Plan Review Details - Permit 02010242
Plan Review Stops For Permit 02010242
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-01-08 Cont ID U-18900
Sent By btrobaug Date 2002-01-08 Time 16:18 Rev Time 0.33
Received By btrobaug Date 2002-01-08 Time 16:17 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-01-08 Cont ID  
Sent By btrobaug Date 2002-01-08 Time 09:06 Rev Time 0.50
Received By btrobaug Date 2002-01-08 Time 09:06 Sent To  
Notes
2002-01-08 00:00:001)PROVIDE AIC RATNG FOR SERVICE
 2)PROVIDE LOAD CALCULATION FOR THE
 SERVICE.
 3)PLEASE PROVIDE PANEL SCHEDULES.
 4)THE #3 SERVICE CONDUCTORS SUPPLYING
 THE EXISTING PANELS CANNOT BE PROTECTED
 BY MORE THAN A 110 AMPERE CIRCUIT
 BREAKER AS PER 230-46B AND 310-15(B)(6).
 5)PLEASE SHOW SERVICE GROUND AND
 BONDING SIZE AND METHOD ON DRAWING.
 6)PLEASE NOTE THAT OUR RECORDS INDICATE
 THE CONTRACTORS WORKERS COMP INSURANCE
 AS HAVING EXPIRED 12/31/2001.
  
  
 IF THERE ARE ANY QUESTIONS,PLEASE CALL.
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 (561) 659-8096 EXT.8392