| Plan Review Stops For Permit 02010564 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2002-05-21 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2002-05-21 |
Time |
10:25 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2002-05-21 |
Time |
10:25 |
Sent To |
M |
|
| Notes |
| 2002-05-21 00:00:00 | BUILDING PLAN REVIEW | | | ******PROVISO******* | | | ROBERT BROWN(561) 659 8096 EXT 8499 | | | | | | SHEET A-1FLOOR PLAN.THE DOOR BETWEEN | | | THE LOUNGE AND THE BUILDING LOBBY SHALL | | | BE REVERSED TO OPEN AGAINST THE ELEVATOR | | | MACHINE ROOM WALL TO IMPROVE ACCESS FROM | | | THE PARKING GARAGE TO THE NEW AREA. | | | MARKED ON PLANS AS PER 5/21/02 TELEPHONE | | | CONVERSATION WITH GARY SMITH OF LEAR | | | ASSOCIATES. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2002-04-02 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2002-04-02 |
Time |
13:39 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2002-04-02 |
Time |
13:39 |
Sent To |
|
|
| Notes |
| 2002-04-02 00:00:00 | BUILDING PLAN REVIEW | | | *******DENIED******* | | | ROBERT BROWN(561) 659 8096 EXT 8499 | | | | | | FBC = FLORIDA BUILDING CODE 2001 | | | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) | | | | | | FOR CONSISTENCY, THE FOLLOWING COMMENTS | | | ARE NUMBERED AS PER THE BUILDING PLAN | | | REVIEW OF 1/22/02: | | | | | | 1) CONTRARY TO THE LEAR ASSOCIATES | | | RESPONSE LETTER RECEIVED 3/13/02 THIS | | | COMMENT HAS NOT BEEN ADDRESSED.A | | | RECORDED COPY OF THE NOTICE OF | | | COMMENCEMENT MUST BE SUBMITTED BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | 2) THE SWITCH FROM STANDARD BUILDING | | | CODE 1997 TO FLORIDA BUILDING CODE 2001 | | | IS NOTED. FOR SPRINKLERED BUILDINGS, FBC | | | TABLE 1004, NOTE 20, ALLOWS DEAD-END | | | CORRIDORS UPTO 50FT (COMPARED TO MAXIMUM | | | 20FT IN SBC).NO FURTHER ACTION REQ'D. | | | | | | 3) FBC 11-4.1.2(1)ACCESSIBLE ROUTE. | | | THIS COMMENT HAS NOT BEEN PROPERLY | | | ADDRESSED.ANNOTATE THE PLANS TO | | | DEMONSTRATE COMPLIANCE WITH THE | | | REQUIREMENTS FOR AT LEAST ONE ACCESSIBLE | | | ROUTE, TO THE ENTRANCE, FROM ACCESSIBLE | | | PARKING, PUBLIC SIDEWALKS AND PUBLIC | | | TRANSPORT,INDICATING CURB RAMPS, CHANGES | | | IN DIRECTION ETC. (REFER TO THE CODE FOR | | | FULL REQUIREMENTS). | | | | | | 4) FBC 11-4.1.3(10)DRINKING FOUNTAIN. | | | THIS COMMENT HAS NOT BEEN PROPERLY | | | ADDRESSED.THE SPOUT HEIGHT AND | | | CLEARANCES AT THE DRINKING FOUNTAIN, IN | | | ACCORDANCE WITH FIG 27, SHALL BE SHOWN | | | ON SHEET A-2. | | | | | | 5) FBC 11-4.35.4THIS COMMENT HAS NOT | | | BEEN PROPERLY ADDRESSED. THE PLANS SHALL | | | BE ANNOTATED TO SHOW THE BENCH MOUNTING | | | HEIGHT, REQUIRED TO BE BETWEEN 17" AND | | | 19" ABOVE FINISHED FLOOR. | | | | | | 8) FBC* 104.2.1.2NEW FLOOR SLAB.THE | | | PLANS STILL DO NOT SHOW CONTINUITY OF | | | REINFORCEMENT BETWEEN THE NEW SLAB AND | | | THE ADJACENT EXISTING CONCRETE USING | | | DOWEL BARS OR SIMILAR. | | | | | | **QUOTE PERMIT# ON ALL CORRESPONDENCE** | | | | | | END OF REVIEW COMMENTS | | | THE CODE REFERENCES GIVE ADDITIONAL INFO | | | IF YOU HAVE ANY QUERIES PLEASE CALL: | | | ROBERT BROWN(561) 659 8096 EXT 8499 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2002-01-22 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2002-01-22 |
Time |
15:24 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2002-01-22 |
Time |
15:24 |
Sent To |
|
|
| Notes |
