| Plan Review Stops For Permit 02010039 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2002-01-07 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-01-07 |
Time |
11:29 |
Rev Time |
1.00 |
| Received By |
btrobaug |
Date |
2002-01-07 |
Time |
09:34 |
Sent To |
|
|
| Notes |
| 2002-01-07 00:00:00 | PASSED WITH PROVISOS. | | | 1)CIRCUIT#13 IS AT 4500 WATTS,ADD ANOTHE | | | R 20 AMPERE CIRCIUT. | | | 2)PANEL SCHEDULE SHOWS #14 WIRE ON 20 AM | | | P BREAKERS,#'S 13,14,15&16.CHANGE TO #12 | | | WIRE AS PER210-52B. | | | 3)NEED A SMOKE DETECTOR OUSIDE OF BED RO | | | OM #1 AS PER2-2.1.1.1 NFPA-72.1997 EDITI | | | ON. | | | 4)WHERE IS THE 2ND AHU?IF IN ATTIC COMPL | | | Y WITH 210-63. | | | 5)ALL BED ROOM RECEPTACLES SHALL HAVE AN | | | ARC FAULT CIRCUIT BREAKER AS PER 210-12. | | | 6)ADD AGROUND WIRE IN PVC CONDUIT FOR A/ | | | C DISCONNECT. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | (561)659-8096 EXT.8392 |
|
|
|