont ID  
Sent By kstevens Date 2002-03-26 Time 09:42 Rev Time 0.00
Received By kstevens Date 2002-03-26 Time 09:42 Sent To  
Notes
2002-03-26 00:00:00PASSED/PROVISO - PER PETE RUSSO - AN
 EXISTING DRYWELL FOR CONDENSATE IS ON
 SITE. KS

Review Stop P PLUMBING
Rev No 2 Status F Date 2002-03-19 Cont ID  
Sent By kstevens Date 2002-03-19 Time 13:35 Rev Time 2.00
Received By kstevens Date 2002-03-19 Time 13:35 Sent To  
Notes
2002-03-19 00:00:00DENIED
 REFERENCE: SPC-94 - FACBC-97 - SGC-97
  
 1) FROM PREVIOUS REVIEW. PLEASE SUBMIT
 AN EXISTING FLOOR PLAN TO DETERMINE THE
 SCOPE OF REMODELING.
 2) FROM PREVIOUS REVIEW. SEPARATE GAS
 PERMIT REQUIRED. PLEASE SEE ATTACHED GAS
 PERMIT APPLICATION REQUIREMENTS SHEET &
 SUPPLY INFORMATION GAS PLAN REVIEW.
 3) SEPARATE GAS DEMO PERMIT WILL BE RE-
 QUIRED.
 4) FROM PREVIOUS REVIEW. SHT A-8 CONDEN-
 SATE A/C NOTE #15 CONDENSATE TO DRAIN TO
 DRYWELL OR STORM OUTSIDE OF BLDG. CONDEN
 SATE LINE SHALL HAVE A RELIEF VENT NEAR
 BLDG.-THIS #15 HAS BEEN CHANGED AND
 I SEE NO REFERENCE TO CONDENSATE ON THE
 PAGE IN QUESTION. PLEASE SUBMIT A DETAIL
 FOR THE CONDENSATE DRAIN.
 5) FROM PREVIOUS REVIEW. ROOF PLAN.
 PLEASE CALCULATIONS FOR PRIMARY AND
 SECONDARY ROOF DRAINS USING SPC SEC 1108
 AND 1109. INCLUDE 1/2 AREA OF ALL VERTI-
 CAL WALLS. SHOW LOCATIONS FOR PRIMARY
 AND SECONDARY DRAINS AND SHOW DETAILS
 FOR SIZE AND SHOW RISER WITH PIPE SIZES.
 6) FROM PREVIOUS REVIEW. NEW GREASE TRAP
 SHALL HAVE TO BE INSTALLED OUTSIDE OF
 THE BLDG PER CONVERSATION WITH RODNEY
 COMPO. HE INDICATES THAT THE GREASE TRAP
 DOES NOT MEET CODE AND THAT THE BAFFLES
 HAVE BEEN REMOVED. SEPARATE SANITARY AND
 GREASE LINE SHALL BE REQUIRED. PLEASE
 INDICATE SEPARATE LINES WHEN RESUBMITT-
 ING PLANS.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-01-30 Cont ID  
Sent By kstevens Date 2002-01-30 Time 18:51 Rev Time 1.25
Received By kstevens Date 2002-01-30 Time 18:48 Sent To  
Notes
2002-01-30 00:00:00DENIED
 REFERENCE: SPC-94 - FABCB-97
  
 1) PLEASE SUBMIT AN EXISTING FLOOR PLAN
 TO DETERMINE SCOPE OF REMODELING.
 2) SEPARATE GAS PERMIT REQUIRED. SEE
 ATTACHED GAS PERMIT APPLICATION REQUIRE-
 MENT SHEET AND SUPPLY INFORMATION FOR
 GAS PLAN REVIEW.
 3) SEPARATE GAS DEMO PERMIT REQUIRED.
 4) ROUTE PLANS TO DEPT. OF BUSINESS REG-
 ULATION, HOTEL AND RESTURANT DIV. FOR
 PLAN REVIEW BEFORE RESUBMITING TO CITY.
 COUNTYWIDE AMENDMENTS TO SPC SEC 101.4.7
 5) SHT A-5 WATER FILTRATION SYSTEM SHALL
 BE NSF APPROVED PER SPC SEC 615.1, 615.2
 SUBMIT MANUFACTURE INFO
 6) SHT A-8 CONDENSATE A/C NOTE #15. CON-
 DENSATE TO DRAIN TO DRYWELL OR STORM OUT
 SIDE OF BLDG. CONDENSATE DRAIN LINE
 SHALL HAVE A RELIEF VENT NEAR BLDG.
 PLEASE SHOW DETAILS.
 7) ROOF PLAN, PLEASE SUBMIT CALCULATIONS
 FOR PRIMARY AND SECONDARY ROOF DRAINS
 USING SPC SEC 1108, AND 1109. SHOW LOC-
 ATIONS FOR PRIMARY AND SECONDARY DRAINS
 AND SHOW DETAILS FOR SIZE AND SHOW RISER
 WITH PIPE SIZE.
 8) SHT A-3 PLEASE SUBMIT EQUIPMENT SCHED
 THAT CORRESPONDS TO EQUIPMENT FLOOR PLAN
 9) RODNEY COMPO, ENVIRONMENTAL COMPLI-
 ANCE TO INSPECT GREAS TRAP LOCATED IN
 BLDG TO DETERMINE IF MAINTENANCE HAS
 BEEN PROVIDED AND IF IT STILL MEETS CODE
 IF NOT GREASE TRAP SHALL HAVE TO BE IN-
 STALLED OUTSIDE BLDG.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status P Date 2002-01-23 Cont ID  
Sent By sgraham Date 2002-01-23 Time 12:05 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***