| 2002-01-24 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 659 8096 EXT 8499 |
| | |
| | SBC = STANDARD BUILDING CODE 1997 |
| | SBC*= STANDARD BUILD'G CODE (CITY AMEND) |
| | FL ENERGY CODE = FLORIDA ENERGY |
| | EFFICIENCY CODE FOR BUILD'G CONSTR'N |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 3) SBC* 1707.4PRODUCT APPROVALS.THE |
| | SUBMITTED PRODUCT APPROVALS DO NOT HAVE |
| | VALID EXPIRATION DATES. |
| | |
| | 4) SHEET 2, ROOF FRAMING PLAN.CLARIFY |
| | DORMER ROOF FRAMING.THE DORMER DETAIL |
| | SHOWS 2'X8" RAFTERS AT 16 O/C WHILST |
| | PLAN SHOWS TRUSSES.TRUSS DRAWINGS, |
| | INCLUDING GIRDER TRUSSES, SHALL BE |
| | SUBMITTED. |
| | |
| | 5) SHEET 2, FLOOR FRAMING PLAN.WHERE |
| | THE EXISTING STAIR OPENING IS TO BE |
| | FILLED IN, THE PROPOSED 'SIMPSON WS28' |
| | IS NOT A VALID SIMPSON CONNECTOR |
| | REFERENCE. PROVIDE CORRECT REFERENCE. |
| | |
| | 6) SBC 1015.3GUARDRAIL RAILINGS SHALL |
| | BE SPACED TO REJECT THE PASSAGE OF A 4" |
| | DIAMETER SPHERE.ADD NOTES TO ENSURE |
| | COMPLIANCE. |
| | |
| | 7) SBC 1005.4EMERGENCY EGRESS WINDOW. |
| | THE SILL HEIGHT OF THE OPENING SHALL NOT |
| | BE GREATER THAN 44" ABOVE THE FLOOR AND |
| | THE CLEAR OPENING SHALL BE MINIMUM OF |
| | 24" HIGH AND 20" WIDE.ADD THE REQUIRED |
| | HEIGHT INFORMATION TO THE PLANS. |
| | |
| | 8) FL ENERGY CODE 103.0COMPLIANCE |
| | SHALL BE DEMONSTRATED BY SUBMITTAL OF |
| | APPROPRIATE ENERGY CODE COMPLIANCE FORMS |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |
| | THE CODE REFERENCES GIVE ADDITIONAL INFO |
| | IF YOU HAVE ANY QUERIES PLEASE CALL: |
| | ROBERT BROWN(561) 659 8096 EXT 8499 |