Plan Review Details - Permit 02010567
Plan Review Stops For Permit 02010567
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2002-03-06 Cont ID  
Sent By rbrown Date 2002-03-06 Time 08:58 Rev Time 0.00
Received By rbrown Date 2002-03-06 Time 08:58 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2002-03-01 Cont ID  
Sent By rbrown Date 2002-03-01 Time 13:46 Rev Time 0.00
Received By rbrown Date 2002-03-01 Time 13:45 Sent To  
Notes
2002-03-01 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 SBC = STANDARD BUILDING CODE 1997
 SBC*= STANDARD BUILD'G CODE (CITY AMEND)
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEW OF 1/23/02:
  
 2) SBC 1007.3.1 DIMENSIONAL RELATIONSHIP
 BETWEEN STAIR RISER HEIGHT (R) AND TREAD
 DEPTH (T).FOR THE STAIR BETWEEN THE
 'PRIVATE AREA' AND 'EXISTING DECK', THE
 RELATIONSHIP 2R+T STILL DOES NOT COMPLY
 WITH THE REQUIREMENT FOR 24<=2R+T<=25.
 NOTE: ARCHITECT HAS BEEN ADVISED AND HAS
 AGREED TO ALTER AND INITIAL THE PLANS,AT
 TIME OF PICK-UP, TO ACHIEVE COMPLIANCE.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUERIES PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-01-23 Cont ID  
Sent By rbrown Date 2002-01-23 Time 20:02 Rev Time 0.00
Received By rbrown Date 2002-01-23 Time 20:02 Sent To  
Notes
2002-01-23 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 SBC = STANDARD BUILDING CODE
 SBC*= STANDARD BUILD'G CODE (AMENDMENTS)
 FL ACC CODE = FLORIDA ACCESSIBILITY CODE
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) SBC 1007.3.1STAIR TREADS AND RISERS
 SHALL BE SO PROPORTIONED THAT THE SUM OF
 TWO RISERS (2R) AND A TREAD (T),
 EXCLUSIVE OF NOSING PROJECTION, IS NOT
 LESS THAN 24" NOR MORE THAN 25".
 TYPICAL STEP DETAIL 5/A-2 SHOWS A 6"
 TYPICAL RISER HEIGHT.MULTIPLES OF 6"
 DO NOT CORRELATE TO THE REQUIRED DECK OR
 PRIVATE AREA HEIGHTS OF 14" AND 28" AFF
 RESPECTIVELY.AMEND THE TREAD/RISER
 RELATIONSHIP.NOTE THAT INCREASING THE
 RISER TO 7" WITH THE PROPOSED 13" TREAD
 WILL NOT COMPLY WITH THE REQUIREMENT FOR
 24"<=2R+T<=25".
  
 3) FL ACC CODE 4.32.3DETAIL 5/A-3,
 H.C. BAR STATION.THE WALL FIXTURE FOR
 THE BAR SUPPORT BRACKET, SHOWN ON THE
 CROSS-SECTION, SHALL NOT PROTRUDE INTO
 THE REQUIRED 27" HIGH BY 19" DEEP KNEE
 CLEARANCE SPACE.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUERIES PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-03-05 Cont ID  
Sent By dpalmer Date 2002-03-05 Time 12:47 Rev Time 0.00
Received By dpalmer Date 2002-03-05 Time 12:32 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-01-18 Cont ID  
Sent By btrobaug Date 2002-01-18 Time 14:27 Rev Time 1.00
Received By btrobaug Date 2002-01-18 Time 13:26 Sent To  
Notes
2002-01-18 00:00:00****************UNSAT!******************
 1) PLEASE PROVIDE DEMOLITION PLANS
 INDICATING REUSE OR TERMINATION OF
 EXISTING WIRING.
 2) ONLY PAGE "EI OF 2" WAS SUBMITTED FOR
 REVIEW ?
 3) PROVIDE LOAD CALCULATIONS FOR
 EXISTING PANELS.
 4) PROVIDE LOAD CALCULATIONS FOR
 ADDITION LOADS ON EXISTING PANELS.
 5) PROVIDE PLANS FOR ROOF TOP ACCU'S &
 LOCATION OF REQUIRED GFI'S AS PER
 210-63NEC AND 309.2 SBCCI MECHANICAL
 CODE.
 6) PROVIDE TITLE BLOCK ON PANEL
 SCHEDULES PER 61G1-16.004.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 (561) 659-8096 EXT.8392