| 2002-01-22 00:00:00 | BUILDING PLAN REVIEW | | | *******DENIED******* | | | ROBERT BROWN(561) 659 8096 EXT 8499 | | | | | | SBC = STANDARD BUILDING CODE | | | SBC*= STANDARD BUILD'G CODE (AMENDMENTS) | | | FL ACC CODE = FLORIDA ACCESSIBILITY CODE | | | | | | 1) A RECORDED COPY OF THE NOTICE OF | | | COMMENCEMENT MUST BE SUBMITTED BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | 2) SBC 1005.2DEAD-END POCKETS OR | | | HALLWAYS. EXITS AND EXIT ACCESS SHALL BE | | | SO ARRANGED THAT DEAD-END POCKETS IN | | | EXCESS OF 20FT LONG DO NOT OCCUR.AN | | | OCCUPANT IN THE SUBWAIT AND CHANGING | | | AREA WOULD HAVE NO ALTERNATIVE PATH OF | | | EGRESS UNTIL ARRIVAL AT THE DOOR TO THE | | | MAIN WAITING ROOM. FROM THIS POINT TWO | | | EGRESS ROUTES ARE AVAILABLE BUT THE | | | DEAD-END ALREADY TRAVERSED EXCEEDS 20FT. | | | AMEND PLANS TO DEMONSTRATE COMPLIANCE. | | | | | | 3) FL ACC CODE 4.1.2(1)AT LEAST ONE | | | ACCESSIBLE ROUTE TO THE FACILITY | | | ENTRANCE SHALL BE INDICATED ON THE KEY | | | PLAN. | | | | | | 4) FL ACC CODE 4.1.3(10)AN ACCESSIBLE | | | DRINKING FOUNTAIN, IN ACCORDANCE WITH | | | FL ACC CODE 4.15, SHALL BE CLEARLY SHOWN | | | ON THE FLOOR PLAN. | | | | | | 5) FL ACC CODE 4.1.3(21)WHERE CHANGING | | | ROOMS ARE PROVIDED, AT LEAST ONE SHALL | | | BE ACCESSIBLE IN ACCORDANCE WITH | | | FL ACC CODE 4.35 | | | | | | 6) FL ACC CODE 4.1.3(3)THE FLOOR | | | SURFACE ALONG ACCESSIBLE ROUTES SHALL | | | COMPLY WITH FL ACC CODE 4.5. WHERE | | | CARPET IS PROPOSED IT SHALL COMPLY WITH | | | FL ACC CODE 4.5.3 | | | | | | 7) SBC* 104.2.2SUBMIT SCAN EQUIPMENT | | | SUPPLIER'S DATA TO DESCRIBE ANY | | | OPERATIONAL OR SAFETY REQUIREMENT FOR | | | ISOLATION OF THIS ROOM THE REMAINDER OF | | | THE BUILDING. | | | | | | 8) SBC* 104.2.2 SUBMIT DETAILS TO | | | DESCRIBE THE MEANS OF REMOVAL OF THE | | | EXISTING FLOOR SLAB AND TYING OF THE NEW | | | SLAB TO THE EXISTING CONSTRUCTION | | | ADJACENT. | | | | | | **QUOTE PERMIT# ON ALL CORRESPONDENCE** | | | | | | END OF REVIEW COMMENTS | | | THE CODE REFERENCES GIVE ADDITIONAL INFO | | | IF YOU HAVE ANY QUERIES PLEASE CALL: | | | ROBERT BROWN(561) 659 8096 EXT 8499 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2002-05-13 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-05-13 |
Time |
16:57 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-05-13 |
Time |
16:57 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2002-03-28 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-03-28 |
Time |
06:18 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-03-28 |
Time |
06:18 |
Sent To |
|
|
| Notes |
| 2002-03-28 00:00:00 | *************** UNSAT ************** | | | | | | 1)NOTE: PLEASE NOTE THAT SHEET E-1 | | | HAS BEEN REVISED AND IS NOW SHOWING | | | 75 KVA TRANSFORMER "ABOVE"?? PLEASE | | | CLARIFY IF ABOVE, IS ABOVE CEILING OR | | | MOUNTED ON WALL ABOVE EQUIPMENT?? | | | 450-13B. | | | | | | 2)NOTE: PLEASE NOTE THAT METER LOCATION | | | IS NOTED IN RESPONSE LETTER AS LOCATION | | | CHANGED PER FIRST SET OF REVIEW NOTES | | | AND STILL SEEMS MENTIONS BEING ABOVE? | | | PLEASE NOTE THAT PER FPL REQ`MENTS AND | | | STANDARDS, ELEC METER ARE NOT TO BE | | | PLACED ABOVE CEILINGS OR ABOVE 6'5". | | | PLEASE CLARIFY. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2002-01-15 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-01-15 |
Time |
08:55 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-01-15 |
Time |
08:55 |
Sent To |
|
|
| Notes |
| 2002-01-15 00:00:00 | *************** UNSAT ***************** | | | | | | 1)NOTE: PLEASE SHOW LOCATION OF TRANSFOR | | | MER. | | | | | | 2)NOTE: PLEASE SEE E-1, PLEASE CLARIFY | | | METER AND DISCONNECT AAS BEING "ABOVE" | | | CEILING??? | | | PLEASE NOTE ACCESSILE SERVICE EQUIPMENT? | | | | | | 3)NOTE: PLEASE NOTE THAT THE LOAD | | | CALCULATIONS NEED TO BE SHOWN, PLEASE | | | NOTE THAT ALLCONTINUOUS LOADS ARE TO | | | SHOWN AT 125% 230-42 215-2. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
