| Plan Review Stops For Permit 02010567 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2002-03-06 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2002-03-06 |
Time |
08:58 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2002-03-06 |
Time |
08:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2002-03-01 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2002-03-01 |
Time |
13:46 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2002-03-01 |
Time |
13:45 |
Sent To |
|
|
| Notes |
| 2002-03-01 00:00:00 | BUILDING PLAN REVIEW | | | *******DENIED******* | | | ROBERT BROWN(561) 659 8096 EXT 8499 | | | | | | SBC = STANDARD BUILDING CODE 1997 | | | SBC*= STANDARD BUILD'G CODE (CITY AMEND) | | | | | | FOR CONSISTENCY, THE FOLLOWING COMMENTS | | | ARE NUMBERED AS PER THE BUILDING PLAN | | | REVIEW OF 1/23/02: | | | | | | 2) SBC 1007.3.1 DIMENSIONAL RELATIONSHIP | | | BETWEEN STAIR RISER HEIGHT (R) AND TREAD | | | DEPTH (T).FOR THE STAIR BETWEEN THE | | | 'PRIVATE AREA' AND 'EXISTING DECK', THE | | | RELATIONSHIP 2R+T STILL DOES NOT COMPLY | | | WITH THE REQUIREMENT FOR 24<=2R+T<=25. | | | NOTE: ARCHITECT HAS BEEN ADVISED AND HAS | | | AGREED TO ALTER AND INITIAL THE PLANS,AT | | | TIME OF PICK-UP, TO ACHIEVE COMPLIANCE. | | | | | | **QUOTE PERMIT# ON ALL CORRESPONDENCE** | | | | | | END OF REVIEW COMMENTS | | | THE CODE REFERENCES GIVE ADDITIONAL INFO | | | IF YOU HAVE ANY QUERIES PLEASE CALL: | | | ROBERT BROWN(561) 659 8096 EXT 8499 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2002-01-23 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2002-01-23 |
Time |
20:02 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2002-01-23 |
Time |
20:02 |
Sent To |
|
|
| Notes |
| 2002-01-23 00:00:00 | BUILDING PLAN REVIEW | | | *******DENIED******* | | | ROBERT BROWN(561) 659 8096 EXT 8499 | | | | | | SBC = STANDARD BUILDING CODE | | | SBC*= STANDARD BUILD'G CODE (AMENDMENTS) | | | FL ACC CODE = FLORIDA ACCESSIBILITY CODE | | | | | | 1) A RECORDED COPY OF THE NOTICE OF | | | COMMENCEMENT MUST BE SUBMITTED BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | 2) SBC 1007.3.1STAIR TREADS AND RISERS | | | SHALL BE SO PROPORTIONED THAT THE SUM OF | | | TWO RISERS (2R) AND A TREAD (T), | | | EXCLUSIVE OF NOSING PROJECTION, IS NOT | | | LESS THAN 24" NOR MORE THAN 25". | | | TYPICAL STEP DETAIL 5/A-2 SHOWS A 6" | | | TYPICAL RISER HEIGHT.MULTIPLES OF 6" | | | DO NOT CORRELATE TO THE REQUIRED DECK OR | | | PRIVATE AREA HEIGHTS OF 14" AND 28" AFF | | | RESPECTIVELY.AMEND THE TREAD/RISER | | | RELATIONSHIP.NOTE THAT INCREASING THE | | | RISER TO 7" WITH THE PROPOSED 13" TREAD | | | WILL NOT COMPLY WITH THE REQUIREMENT FOR | | | 24"<=2R+T<=25". | | | | | | 3) FL ACC CODE 4.32.3DETAIL 5/A-3, | | | H.C. BAR STATION.THE WALL FIXTURE FOR | | | THE BAR SUPPORT BRACKET, SHOWN ON THE | | | CROSS-SECTION, SHALL NOT PROTRUDE INTO | | | THE REQUIRED 27" HIGH BY 19" DEEP KNEE | | | CLEARANCE SPACE. | | | | | | **QUOTE PERMIT# ON ALL CORRESPONDENCE** | | | | | | END OF REVIEW COMMENTS | | | THE CODE REFERENCES GIVE ADDITIONAL INFO | | | IF YOU HAVE ANY QUERIES PLEASE CALL: | | | ROBERT BROWN(561) 659 8096 EXT 8499 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2002-03-05 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-03-05 |
Time |
12:47 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-03-05 |
Time |
12:32 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2002-01-18 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-01-18 |
Time |
14:27 |
Rev Time |
1.00 |
| Received By |
btrobaug |
Date |
2002-01-18 |
Time |
13:26 |
Sent To |
|
|
| Notes |
| 2002-01-18 00:00:00 | ****************UNSAT!****************** | | | 1) PLEASE PROVIDE DEMOLITION PLANS | | | INDICATING REUSE OR TERMINATION OF | | | EXISTING WIRING. | | | 2) ONLY PAGE "EI OF 2" WAS SUBMITTED FOR | | | REVIEW ? | | | 3) PROVIDE LOAD CALCULATIONS FOR | | | EXISTING PANELS. | | | 4) PROVIDE LOAD CALCULATIONS FOR | | | ADDITION LOADS ON EXISTING PANELS. | | | 5) PROVIDE PLANS FOR ROOF TOP ACCU'S & | | | LOCATION OF REQUIRED GFI'S AS PER | | | 210-63NEC AND 309.2 SBCCI MECHANICAL | | | CODE. | | | 6) PROVIDE TITLE BLOCK ON PANEL | | | SCHEDULES PER 61G1-16.004. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | (561) 659-8096 EXT.8392 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