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2002-01-24 Cont ID  
Sent By pkrauss Date 2002-01-24 Time 15:01 Rev Time 0.05
Received By pkrauss Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-02-28 Cont ID  
Sent By mcarsill Date 2002-02-28 Time 09:36 Rev Time 0.00
Received By mcarsill Date 2002-02-28 Time 09:36 Sent To  
Notes
2002-02-28 00:00:00A) PLEASE PROVIDE PRODUCT APPROVALS FOR
 FIRE RETARDANT FABRIC.
 B) INTERIOR FINISH INFORMATION ON WALLS
 AND CEILINGS SHALL COMPLY WITH
 APPLICABLE FIRE CODE REQUIREMENTS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-01-16 Cont ID  
Sent By mcarsill Date 2002-01-16 Time 12:23 Rev Time 0.00
Received By mcarsill Date 2002-01-16 Time 12:23 Sent To  
Notes
2002-01-16 00:00:001) ONE SET OF PLANS MISSING FP1 SHEET.
 2) NO INTERIOR FINISH INFORMATION
 PROVIDED FOR WALLS AND CEILINGS.
 3) THE PLATFORM IS TO BE CONSTRUCTED
 FOR THE TYPE OF BUILDING CONSTRUCTION IN
 WHICH IS LOCATED. ANY ITEMS BELOW THE
 PLATFORM BESIDES ELECTRICAL WIRING OR
 PLUMBING FIXTURES, THE FLOOR MUST BE
 ONE HOUR FIRE RATED.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2002-01-24 Cont ID  
Sent By pkrauss Date 2002-01-24 Time 15:00 Rev Time 0.20
Received By pkrauss Date 2002-01-24 Time 15:00 Sent To  
Notes
2002-01-24 00:00:00MECHANICAL PLANS & PERMIT SUBMITTED
 SEPERATELY.

Review Stop P PLUMBING
Rev No 3 Status P Date 2002-04-18 Cont ID  
Sent By kstevens Date 2002-04-18 Time 09:29 Rev Time 0.00
Received By kstevens Date 2002-04-18 Time 09:29 Sent To  
Notes
2002-04-18 00:00:00REVISION OK - ADD ICE MACHINE - FLOOR
 SINK.

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-03-04 Cont ID  
Sent By kstevens Date 2002-03-04 Time 17:53 Rev Time 0.50
Received By kstevens Date 2002-03-04 Time 17:53 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-01-22 Cont ID  
Sent By kstevens Date 2002-01-22 Time 16:33 Rev Time 2.00
Received By kstevens Date 2002-01-22 Time 16:33 Sent To  
Notes
2002-01-22 00:00:00DENIED
 REFERENCE: SPC-94-FACBC-97
  
 1) ROUTE PLANS TO PALM BEACH COUNTY
 HEALTH UNIT DIVISION OF ENVIRONMENTAL
 HEALTH 901 EVERNIA STREET, WPB FL 33401
 PHONE # (561) 355-3018. PLEASE ROUTE BE-
 FORE PLAN REVIEW.
 2) EXISTING FLOOR PLAN REQUIRED FOR DEMO
 3) SHT A1. TURNING RADIUS TO BE SHOWN IN
 REST ROOM NOT IN STALL. (SEE FIG. 30(E))
 PLEASE SHOW DETAIL ON PLANS.
 4) SHT P-1 OF 2, INDIRECT WASTE TO BE
 DRAINED TO FLOOR SINK NOT FLOOR DRAIN.
 SPC SEC 804.1 & 804.5
 5) SHT P-2 0F 2 NOTES #'S 6 & 7 AIR
 CHAMBERS ARE TEMPORY FIX AND SHALL HAVE
 ACESS AND BE RECHARGEABLE PER SPC SEC
 607.8.3. WATER HAMMER ARRESTORS ARE RE-
 COMMENDED.
 6) SHT P-2 OF 2 WATER HAMMER ARRESTORS
 SHALL BE LOCATED NEAR THE FIXTURES IN AN
 "EFFECTIVE RANGE" NOT AT TOP OF DROP AS
 SHOWN. (SEE ATTACHED SHEET) LOCATE ARRES
 TORS PER MANUFACTURES INSTALLATION INST-
 RUCTIONS AND PDI-WH 201.
 7) SHT P-2 OF 2, WATER HEATER LOCATION
 REQUIRES A PERMINATE SHIPS LADDER AND A
 SERVICE PLATFORM, MIMIMUM OF 30"X30" AT
 SERVICE SIDE OF WATER HEATER. SHOW DE-
 TAILS.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status N Date 2002-01-24 Cont ID  
Sent By pkrauss Date 2002-01-24 Time 15:01 Rev Time 0.05
Received By pkrauss Date   Time   Sent To  
Notes
***NONE***