| Plan Review Stops For Permit 02010328 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2002-03-19 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-03-19 |
Time |
13:10 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2002-03-19 |
Time |
12:29 |
Sent To |
|
|
| Notes |
| 2002-03-19 00:00:00 | **************FAILED!******************* | | | PLEASE CLARIFY THE | | | INFORMATION SUBMITTED AND CORRECT THE | | | OCP OR CHANGE CONDUCTOR SIZES TO | | | CONFORM TO NEC ARTICLES.NOTES ON | | | PLAN.EG;#2=125AMPS,#3=110 AMPS,#4=100 | | | AMPS,#8 EQUIPMENT GROUND FOR 100 AMP | | | SERVICE. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | 561/659-8096 EXT.8392 |
|
|
|