N |
Date |
2002-01-24 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-01-24 |
Time |
15:01 |
Rev Time |
0.05 |
| Received By |
pkrauss |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2002-02-28 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-02-28 |
Time |
09:36 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-02-28 |
Time |
09:36 |
Sent To |
|
|
| Notes |
| 2002-02-28 00:00:00 | A) PLEASE PROVIDE PRODUCT APPROVALS FOR | | | FIRE RETARDANT FABRIC. | | | B) INTERIOR FINISH INFORMATION ON WALLS | | | AND CEILINGS SHALL COMPLY WITH | | | APPLICABLE FIRE CODE REQUIREMENTS. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2002-01-16 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-01-16 |
Time |
12:23 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-01-16 |
Time |
12:23 |
Sent To |
|
|
| Notes |
| 2002-01-16 00:00:00 | 1) ONE SET OF PLANS MISSING FP1 SHEET. | | | 2) NO INTERIOR FINISH INFORMATION | | | PROVIDED FOR WALLS AND CEILINGS. | | | 3) THE PLATFORM IS TO BE CONSTRUCTED | | | FOR THE TYPE OF BUILDING CONSTRUCTION IN | | | WHICH IS LOCATED. ANY ITEMS BELOW THE | | | PLATFORM BESIDES ELECTRICAL WIRING OR | | | PLUMBING FIXTURES, THE FLOOR MUST BE | | | ONE HOUR FIRE RATED. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2002-01-24 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-01-24 |
Time |
15:00 |
Rev Time |
0.20 |
| Received By |
pkrauss |
Date |
2002-01-24 |
Time |
15:00 |
Sent To |
|
|
| Notes |
| 2002-01-24 00:00:00 | MECHANICAL PLANS & PERMIT SUBMITTED | | | SEPERATELY. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2002-04-18 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-04-18 |
Time |
09:29 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2002-04-18 |
Time |
09:29 |
Sent To |
|
|
| Notes |
| 2002-04-18 00:00:00 | REVISION OK - ADD ICE MACHINE - FLOOR | | | SINK. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2002-03-04 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-03-04 |
Time |
17:53 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2002-03-04 |
Time |
17:53 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2002-01-22 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-01-22 |
Time |
16:33 |
Rev Time |
2.00 |
| Received By |
kstevens |
Date |
2002-01-22 |
Time |
16:33 |
Sent To |
|
|
| Notes |
| 2002-01-22 00:00:00 | DENIED | | | REFERENCE: SPC-94-FACBC-97 | | | | | | 1) ROUTE PLANS TO PALM BEACH COUNTY | | | HEALTH UNIT DIVISION OF ENVIRONMENTAL | | | HEALTH 901 EVERNIA STREET, WPB FL 33401 | | | PHONE # (561) 355-3018. PLEASE ROUTE BE- | | | FORE PLAN REVIEW. | | | 2) EXISTING FLOOR PLAN REQUIRED FOR DEMO | | | 3) SHT A1. TURNING RADIUS TO BE SHOWN IN | | | REST ROOM NOT IN STALL. (SEE FIG. 30(E)) | | | PLEASE SHOW DETAIL ON PLANS. | | | 4) SHT P-1 OF 2, INDIRECT WASTE TO BE | | | DRAINED TO FLOOR SINK NOT FLOOR DRAIN. | | | SPC SEC 804.1 & 804.5 | | | 5) SHT P-2 0F 2 NOTES #'S 6 & 7 AIR | | | CHAMBERS ARE TEMPORY FIX AND SHALL HAVE | | | ACESS AND BE RECHARGEABLE PER SPC SEC | | | 607.8.3. WATER HAMMER ARRESTORS ARE RE- | | | COMMENDED. | | | 6) SHT P-2 OF 2 WATER HAMMER ARRESTORS | | | SHALL BE LOCATED NEAR THE FIXTURES IN AN | | | "EFFECTIVE RANGE" NOT AT TOP OF DROP AS | | | SHOWN. (SEE ATTACHED SHEET) LOCATE ARRES | | | TORS PER MANUFACTURES INSTALLATION INST- | | | RUCTIONS AND PDI-WH 201. | | | 7) SHT P-2 OF 2, WATER HEATER LOCATION | | | REQUIRES A PERMINATE SHIPS LADDER AND A | | | SERVICE PLATFORM, MIMIMUM OF 30"X30" AT | | | SERVICE SIDE OF WATER HEATER. SHOW DE- | | | TAILS. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
2002-01-24 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-01-24 |
Time |
15:01 |
Rev Time |
0.05 |
| Received By |
pkrauss |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|