Plan Review Details - Permit 01121737
Plan Review Stops For Permit 01121737
Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status P Date 2003-01-23 Cont ID  
Sent By jwitmer Date 2003-01-23 Time 14:06 Rev Time 0.50
Received By jwitmer Date 2003-01-23 Time 14:06 Sent To  
Notes
2003-01-23 00:00:0001-23-03 PRODUCT APPROVAL SKYLIGHT /
 WITH LARGE MISSLE IMPACTJW

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2003-01-13 Cont ID  
Sent By dpalmer Date 2003-01-23 Time 10:31 Rev Time 0.25
Received By jwitmer Date   Time   Sent To  
Notes
2003-01-13 00:00:00REVISION DATED 12-22-02 STAIR SHOP
 DRAWINGS OKJW

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2003-01-09 Cont ID  
Sent By btrobaug Date 2003-01-10 Time 16:37 Rev Time 0.55
Received By jwitmer Date   Time   Sent To  
Notes
2003-01-09 00:00:00REV 01-07-03 OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2002-12-31 Cont ID  
Sent By btrobaug Date 2003-01-08 Time 17:20 Rev Time 0.50
Received By jwitmer Date 2002-12-31 Time 15:34 Sent To  
Notes
2002-12-31 00:00:00SHOP DRAWINGS :GUARDRAILS/ HANDRAILS
 SEE FL ACCESSIBILITY CODE: 4.9.4(2)
 SEE PAGE 2 SECTION 2 THERE IS NO EXTEN-
 SION ATTHE BOTTOM OF STAIR.
 AT THE TOP, THE EXTENSION SHALL BE
 PARALLEL WITH THE FLOOR AT LEAST 12"
 BEYOND THE TOP RISER, AT THE BOTTOM THE
 HANDRAIL SHALL CONTINUE THE SLOPE FOR A
 DISTANCE OF THE WIDTH OF 1 TREAD FROM
 THE RISER, THE REMAINDER OF THE EXTEN-
 SION SHALL BE HORIZONTAL (12").
 BUILDING PLAN REVIEW
 JIM WITMER

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2002-12-31 Cont ID  
Sent By jwitmer Date 2002-12-31 Time 15:19 Rev Time 1.00
Received By jwitmer Date 2002-12-31 Time 15:19 Sent To  
Notes
2002-12-31 00:00:00REVISION DATED 12/23/02 ACCESS TO ELEC
 ROOM OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2003-01-07 Cont ID  
Sent By jwitmer Date 2002-12-11 Time 15:17 Rev Time 1.55
Received By jwitmer Date   Time   Sent To  
Notes
2002-12-31 00:00:00REVISIONS: DELETE CORRIDOR FIRST FLOOR
 RECONFIGURE 2ND FLOOR. OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2002-12-11 Cont ID  
Sent By dpalmer Date 2002-12-31 Time 10:53 Rev Time 1.25
Received By jwitmer Date 2002-12-11 Time 14:46 Sent To  
Notes
2002-12-11 00:00:00BUILDING PLAN REVIEW
 REVISION DATED: 11-15-02REVIEWED
 PERMIT: 01121737
 ADD: 707 N DIXIE
 CONT: GSP & ASSOCIATES
 TEL: (561)722-3301
 SBC = 1997 STANDARD BUILDING CODE
  
 1) SUITE 102/104 DELETION OF CORRIDOR.
 BUILDING PLAN REVIEW
 J WITMER

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-04-01 Cont ID  
Sent By btrobaug Date 2002-11-26 Time 18:02 Rev Time 1.75
Received By jwitmer Date   Time   Sent To  
Notes
2002-04-01 00:00:00PROVISO:
 1) PLANS TO BE REVIEWED BY COUNTY FOR
 ASSESSMENT FOR IMPACT FEES! BEFORE
 ISSUANCE

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-01-15 Cont ID  
Sent By jwitmer Date 2002-01-15 Time 09:12 Rev Time 4.50
Received By jwitmer Date 2002-01-15 Time 09:12 Sent To  
Notes
2002-01-15 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01121737
 711 N DIXIE
 CONT: GSP & ASSOCIATES
 TEL: (561) 697-8444
  
