| Plan Review Stops For Permit 01121783 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2002-01-02 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-01-02 |
Time |
12:45 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2002-01-02 |
Time |
12:42 |
Sent To |
|
|
| Notes |
| 2002-01-02 00:00:00 | **************UNSATISFACTORY!*********** | | | 1)PROVIDE AIC RATINGS AS PER NFPA-70,ART | | | CLE 110-9 & 110-10. | | | 2)PROVIDEICAL LOAD CALLCULATIONS F | | | R THE SERVIEBRANCH CIRCUITS AND FEEDERS. | | | ***************UNSAT!******************* | | | 1)PROVIDE AIC RATINGS AS PER | | | NFPA-70,ARTICLES 110-9 & 110-10 | | | 2)PROVIDE ELECTRICAL LOAD CALCULATIONS | | | FOR THE SERVICE,BRANCH CIRCUITS AND | | | FEEDERS. | | | 3)PROVIDE METER ENCLOSURE TYPE AND | | | AMPERAGE ON RESUBMITTALS. | | | 4)PLEASE SHOW PANEL TYPE,SIZE AND NUMBER | | | OF CIRCUITS. | | | 5)PLEASE SUBMIT PANEL SCHEDULE. | | | 6)SHOW ALL CONDUIT SIZE AND TYPE FOR | | | SERVICE AND RELATED EQUIPMENT. | | | 7)PROVIDE ALL CONDUCTOR SIZE,TYPE AND | | | NUMBER OF SAME IN NEW OR ADDED CONDUIT. | | | 8)SHOW ALL GROUNDING AS PER NEC. | | | 9)PLEASE DRAW RESUBMITTALS TO BE | | | LEGIBLE10)SHOW LOCATION OF GFI AT REAR | | | OF THE HOUSE AS PER 210-52E. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | (561) 659-8096 EXT.8392 |
|
|
|