Plan Review Details - Permit 02010378
Plan Review Stops For Permit 02010378
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-01-29 Cont ID  
Sent By rbrown Date 2002-01-29 Time 09:21 Rev Time 0.00
Received By rbrown Date 2002-01-29 Time 09:21 Sent To  
Notes
2002-01-29 00:00:00BUILDING PLAN REVIEW
 ******PROVISO*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 SBC = STANDARD BUILDING CODE 1997
 SBC*= STANDARD BUILD'G CODE (CITY AMEND)
  
 --PROVISO--
 COMMENT NO.2 OF FIRE DEPARTMENT REVIEW,
 DATED 1/25/02, REGARDING DOOR SWING
 ACROSS CORRIDOR MUST BE ADDRESSED.
  
 --PROVISO--
 SBC 1004.2.1 THE TWO EXITS FROM "OTHER
 SUITES" ARE TOO CLOSE TOGETHER TO BE
 CONSIDERED "...TWO INDEPENDENT EXITS".
 THIS IS ACCEPTABLE ONLY, UNDER THE
 EXCEPTION GIVEN IN SBC 1020.1 'SINGLE
 EXIT', IF NO MORE THAN 40 PERSONS OCCUPY
 THAT SPACE.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUERIES PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-01-17 Cont ID  
Sent By rbrown Date 2002-01-17 Time 16:12 Rev Time 0.00
Received By rbrown Date 2002-01-17 Time 16:12 Sent To  
Notes
2002-01-17 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 SBC = STANDARD BUILDING CODE
 SBC*= STANDARD BUILD'G CODE (AMENDMENTS)
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) SBC* 104.2.3NONE OF THE SUBMITTED
 PLANS HAVE BEEN SEALED PROPERLY.
  
 3) SBC 1004.2.1EACH TENANT AREA SHALL
 HAVE ACCESS TO TWO INDEPENDENT EXITS.
 SHOW ENTRANCES/EXITS FROM THE AREA
 DESCRIBED AS "OTHER SUITES", AS THE
 PLANS ARE SHOWING ONE DOOR FILLED-IN.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUERIES PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-01-30 Cont ID  
Sent By dpalmer Date 2002-01-30 Time 18:35 Rev Time 0.00
Received By dpalmer Date 2002-01-30 Time 18:35 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-01-14 Cont ID  
Sent By dpalmer Date 2002-01-14 Time 14:08 Rev Time 0.00
Received By dpalmer Date 2002-01-14 Time 14:08 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2002-02-15 Cont ID  
Sent By mcarsill Date 2002-02-15 Time 10:09 Rev Time 0.00
Received By mcarsill Date 2002-02-15 Time 10:09 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2002-01-25 Cont ID  
Sent By mcarsill Date 2002-01-25 Time 15:35 Rev Time 0.00
Received By mcarsill Date 2002-01-25 Time 15:35 Sent To  
Notes
2002-01-25 00:00:001) NO FIRE SPRINKLER PLANS PROVIDED
 WITH DRAWINGS.
 2) REVISED DOORS SHOWN FROM OTHER SUITES
 SWING INTO THE CORRIDOR WHICH CUTS THE
 HALLWAY DOWN TO MORE THAN 50 PERCENT.
 DOORS CAN SWING INWARD IF OCCUPANT LOAD
 IS LESS THAN 50 PERSONS. ALSO THE
 DOORS ARE EXTREMELY CLOSE TOGETHER.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-01-10 Cont ID  
Sent By mcarsill Date 2002-01-10 Time 16:57 Rev Time 0.00
Received By mcarsill Date 2002-01-10 Time 16:57 Sent To  
Notes
2002-01-10 00:00:001) NO FIRE SPRINKLER PLANS PROVIDED
 WITH DRAWINGS.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-02-04 Cont ID  
Sent By pkrauss Date 2002-02-04 Time 09:17 Rev Time 0.35
Received By pkrauss Date 2002-02-04 Time 09:17 Sent To  
Notes
2002-02-04 00:00:00 
 PROVISO:
  
 PLAN SHEET A-1 INDICATES AN EXISTING 1
 HOUR RATED WALL.NO PENETRATIONS ARE
 SHOWN ON PLAN.PLEASE NOTE ANY
 PENETRATIONS THROUGH A WALL OR
 PARTITION HAVING A FIRE RESISTANCE
 RATING OF 1 OR MORE HOURS SHALL BE
 PROTETED BY A FIRE DAMPER.
 (1997 SMC 610.1.2)
  
 SPECIFIC LOCATION OF EACH FIRE DAMPER
 SHALL BE PROPERLY IDENTIFIED ON THE
 BUILDING PLAN.(1997 SMC 610.6)
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-01-11 Cont ID  
Sent By pkrauss Date 2002-01-11 Time 13:08 Rev Time 0.40
Received By pkrauss Date 2002-01-11 Time 13:02 Sent To  
Notes
2002-01-11 00:00:00MECHANICAL PERMIT 02010575
  
 PROVISO:
  
 PRIOR TO CONNECTING TO ANY EXISTING
 DUCTWORK, CALL FOR AN INSPECTION.
  
 NO COMBUSTIBLES ABOVE THE CEILING IN
 THE RETURN AIR PLENUM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 1 Status N Date 2002-02-04 Cont ID  
Sent By pkrauss Date 2002-02-04 Time 09:54 Rev Time 0.10
Received By pkrauss Date   Time   Sent To  
Notes
2002-02-04 00:00:00 
 NO PLUMBING PLANS SUBMITTED FOR REVIEW
 WITH THIS PERMIT APPLICATION.
  
 PATTY