 SBC= 1997 STANDARD BUILDING CODE
 SBC*= AMENDMENTS STANDARD BUILDING CODE
 FL ACC CODE= FLORIDA ACCESSIBILITY CODE
 1997 EDITION
  
 1)- SBC* 104.2.2 ADDITONAL INFORMATION
 REQUIRED. BETWEEN THE SITE PLAN & ARCH.
 PLANS PATH OF TRAVEL FOR HANDICAPPED IS
 UNCLEAR FOR ENTRY RAMP.
  
 2)- PLEASE INDICATE WHAT TYPE OF BUILD-
 ING DESIGN WAS USED IN THE DESIGN?
 PLANS INDICATE A EXISTING FIRE RISER, IS
 THIS TO BE CONSIDERED A FIRE SPRINKLERED
 BUILDING? IF SO,ADDITIONAL INFORMATIOIN
 WILL BE REQUIRED TO DO A COMPETENT PLAN
 REVIEW. THIS PLAN REVIEW WAS COMPLETED
 AS A WORSE CASE, NO FIRE SPRINKLERS
 SINCE THE REQUIRED INFORMATION WAS LACK-
 ING.
  
 3)- SBC (FIRE DISTRICT) 102.1 TYPES OF
 CONSTRUCTION PRMITTED. TYPE I,II,III,
 IV OR V ARE PERMITTED IN FIRE DISTRICT.
  
 4)- BALCONY INDICATES USE OF WOOD ON THE
 EXTERIOR WALLS.
  
 5)-SBC FI02.2.5 ALL WALLS, FLOORS,
 ROOFS, & THEIR SUPPORTING STRUCTURAL
 MEMBERS SHALL PROVIDE NOT LESS THAN
 1-HR FIRE RESISTANCE.
  
 6)- SBC TABLE 600 INDICATE COMPLIANCE
 WITH TYPE V BUILDING 0'-3' FROM PROPERTY
 LINE 3 HR EXTERIOR WALLS.
  
 7)- SURVEY INDICATES THE FRONT ENTRY
 PROJECTING 1'-0" INTO THE PUBLIC PROPER-
 TY AT GRADE ?
  
 8)- BALCONY CORBELS, WHAT TYPE OF MATER-
 IAL, HOW WILL IT BE ATTACHED?
  
 9)- F 102.2.7 ARCH. TRIM APPROVED NON-
 COMBUSTIBLE TRIM SHOW COMPLIANCE REPORT
 FOR NONCOMBUSTIBLES, (EXPANDED POLYSTI-
 RENE SYSTEMS).
  
 10)- ENERGY CALS W/ MANUAL "J"
  
 11)- SHEET A101, SHOW DOORWAYS INTO
 TENANT SPACE. SBC1001.1.2.IN EVERY BUILD
 ING HEREAFTER ERECTED, MEANS OF EGRESS
 SHALL COMPLY WITH THE MINIMUM REQUIRE-
 MENTS OF THIS CHAPTER. THE PLANS DO NOT
 INDICATE EGRESS FROM TENANT SPACE OR
 COMMON ELEMENTS AS RESTROOMS.
  
 12)- SECOND FLOOR EGRESS, SBC 1020.1-
 SINGLE EGRESS REQUIREMENTS > 3500 SQ FT,
 DO NOT MEET REQUIREMENTS, 1004.2.2 REQUI
 RES A MINIMUM OF 2 MEANS OF EGRESS ARE
 REQUIRED.
  
 13)- SHEET 101/201 SBC 1004.1.4. WHERE
 2 OR MORE EXITS OR EXIT ACCESS DOORS
 SHALL BE PLACED A DISTANCE APART EQUAL
 TO NOT LESS THAN ONE HALF OF THE LENGTH
 OF THE MAXIMUM OVERALL DIAGONAL DIMEN-
 SION OF THE BUILDING OR AREA TO BE
 SERVED.
  