N |
Date |
2002-05-28 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2002-05-28 |
Time |
12:42 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2002-03-28 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-03-28 |
Time |
16:16 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-03-28 |
Time |
16:16 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2002-01-16 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-01-16 |
Time |
13:09 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-01-16 |
Time |
13:09 |
Sent To |
|
|
| Notes |
| 2002-01-16 00:00:00 | 1) PLEASE INDICATE LOCATIONS OF | | | ILLUMINATED EXIT SIGNS AND EMERGENCY | | | LIGHTING FIXTURES. | | | 2) PLEASE PROVIDE UL NUMBER FOR NEW | | | ONE-HOUR DEMISING WALL. | | | 3) THE HALLWAY NEAR THE SUBWAIT AREA | | | APPEARS TO CREATE A DEAD-END CONDITION. | | | THIS DESIGN MAY MEET MINIMUM CODE, BUT | | | IT IS NOT A PREFERRED ARRANGEMENT. | | | 4) PLEASE INDICATE INTERIOR FINISH | | | CLASSIFICATION INFORMATION FOR THE | | | WALLS AND CEILINGS. | | | 5) PLEASE INDICATE LOCATIONS OF FIRE | | | ALARM EQUIPMENT WITHIN TENANT | | | SPACE. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
5 |
Status |
P |
Date |
2002-06-19 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-06-19 |
Time |
13:18 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2002-06-19 |
Time |
12:47 |
Sent To |
|
|
| Notes |
| 2002-06-19 00:00:00 | PROVISO: | | | | | | PLEASE SUBMIT MANUFACTURER INSTALLATION | | | INSTRUCTIONS FOR THE FIRE DAMPERS SHOWN | | | ON PLAN SHEET M-2. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2002-05-28 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-05-28 |
Time |
15:00 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2002-05-28 |
Time |
15:00 |
Sent To |
|
|
| Notes |
| 2002-05-28 00:00:00 | PROVISO: | | | | | | PROVIDE ACCESS FOR BOOSTER FAN. | | | | | | PROVIDE FEEDBACK TO DRYER SHOULD BOOSTER | | | FAN "FAIL". | | | | | | AS PER 2001 FBC(M) 504.4, EXHAUST SHALL | | | TERMINATE ON THE OUTSIDE OF THE BUILDING | | | & SHALL BE EQUIPPED WITH A BACKDRAFT | | | DAMPER.SCREENS SHALL NOT BE INSTALLED | | | AT THE DUCT TERMINATION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2002-05-25 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2002-05-21 |
Time |
10:47 |
Rev Time |
0.45 |
| Received By |
hmoser |
Date |
2002-05-25 |
Time |
08:44 |
Sent To |
|
|
| Notes |
| 2002-05-17 00:00:00 | SPOKE WITH CONTRACTOR 5-17-02 - NEED | | | MANUFACTURER SUBMITTAL FOR THE VENTING | | | ON THE DRYER.INFORMATION SUBMITTED | | | DOES NOT SPECIFY MAXIMUM DISTANCE.I | | | ALSO INFORMED BRIAN SHOULD DRYER | | | EXHAUST BE GREATER THAN 2,000 CFM, | | | MAKE-UP AIR WILL BE REQUIRED AS PER | | | 504.5 | | | | | | CONTRACTOR TO FAX INFO MONDAY |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2002-04-03 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-04-03 |
Time |
10:45 |
Rev Time |
0.50 |
| Received By |
pkrauss |
Date |
2002-04-03 |
Time |
07:53 |
Sent To |
Z |
|
| Notes |
| 2002-04-03 00:00:00 | | | | PLANS CHANGED FROM THE 1997 STANDARD | | | MECHANICAL CODE TO THE 2001 FLORIDA | | | BUILDING CODE. | | | | | | MECHANICAL 401.5, OUTSIDE AIR EXHAUST & | | | INTAKE OPENINGS SHALL BE LCOATED A | | | MINIMUM OF 10 FT FROM LOT LINES OR | | | BUILDINGS ON THE SAME LOT. | | | | | | AS PER 2001 FBC, MECHANICAL 401.5.2, | | | EXHAUST OPENINGS SHALL BE LOCATED SO AS | | | NOT TO CREATE A NUISANCE.EXHAUST AIR | | | SHALL NOT BE DIRECTED ONTO WALKWAYS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2002-02-04 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-02-01 |
