Plan Review Details - Permit 02010564
Plan Review Stops For Permit 02010564
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2002-05-21 Cont ID  
Sent By rbrown Date 2002-05-21 Time 10:25 Rev Time 0.00
Received By rbrown Date 2002-05-21 Time 10:25 Sent To M
Notes
2002-05-21 00:00:00BUILDING PLAN REVIEW
 ******PROVISO*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 SHEET A-1FLOOR PLAN.THE DOOR BETWEEN
 THE LOUNGE AND THE BUILDING LOBBY SHALL
 BE REVERSED TO OPEN AGAINST THE ELEVATOR
 MACHINE ROOM WALL TO IMPROVE ACCESS FROM
 THE PARKING GARAGE TO THE NEW AREA.
 MARKED ON PLANS AS PER 5/21/02 TELEPHONE
 CONVERSATION WITH GARY SMITH OF LEAR
 ASSOCIATES.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2002-04-02 Cont ID  
Sent By rbrown Date 2002-04-02 Time 13:39 Rev Time 0.00
Received By rbrown Date 2002-04-02 Time 13:39 Sent To  
Notes
2002-04-02 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEW OF 1/22/02:
  
 1) CONTRARY TO THE LEAR ASSOCIATES
 RESPONSE LETTER RECEIVED 3/13/02 THIS
 COMMENT HAS NOT BEEN ADDRESSED.A
 RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE SWITCH FROM STANDARD BUILDING
 CODE 1997 TO FLORIDA BUILDING CODE 2001
 IS NOTED. FOR SPRINKLERED BUILDINGS, FBC
 TABLE 1004, NOTE 20, ALLOWS DEAD-END
 CORRIDORS UPTO 50FT (COMPARED TO MAXIMUM
 20FT IN SBC).NO FURTHER ACTION REQ'D.
  
 3) FBC 11-4.1.2(1)ACCESSIBLE ROUTE.
 THIS COMMENT HAS NOT BEEN PROPERLY
 ADDRESSED.ANNOTATE THE PLANS TO
 DEMONSTRATE COMPLIANCE WITH THE
 REQUIREMENTS FOR AT LEAST ONE ACCESSIBLE
 ROUTE, TO THE ENTRANCE, FROM ACCESSIBLE
 PARKING, PUBLIC SIDEWALKS AND PUBLIC
 TRANSPORT,INDICATING CURB RAMPS, CHANGES
 IN DIRECTION ETC. (REFER TO THE CODE FOR
 FULL REQUIREMENTS).
  
 4) FBC 11-4.1.3(10)DRINKING FOUNTAIN.
 THIS COMMENT HAS NOT BEEN PROPERLY
 ADDRESSED.THE SPOUT HEIGHT AND
 CLEARANCES AT THE DRINKING FOUNTAIN, IN
 ACCORDANCE WITH FIG 27, SHALL BE SHOWN
 ON SHEET A-2.
  
 5) FBC 11-4.35.4THIS COMMENT HAS NOT
 BEEN PROPERLY ADDRESSED. THE PLANS SHALL
 BE ANNOTATED TO SHOW THE BENCH MOUNTING
 HEIGHT, REQUIRED TO BE BETWEEN 17" AND
 19" ABOVE FINISHED FLOOR.
  
 8) FBC* 104.2.1.2NEW FLOOR SLAB.THE
 PLANS STILL DO NOT SHOW CONTINUITY OF
 REINFORCEMENT BETWEEN THE NEW SLAB AND
 THE ADJACENT EXISTING CONCRETE USING
 DOWEL BARS OR SIMILAR.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUERIES PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-01-22 Cont ID  
Sent By rbrown Date 2002-01-22 Time 15:24 Rev Time 0.00
Received By rbrown Date 2002-01-22 Time 15:24 Sent To  
Notes
2002-01-22 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 SBC = STANDARD BUILDING CODE
 SBC*= STANDARD BUILD'G CODE (AMENDMENTS)
 FL ACC CODE = FLORIDA ACCESSIBILITY CODE
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) SBC 1005.2DEAD-END POCKETS OR
 HALLWAYS. EXITS AND EXIT ACCESS SHALL BE
 SO ARRANGED THAT DEAD-END POCKETS IN
 EXCESS OF 20FT LONG DO NOT OCCUR.AN
 OCCUPANT IN THE SUBWAIT AND CHANGING
 AREA WOULD HAVE NO ALTERNATIVE PATH OF
 EGRESS UNTIL ARRIVAL AT THE DOOR TO THE
 MAIN WAITING ROOM. FROM THIS POINT TWO
 EGRESS ROUTES ARE AVAILABLE BUT THE
 DEAD-END ALREADY TRAVERSED EXCEEDS 20FT.
 AMEND PLANS TO DEMONSTRATE COMPLIANCE.
  