 14)- EXITS, SPIRAL STAIRS, SBC 1006.1.1.
 EXIT STAIRWAYS BETWEEN FLOORS SHALL BE
 ENCLOSED IN OR SEPERATED BY FIRE RESIS-
 TANT CONSTRUCTION IN ACCORDANCE WITH
 705.2 & TABLE 705.1.2.PRPOTECTION OF
 FLOOR OPENINGS.
  
 15)- SBC 704.2.4. EXIT ACCESS CORRIDORS:
 FIRE EXIT RATINGS SHALL BE IN ACCORDANCE
 WITH TABLE 704.2.3.2.
  
 16)- SBC 705.1.1.FIRE RATED ASSEMBLIES
 SHOW COMPLIANCE EITHER UL LISTING OR GYP
 SUM ASSOC NUMBER.
  
 17)- SBC 705.5.1.2. FIRESTOP SYSTEMS,
 LIST PRODUCTS ,CUT SHEETS.
  
 18)- SPIRAL STAIRS: SBC SHOW HOW ONCE
 YOU LEAVE THE STAIR ENCLOSURE FOR SPIRAL
 STAIRS COMPLIANCE FOR EXIT PASSAGEWAYS
 SBC 1010.3.
  
 19)- 1004.3.1 ACCESSIBLE MEANS OF EGRESS
 WHERE MORE THAN 1 MEANS OF EGRESS IS RE-
 QUIRED FROM ANY REQUIRED ACCESSIBLE
 SPACE, EACH ACCESSIBLE PORTION OF SPACE
 SHALL BE SERVED BY NOT LESS THAN 2A
 CCESSIBLE MEANS OF EGRESS.
 1004.3.2.1. TO BE AN ACCESSIBLE MEANS OF
 EGRESS SHALL HAVE A CLEAR WIDTH OF 48"
 BETWEEN THE HANDRAILS AND INCORPARATE
 AN AREA OF REFUGE WITHIN AN ENLARGED
 STORY LEVEL LANDING OR SHALL BE ACCESSED
 FROM EITHER AN AREA OF REFUGE COMPLYING
 WITH 1004.3.5 OR A HORIZONTAL EXIT.
  
 20)- SHEET A.104 SHOW COMPLIANCE WITH
 SECTION 1007.5.5.12" HANDRAIL EXTENTIONS
  
 21)- SHEET A-105 SEC 2: GUARDRAILS SEE
 1015.3 FOR 4" SPHERE (BALCONY), ALSO
 SHEET A104 SEC BB GAURDRAIL 2" SPHERE
 AT NEW GUARDRAIL.
  
 22)-SBC 1606.2.6.2 COMPONENTS & CLADDING
 PROVIDE (2 COPIES) OF PRODUCT APPROVAL
 REPORTS FOR ALL GLAZED OPENINGS, WINDOWS
 DOORS & SKYLIGHTS. DOORS WITH NO GLAZING
 (EXTERIOR) SHALL ALSO BE REQUIRED TO SUB
 MIT PRODUCT TESTING REPORTS.
  
 23)- MISSING WINDOW & DOOR BUCK ATTACH-
 MENT.
  
 24)- PROVIDE INFORMATION ON NEW ROOF
 ACCESS ?
  
 25)- UNCLEAR AS TO WHAT IS GOING TO
 HAPPEN AT EXISTING SKYLIGHT? IS THE SKY-
 LIGHT BEING USED FOR THIS PURPOSE?
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561)659-8096 X 8412

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2003-01-08 Cont ID  
Sent By btrobaug Date 2003-01-08 Time 17:20 Rev Time 0.50
Received By btrobaug Date   Time   Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status N Date 2003-01-07 Cont ID  
Sent By btrobaug Date 2003-01-07 Time 14:00 Rev Time 1.00
Received By btrobaug Date 2003-01-07 Time 13:15 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2002-04-08 Cont ID  
Sent By btrobaug Date 2002-04-08 Time 15:29 Rev Time 0.00
Received By btrobaug Date 2002-04-08 Time 12:57 Sent To FIRE
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2002-03-25 Cont ID  
Sent By dpalmer Date 2002-03-25 Time 07:31 Rev Time 0.00
Received By dpalmer Date 2002-03-25 Time 07:31 Sent To  
Notes
2002-03-25 00:00:00***************** UNSAT **************
  
 1)NOTE: PLEASE NOTE THAT ONLY THE
 ELECTRICAL RISER DIAGRAM IS STILL
 SUBMITTED? PLEASE CLARIFY WHERE SHELL
 ELECTRICAL IS SHOWN?
  
