| 2002-02-01 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 659 8096 EXT 8499 |
| | |
| | SBC = STANDARD BUILDING CODE 1997 |
| | SBC*= STANDARD BUILD'G CODE (CITY AMEND) |
| | FL ENERGY CODE = FLORIDA ENERGY |
| | EFFICIENCY CODE FOR BUILD'G CONSTR'N |
| | |
| | 1) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 2) SBC* 104.1.1A SEPARATE HURRICANE |
| | MISSILE IMPACT SHUTTER PERMIT IS REQ'D. |
| | |
| | 3) SBC* 104.2 DETAILS SHALL BE SUBMITTED |
| | OF THE BEAM, AND IT'S SUPPORTING HEADER |
| | STUDS, AT THE OPENING THROUGH THE |
| | EXISTING WALL TO FORM THE NEW BAY WINDOW |
| | |
| | 4) SBC* 104.2 THE PLANS SHALL BE AMENDED |
| | TO SHOW WINDOW BUCKS AND HEADERS IN |
| | ACCORDANCE WITH THE SUBMITTED WINDOW |
| | PRODUCT APPROVALS. |
| | |
| | 5) IS THE EXISTING FRONT ENTRANCE DOOR |
| | TO BE RE-USED?IF NOT, THEN PRODUCT |
| | APPROVAL IS REQUIRED FOR THE NEW DOOR. |
| | |
| | 6) SBC* 104.2DETAILS/DESIGN AND |
| | FASTENING SPECIFICATION FOR THE FOYER |
| | ROOF TRUSSES SHALL BE SUBMITTED. |
| | |
| | 7) SBC* 1503.1.2.2 AND SBC 2308.2.2.1 |
| | THE PLANS SHALL BE AMENDED TO SHOW MIN. |
| | 5/8" PLYWOOD (OR EQUIVALENT) SHEATHING |
| | ON THE NEW WALLS AND FOYER ROOF AND THE |
| | MEANS OF FASTENING TO THE FRAME/TRUSSES |
| | IN ACCORDANCE WITH SBC* TABLE 2306.1 |
| | |
| | 8) SBC 1503.1.1THE PLANS SHALL BE |
| | AMENDED TO ANNOTATE THE ROOF COVERING ON |
| | THE FOYER ROOF. |
| | |
| | 9) SBC* 104.2THE PLANS SHALL BE |
| | AMENDED TO SHOW THE MEANS OF ANCHORING |
| | THE NEW WOOD FRAMED WALLS TO THE |
| | FOUNDATIONS AND TO THE EXISTING WALLS. |
| | |
| | 10) SBC* 104.2THE PLANS SHALL BE |
| | AMENDED TO SHOW THE MEANS OF TYING THE |
| | NEW SLAB/FOUNDATIONS TO THE EXISTING. |
| | |
| | 11) SBC 1804.1.3THE PLANS SHALL BE |
| | AMENDED TO SHOW THE BASE OF THE NEW |
| | FOUNDATIONS TO BE AT LEAST 12" BELOW |
| | FINISH GRADE. |
| | |
| | 12) SBC* 2304.1.2THE SOIL SHALL BE |
| | TREATED AGAINST TERMITES PRIOR TO THE |
| | PLACEMENT OF THE CONCRETE SLABS. |
| | |
| | 13) SBC* 2304.2.5WOOD SIDING SHALL BE |
| | AT LEAST 6" CLEAR OF FINISH GRADE EARTH. |
| | |
| | 14) SBC 2304.3.2ALL WOOD FRAMING AND |
| | SHEATHING LESS THAN 8" FROM EXPOSED |
| | EARTH SHALL BE APPROVED NATURALLY |
| | DURABLE OR PRESSURE TREATED WOOD. |
| | |
| | 15)FL ENERGY CODE 101.2.2ADDITIONS |
| | TO EXISTING RESIDENTIAL BUILDINGS SHALL |
| | COMPLY WITH THE REQUIREMENTS OF EITHER |
| | METHOD A, B OR C OF CHAPTER 6. |
| | |
| | 16) FL ENERGY CODE 103.0COMPLIANCE |
| | SHALL BE DEMONSTRATED BY SUBMITTAL OF |
| | APPROPRIATE ENERGY CODE COMPLIANCE FORMS |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |
| | THE CODE REFERENCES GIVE ADDITIONAL INFO |
| | IF YOU HAVE ANY QUERIES PLEASE CALL: |
| | ROBERT BROWN(561) 659 8096 EXT 8499 |