 3) FL ACC CODE 4.1.2(1)AT LEAST ONE
 ACCESSIBLE ROUTE TO THE FACILITY
 ENTRANCE SHALL BE INDICATED ON THE KEY
 PLAN.
  
 4) FL ACC CODE 4.1.3(10)AN ACCESSIBLE
 DRINKING FOUNTAIN, IN ACCORDANCE WITH
 FL ACC CODE 4.15, SHALL BE CLEARLY SHOWN
 ON THE FLOOR PLAN.
  
 5) FL ACC CODE 4.1.3(21)WHERE CHANGING
 ROOMS ARE PROVIDED, AT LEAST ONE SHALL
 BE ACCESSIBLE IN ACCORDANCE WITH
 FL ACC CODE 4.35
  
 6) FL ACC CODE 4.1.3(3)THE FLOOR
 SURFACE ALONG ACCESSIBLE ROUTES SHALL
 COMPLY WITH FL ACC CODE 4.5. WHERE
 CARPET IS PROPOSED IT SHALL COMPLY WITH
 FL ACC CODE 4.5.3
  
 7) SBC* 104.2.2SUBMIT SCAN EQUIPMENT
 SUPPLIER'S DATA TO DESCRIBE ANY
 OPERATIONAL OR SAFETY REQUIREMENT FOR
 ISOLATION OF THIS ROOM THE REMAINDER OF
 THE BUILDING.
  
 8) SBC* 104.2.2 SUBMIT DETAILS TO
 DESCRIBE THE MEANS OF REMOVAL OF THE
 EXISTING FLOOR SLAB AND TYING OF THE NEW
 SLAB TO THE EXISTING CONSTRUCTION
 ADJACENT.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUERIES PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2002-05-13 Cont ID  
Sent By dpalmer Date 2002-05-13 Time 16:57 Rev Time 0.00
Received By dpalmer Date 2002-05-13 Time 16:57 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2002-03-28 Cont ID  
Sent By dpalmer Date 2002-03-28 Time 06:18 Rev Time 0.00
Received By dpalmer Date 2002-03-28 Time 06:18 Sent To  
Notes
2002-03-28 00:00:00*************** UNSAT **************
  
 1)NOTE: PLEASE NOTE THAT SHEET E-1
 HAS BEEN REVISED AND IS NOW SHOWING
 75 KVA TRANSFORMER "ABOVE"?? PLEASE
 CLARIFY IF ABOVE, IS ABOVE CEILING OR
 MOUNTED ON WALL ABOVE EQUIPMENT??
 450-13B.
  
 2)NOTE: PLEASE NOTE THAT METER LOCATION
 IS NOTED IN RESPONSE LETTER AS LOCATION
 CHANGED PER FIRST SET OF REVIEW NOTES
 AND STILL SEEMS MENTIONS BEING ABOVE?
 PLEASE NOTE THAT PER FPL REQ`MENTS AND
 STANDARDS, ELEC METER ARE NOT TO BE
 PLACED ABOVE CEILINGS OR ABOVE 6'5".
 PLEASE CLARIFY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-01-15 Cont ID  
Sent By dpalmer Date 2002-01-15 Time 08:55 Rev Time 0.00
Received By dpalmer Date 2002-01-15 Time 08:55 Sent To  
Notes
2002-01-15 00:00:00*************** UNSAT *****************
  
 1)NOTE: PLEASE SHOW LOCATION OF TRANSFOR
 MER.
  
 2)NOTE: PLEASE SEE E-1, PLEASE CLARIFY
 METER AND DISCONNECT AAS BEING "ABOVE"
 CEILING???
 PLEASE NOTE ACCESSILE SERVICE EQUIPMENT?
  