 2)NOTE: PLEASE NOTE THAT NOTE#1 FROM
 FIRST REVIEW STILL NEEDS TO BE ADDRESSED
 PLEASE NOTE LOAD CALCUALTIONS NEED TO
 BE SHOWN. WATTS PER SQ FT ETC.
 NEC ART 220.
  
 PLEASE NOTE FIRE REVIEW NOTES FOR EM LTS
 AND EXIT LTS.
  
 PLEASE SUBMIT THE ABOVE INFORMAITON FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-01-08 Cont ID  
Sent By dpalmer Date 2002-01-08 Time 07:00 Rev Time 0.00
Received By dpalmer Date 2002-01-08 Time 07:00 Sent To  
Notes
2002-01-08 00:00:00**************** UNSAT *****************
  
 1)NOTE: PLEASE NOTE LOAD CALACULATIONS
 NEED TO BE SHOWN. 215-5,220-3,220-10,
 220-11,220-13 ETC. PLEASE ALSO NOTE
 THAT ALL CONTINUOUS LOADS NEED TO BE
 SHOWN AT 125%. 230-42,215-3.
  
 2)NOTE: PLEASE NOTE THAT TOTAL EXCEEDS
 RATING OF SERIVCE ENTRANCE CONDUCTORS
 310-16.
 ALSO NOTE OCP IS NOT LARGE ENOUGH FOR
 LOAD SHOWN.
  
 3)NOTE: PLEASE CLARIFY METHOD OF EQUIP-
 -MENT GROUNDING BETWEEN DISCONNECT AND
 UNIT PANELS.
  
 4)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 5)NOTE: PLEASE PROVIDE SIZING OF GUTTER.
 374
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 2 Status N Date 2002-04-03 Cont ID  
Sent By mamini Date 2002-04-03 Time 16:53 Rev Time 1.00
Received By mamini Date 2002-04-03 Time 16:53 Sent To  
Notes
2002-04-03 00:00:00N/A
 THIS PEMITT IS FOR SHELL ONLY, WILL
 APPLY FOR SITE/CIVIL SEPARATLY.
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2002-03-27 Cont ID  
Sent By mamini Date 2002-03-27 Time 09:41 Rev Time 3.00
Received By mamini Date 2002-03-27 Time 09:41 Sent To  
Notes
2002-03-27 00:00:00FAILED:
 1. PLEASE PROVIDE STORM WATER CALC.
 FOR OUR REVIEW AND APPROVAL.
 2. PLEASE PROVIDE PERVIOUS & IMPERVIOUS
 CALC. FOR ENTIRE SITE.
 3. PLEASE NOTE THAT, ALL DRIVEWAY
 APPROACHES MUST BE AT MIN. PER CITY OF
 WPB STANDARD AND REQUIREMENTS.SEE
 ATTACHED.
 4. PLEASE PROVIDE DETAILS FOR THE
 PROPOSED DUMPSTER ENCLOSURE.IT SHOULD
 BE CONSTRUCTED PER CITY'S REQUIREMENT IF
 GARBAGE IS TO BE PICKED UP BY THE CITY.
 SEE ATTACHED.
 5. IS THERE ANY NEW SEWER CONNECTIONS?
 6. PLEASE INCLUDE POLLUTION PREVENTION
 PLAN (NOTES, DETAILS).IT SHOULD BE
 INSTALLED IN THE FIELD PROIR TO ANY
 EARTH WORKS.
 7. ALL CONNECTIONS TO THE CITY OF WPB
 SERVICES AND BACKFLOW PREVENTERS MUST BE
 APPROVED AND INSPECTED BY THE CITY
 OFFICIALS, 659-8040.
 8. A SEPARATE PERMIT APPLICATION AND
 FEES FOR UNDRGROUND UTILITIES/SITE WORKS
 IS REQUIRED.
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2003-01-02 Cont ID  
Sent By mcarsill Date 2003-01-02 Time 16:35 Rev Time 0.00
Received By mcarsill Date 2003-01-02 Time 16:35 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-04-09 Cont ID  
Sent By mcarsill Date 2002-04-09 Time 11:00 Rev Time 0.00
Received By mcarsill Date 2002-04-09 Time 11:00 Sent To  
Notes
2002-04-09 00:00:00ELECTRICAL PLANS FOR SHELL ONLY.
  
