Plan Review Details - Permit 02010039
Plan Review Stops For Permit 02010039
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-01-07 Cont ID  
Sent By btrobaug Date 2002-01-07 Time 11:29 Rev Time 1.00
Received By btrobaug Date 2002-01-07 Time 09:34 Sent To  
Notes
2002-01-07 00:00:00PASSED WITH PROVISOS.
 1)CIRCUIT#13 IS AT 4500 WATTS,ADD ANOTHE
 R 20 AMPERE CIRCIUT.
 2)PANEL SCHEDULE SHOWS #14 WIRE ON 20 AM
 P BREAKERS,#'S 13,14,15&16.CHANGE TO #12
 WIRE AS PER210-52B.
 3)NEED A SMOKE DETECTOR OUSIDE OF BED RO
 OM #1 AS PER2-2.1.1.1 NFPA-72.1997 EDITI
 ON.
 4)WHERE IS THE 2ND AHU?IF IN ATTIC COMPL
 Y WITH 210-63.
 5)ALL BED ROOM RECEPTACLES SHALL HAVE AN
 ARC FAULT CIRCUIT BREAKER AS PER 210-12.
 6)ADD AGROUND WIRE IN PVC CONDUIT FOR A/
 C DISCONNECT.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 (561)659-8096 EXT.8392