Time |
16:09 |
Rev Time |
1.50 |
| Received By |
pkrauss |
Date |
2002-02-01 |
Time |
15:37 |
Sent To |
Z |
|
| Notes |
| 2002-02-04 00:00:00 | *******************DENIED*************** | | | | | | PLAN SHEET A-1 THE "N" DIRECTIONAL IS | | | IN REALITY "EAST". | | | | | | PLEASE PROVIDE MANUFACTURER SUBMITTAL | | | DATA FOR THE DRYER. | | | | | | NOTE:OPENINGS SHALL BE SCREENED | | | | | | PROVIDE MANUFACTURER DRAWINGS AS | | | REFERENCED ON PLAN SHEET M-4. | | | | | | PLEASE NOTE, PLANS DO NOT INDICATE ANY | | | EXISTING EQUIPMENT THAT MAY BE LOCATED | | | ON THE LOWER ROOF.PLANS INDICATE THE | | | DISCHARGE OF THE QUENCH VENT SHALL BE | | | AWAY FROM AHU'S.THIS ALSO PERTAINS TO | | | THE STAIRWELL. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXZT. 8388. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2002-05-14 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-05-14 |
Time |
09:54 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2002-05-14 |
Time |
09:54 |
Sent To |
|
|
| Notes |
| 2002-05-14 00:00:00 | PASSED/PROVISO | | | | | | LOUNGE SINK SHALL BE 34" AFF PER FACBC- | | | SEC 4.24.2. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2002-04-18 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-04-18 |
Time |
10:33 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2002-04-18 |
Time |
10:33 |
Sent To |
|
|
| Notes |
| 2002-04-18 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 11 | | | | | | 1) FROM PREVIOUS REVIEW: PLEASE PROVIDE | | | DETAILS FOR LOUNGE SINK SHT A-1. COMPLY | | | WITH SECTION 4.24.2 | | | 2) SHT P-1 PLEASE PROVIDE INFORMATION | | | FOR SERVICE SINK ON PLUMBING FIXTURE | | | SCHEDULE WITH OTHER FIXTURES. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2002-01-31 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-01-31 |
Time |
13:33 |
Rev Time |
1.25 |
| Received By |
kstevens |
Date |
2002-01-29 |
Time |
18:23 |
Sent To |
|
|
| Notes |
| 2002-01-31 00:00:00 | DENIED | | | REFERENCE: SPC-94-FACBC-97 | | | | | | 1) SHT A-1 SPC TABLE 407 REQUIRES TWO | | | WATER CLOSETS AND TWO LAVS FOR WOMENS | | | RESTROOM. 1 EA PROVIDED. | | | | | | 2) SHT A-2 WATER FOUNTAIN DETAIL. PER | | | FACBC SEC 4.1.3(10) PROVISIONS SHALL BE | | | PROVIDED FOR THOSE WHO HAVE DIFFICULTY | | | BENDING OR STOOPING. EITHER A HI/LOW DF | | | OR PROVIDE CUP DISPENSER. SHOW DETAILS. | | | | | | 3) SHT P-1 DOMESTIC WATER ISOMETRIC DIA. | | | WATER HAMMER ARRESTORS TO BE LOCATED PER | | | MANUFACTURE INSTALLATION INSTRUCTIONS & | | | PDI-WH 201, IN AN "EFFECTIVE RANGE" | | | CLOSE TO FIXTURE NOT ON TOP OF DROP AS | | | SHOWN. | | | | | | 4) SHT A-1 LOUNGE SINK. PLEASE PROVIDE | | | DETAILS TO SHOW COMPLIANCE WITH FACBC | | | SEC 4.24. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2002-05-09 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2002-05-09 |
Time |
11:47 |
Rev Time |
0.25 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-05-09 00:00:00 | PROVISO:STOREFRONT GLAZING TO BE CLEAR |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2002-04-11 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-04-11 |
Time |
16:22 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-04-11 00:00:00 | DENIED AS PER JOE MINICOZZI |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2002-04-04 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-04-04 |
Time |
10:40 |
Rev Time |
0.25 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|