 A) THE FIRE SPRINKLER SYSTEM IS TO BE
 MONITORED BY LICENSED UL LISTED CENTRAL
 STATION APPROVED BY THE FIRE DEPARTMENT.
 B) ADDITIONAL EXIT SIGNS AND EMERGENCY
 LIGHTING EQUIPMENT WILL BE REQUIRED
 FOR THE FUTURE TENANT SPACES.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-01-07 Cont ID  
Sent By btrobaug Date 2002-04-08 Time 15:29 Rev Time 0.00
Received By mcarsill Date 2002-01-07 Time 12:03 Sent To  
Notes
2002-01-07 00:00:001) PLEASE BE ADVISED THAT THE BUILDING
 IS LOCATED WITHIN THE CITY FIRE LIMITS.
 CERTAIN RESTRICTIONS APPLY.
 2) BUILDING ADDRESS REQUIRED PER CITY
 CODE 3343-00.
 3) NO INDICATIONS ON PLANS REGARDING
 THE RATINGS ON THE PROPOSED TENANT WALLS
 4) NO ILLUMINATED EXIT SIGNS OR
 EMERGENCY LIGHTING SHOWN ON THE PLANS.
 5) NO INTERIOR FINISH CLASSIFICATION
 INFORMATION ON PLANS FOR THE WALLS
 AND CEILINGS.
 6) THE PLANS INDICATE AN EXISTING FIRE
 SPRINKLER RISER, HOWEVER NO FIRE
 SPRINKLER WERE SUBMITTED WITH THE
 DRAWINGS. IT IS BELIEVED THAT THE
 FIRE SPRINKLER SYSTEM IS OF AN OLDER
 TYPE AND THE PRESENT CONDITION OF IT
 IS UNKNOWN.
 7) NO EXIT DOORS SHOWN FROM TENANT
 SPACE.
 8) PLEASE EXPLAIN HOW EXITING OCCURS
 FROM THE BUILDING. PLEASE EXPLAIN
 RATIONALE FOR EXITING.
 9) WHAT WILL THE CURVED STAIR TO BE
 USED FOR.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2003-01-23 Cont ID  
Sent By dpalmer Date 2003-01-23 Time 10:31 Rev Time 0.00
Received By dpalmer Date 2003-01-23 Time 10:31 Sent To B
Notes
2003-01-23 00:00:00TO JIM WITMERS DESK.

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2003-01-15 Cont ID  
Sent By dpalmer Date 2003-01-15 Time 13:22 Rev Time 0.00
Received By dpalmer Date 2003-01-15 Time 13:22 Sent To B
Notes
2003-01-15 00:00:00TO JIM WITMER'S DESK.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-01-10 Cont ID  
Sent By btrobaug Date 2003-01-10 Time 16:37 Rev Time 0.00
Received By btrobaug Date 2003-01-10 Time 16:37 Sent To B
Notes
2003-01-10 00:00:00TO JIM W./WRT