 3)NOTE: PLEASE NOTE THAT THE LOAD
 CALCULATIONS NEED TO BE SHOWN, PLEASE
 NOTE THAT ALLCONTINUOUS LOADS ARE TO
 SHOWN AT 125% 230-42 215-2.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2002-05-28 Cont ID  
Sent By rbrown Date 2002-05-28 Time 12:42 Rev Time 0.00
Received By rbrown Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-03-28 Cont ID  
Sent By mcarsill Date 2002-03-28 Time 16:16 Rev Time 0.00
Received By mcarsill Date 2002-03-28 Time 16:16 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-01-16 Cont ID  
Sent By mcarsill Date 2002-01-16 Time 13:09 Rev Time 0.00
Received By mcarsill Date 2002-01-16 Time 13:09 Sent To  
Notes
2002-01-16 00:00:001) PLEASE INDICATE LOCATIONS OF
 ILLUMINATED EXIT SIGNS AND EMERGENCY
 LIGHTING FIXTURES.
 2) PLEASE PROVIDE UL NUMBER FOR NEW
 ONE-HOUR DEMISING WALL.
 3) THE HALLWAY NEAR THE SUBWAIT AREA
 APPEARS TO CREATE A DEAD-END CONDITION.
 THIS DESIGN MAY MEET MINIMUM CODE, BUT
 IT IS NOT A PREFERRED ARRANGEMENT.
 4) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATION INFORMATION FOR THE
 WALLS AND CEILINGS.
 5) PLEASE INDICATE LOCATIONS OF FIRE
 ALARM EQUIPMENT WITHIN TENANT
 SPACE.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2002-06-19 Cont ID  
Sent By pkrauss Date 2002-06-19 Time 13:18 Rev Time 0.40
Received By pkrauss Date 2002-06-19 Time 12:47 Sent To  
Notes
2002-06-19 00:00:00PROVISO:
  
 PLEASE SUBMIT MANUFACTURER INSTALLATION
 INSTRUCTIONS FOR THE FIRE DAMPERS SHOWN
 ON PLAN SHEET M-2.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2002-05-28 Cont ID  
Sent By pkrauss Date 2002-05-28 Time 15:00 Rev Time 0.40
Received By pkrauss Date 2002-05-28 Time 15:00 Sent To  
Notes
2002-05-28 00:00:00PROVISO:
  
 PROVIDE ACCESS FOR BOOSTER FAN.
  
 PROVIDE FEEDBACK TO DRYER SHOULD BOOSTER
 FAN "FAIL".
  
 AS PER 2001 FBC(M) 504.4, EXHAUST SHALL
 TERMINATE ON THE OUTSIDE OF THE BUILDING
 & SHALL BE EQUIPPED WITH A BACKDRAFT
 DAMPER.SCREENS SHALL NOT BE INSTALLED
 AT THE DUCT TERMINATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2002-05-25 Cont ID  
Sent By rbrown Date 2002-05-21 Time 10:47 Rev Time 0.45
Received By hmoser Date 2002-05-25 Time 08:44 Sent To  
Notes
2002-05-17 00:00:00SPOKE WITH CONTRACTOR 5-17-02 - NEED
 MANUFACTURER SUBMITTAL FOR THE VENTING
 ON THE DRYER.INFORMATION SUBMITTED
 DOES NOT SPECIFY MAXIMUM DISTANCE.I
 ALSO INFORMED BRIAN SHOULD DRYER
 EXHAUST BE GREATER THAN 2,000 CFM,
 MAKE-UP AIR WILL BE REQUIRED AS PER
 504.5
  
 CONTRACTOR TO FAX INFO MONDAY

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2002-04-03 Cont ID  
Sent By pkrauss Date 2002-04-03 Time 10:45 Rev Time 0.50
Received By pkrauss Date 2002-04-03 Time 07:53 Sent To Z
Notes
2002-04-03 00:00:00 
 PLANS CHANGED FROM THE 1997 STANDARD
 MECHANICAL CODE TO THE 2001 FLORIDA
 BUILDING CODE.
  
 MECHANICAL 401.5, OUTSIDE AIR EXHAUST &
 INTAKE OPENINGS SHALL BE LCOATED A
 MINIMUM OF 10 FT FROM LOT LINES OR
 BUILDINGS ON THE SAME LOT.
  
