Plan Review Details - Permit 02010328
Plan Review Stops For Permit 02010328
Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-03-19 Cont ID  
Sent By btrobaug Date 2002-03-19 Time 13:10 Rev Time 0.00
Received By btrobaug Date 2002-03-19 Time 12:29 Sent To  
Notes
2002-03-19 00:00:00**************FAILED!*******************
 PLEASE CLARIFY THE
 INFORMATION SUBMITTED AND CORRECT THE
 OCP OR CHANGE CONDUCTOR SIZES TO
 CONFORM TO NEC ARTICLES.NOTES ON
 PLAN.EG;#2=125AMPS,#3=110 AMPS,#4=100
 AMPS,#8 EQUIPMENT GROUND FOR 100 AMP
 SERVICE.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/659-8096 EXT.8392