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2002-12-31 Cont ID  
Sent By dpalmer Date 2002-12-31 Time 10:52 Rev Time 0.00
Received By dpalmer Date 2002-12-31 Time 10:52 Sent To B
Notes
2002-12-31 00:00:00TI JIM WITMER'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2002-12-31 Cont ID  
Sent By dpalmer Date 2002-12-31 Time 10:49 Rev Time 0.00
Received By dpalmer Date 2002-12-31 Time 10:49 Sent To B
Notes
2002-12-31 00:00:00TO JIM WITMER'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-11-26 Cont ID  
Sent By btrobaug Date 2002-11-26 Time 18:02 Rev Time 0.00
Received By btrobaug Date 2002-11-26 Time 18:02 Sent To B
Notes
2002-11-26 00:00:00TO JIM W./WRT

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-04-01 Cont ID  
Sent By pkrauss Date 2002-04-01 Time 10:19 Rev Time 0.40
Received By pkrauss Date 2002-04-01 Time 10:16 Sent To  
Notes
2002-04-01 00:00:00NO MECHANICAL PLANS SUBMITTED FOR
 REVIEW.PLEASE PROVIDE PLANS WITH
 MECHANICAL PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2002-01-05 Cont ID  
Sent By pkrauss Date 2002-01-05 Time 10:14 Rev Time 0.45
Received By pkrauss Date 2002-01-05 Time 10:06 Sent To  
Notes
2002-01-05 00:00:00 
  
 NO MECHANICAL PLANS SUBMTTED FOR REVIEW.
 PLEASE PROVIDE MECHANICAL PLANS WITH
 MECHANICAL PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 3 Status N Date 2002-04-23 Cont ID  
Sent By kstevens Date 2002-04-23 Time 13:17 Rev Time 0.00
Received By kstevens Date 2002-04-23 Time 13:17 Sent To  
Notes
2002-04-23 00:00:00THIS PERMIT FOR SHELL ONLY - ROOF DRAIN
 CALCULATIONS FOR PRIMARY AND SECONDARY
 DRAINS SUBMITTED, BUT FOR 1997 SPC NOT
 1994. CALCULATIONS WORK FOR EITHER CODE,
 PIPE SIZE IS SUFFICIENT. REQUEST REVIS-
 IONS FOR CALCULATIONS UNDER PROPER CODE.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 2 Status F Date 2002-04-12 Cont ID  
Sent By kstevens Date 2002-04-12 Time 23:58 Rev Time 0.00
Received By kstevens Date 2002-04-12 Time 23:58 Sent To  
Notes
2002-04-13 00:00:00DENIED
 REFERENCE: SPC-94 - FACBC-97
  
 1) SUBMIT CALCULATIONS FOR MINIMUM FAC-
 ILITIES PER SPC-94 TABLE 407 AND SECTION
 407.1.3. DRINKING FOUNTAINS REQUIRED
  
 2) SUBMIT CALCULATIONS FOR PRIMARY AND
 SECONDARY ROOF DRAINS. INCLUDE ALL AREA
 OF ROOFS THAT MAY DRAIN TO ROOF FROM
 ABOVE AND 1/2 AREA OF ALL VERTICAL WALLS
 PER SPC-94 SEC 1108 AND 1109.
  
 3) SUBMIT A SANITARY RISER DIAGRAM.
  
 4) SUBMIT A WATER RISER DIAGRAM.
  
 5) SUBMIT A STORM RISER DIAGRAM.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status N Date 2002-01-16 Cont ID  
Sent By jleech Date 2002-01-16 Time 19:32 Rev Time 0.75
Received By jleech Date 2002-01-16 Time 19:32 Sent To  
Notes
2002-01-16 00:00:00NO PLUMBING SHOWN;
 94 SPC 401.2.2 ALL BUILDINGS INTENDED
 FOR HUMAN OCCUPANCY SHALL ADEQUATE
 SANITARY FACILITIES.
 SHOW WATER AND STORM DIAGRAMS AND
 INFORMATION.

Review Stop Z ZONING
Rev No 2 Status P Date 2002-03-14 Cont ID  
Sent By sgraham Date 2002-03-14 Time 10:38 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2002-01-04 Cont ID  
Sent By sgraham Date 2002-01-04 Time 15:11 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***