 AS PER 2001 FBC, MECHANICAL 401.5.2,
 EXHAUST OPENINGS SHALL BE LOCATED SO AS
 NOT TO CREATE A NUISANCE.EXHAUST AIR
 SHALL NOT BE DIRECTED ONTO WALKWAYS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-02-04 Cont ID  
Sent By pkrauss Date 2002-02-01 Time 16:09 Rev Time 1.50
Received By pkrauss Date 2002-02-01 Time 15:37 Sent To Z
Notes
2002-02-04 00:00:00*******************DENIED***************
  
 PLAN SHEET A-1 THE "N" DIRECTIONAL IS
 IN REALITY "EAST".
  
 PLEASE PROVIDE MANUFACTURER SUBMITTAL
 DATA FOR THE DRYER.
  
 NOTE:OPENINGS SHALL BE SCREENED
  
 PROVIDE MANUFACTURER DRAWINGS AS
 REFERENCED ON PLAN SHEET M-4.
  
 PLEASE NOTE, PLANS DO NOT INDICATE ANY
 EXISTING EQUIPMENT THAT MAY BE LOCATED
 ON THE LOWER ROOF.PLANS INDICATE THE
 DISCHARGE OF THE QUENCH VENT SHALL BE
 AWAY FROM AHU'S.THIS ALSO PERTAINS TO
 THE STAIRWELL.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXZT. 8388.

Review Stop P PLUMBING
Rev No 3 Status P Date 2002-05-14 Cont ID  
Sent By kstevens Date 2002-05-14 Time 09:54 Rev Time 0.00
Received By kstevens Date 2002-05-14 Time 09:54 Sent To  
Notes
2002-05-14 00:00:00PASSED/PROVISO
  
 LOUNGE SINK SHALL BE 34" AFF PER FACBC-
 SEC 4.24.2.

Review Stop P PLUMBING
Rev No 2 Status F Date 2002-04-18 Cont ID  
Sent By kstevens Date 2002-04-18 Time 10:33 Rev Time 0.00
Received By kstevens Date 2002-04-18 Time 10:33 Sent To  
Notes
2002-04-18 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) FROM PREVIOUS REVIEW: PLEASE PROVIDE
 DETAILS FOR LOUNGE SINK SHT A-1. COMPLY
 WITH SECTION 4.24.2
 2) SHT P-1 PLEASE PROVIDE INFORMATION
 FOR SERVICE SINK ON PLUMBING FIXTURE
 SCHEDULE WITH OTHER FIXTURES.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-01-31 Cont ID  
Sent By kstevens Date 2002-01-31 Time 13:33 Rev Time 1.25
Received By kstevens Date 2002-01-29 Time 18:23 Sent To  
Notes
2002-01-31 00:00:00DENIED
 REFERENCE: SPC-94-FACBC-97
  
 1) SHT A-1 SPC TABLE 407 REQUIRES TWO
 WATER CLOSETS AND TWO LAVS FOR WOMENS
 RESTROOM. 1 EA PROVIDED.
  
 2) SHT A-2 WATER FOUNTAIN DETAIL. PER
 FACBC SEC 4.1.3(10) PROVISIONS SHALL BE
 PROVIDED FOR THOSE WHO HAVE DIFFICULTY
 BENDING OR STOOPING. EITHER A HI/LOW DF
 OR PROVIDE CUP DISPENSER. SHOW DETAILS.
  
 3) SHT P-1 DOMESTIC WATER ISOMETRIC DIA.
 WATER HAMMER ARRESTORS TO BE LOCATED PER
 MANUFACTURE INSTALLATION INSTRUCTIONS &
 PDI-WH 201, IN AN "EFFECTIVE RANGE"
 CLOSE TO FIXTURE NOT ON TOP OF DROP AS
 SHOWN.
  
 4) SHT A-1 LOUNGE SINK. PLEASE PROVIDE
 DETAILS TO SHOW COMPLIANCE WITH FACBC
 SEC 4.24.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 3 Status P Date 2002-05-09 Cont ID  
Sent By sgraham Date 2002-05-09 Time 11:47 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
2002-05-09 00:00:00PROVISO:STOREFRONT GLAZING TO BE CLEAR

Review Stop Z ZONING
Rev No 2 Status F Date 2002-04-11 Cont ID  
Sent By pkrauss Date 2002-04-11 Time 16:22 Rev Time 0.35
Received By pkrauss Date   Time   Sent To  
Notes
2002-04-11 00:00:00DENIED AS PER JOE MINICOZZI

Review Stop Z ZONING
Rev No 1 Status F Date 2002-04-04 Cont ID  
Sent By pkrauss Date 2002-04-04 Time 10:40 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***