Plan Review Details - Permit 01121693
| Plan Review Stops For Permit 01121693 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2002-01-28 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-01-28 |
Time |
16:25 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-01-28 |
Time |
16:24 |
Sent To |
|
|
| Notes |
| 2002-01-28 00:00:00 | **************** UNSAT ************ | | | | | | 1)NOTE: PLEASE E2.1 SOME NOTES DO NOT | | | CORRELATE WITH PLANS. SEE #11, TWO #17`S | | | #10? | | | | | | 2)NOTE: PLEASE SHOW GFI LOCATIONS FOR | | | A/C COND UNITS REQ`D PER 210-63 AND | | | 309.2 OF THE MECH CODE. IN A READILY | | | ACCESS. PLEASE SHOW LOCATIIONS ON E4.5 | | | ROOF TOP ALSO. | | | | | | 3)NOTE: PLEASE SEE MISSING OUTLETS PER | | | 2' OF WALL IN UNITS. 210-52 | | | | | | 4)NOTE: PLEASE NOTE THAT LOAD ON PANELS | | | P1EA,P1EB EXCEED 150AMPS. | | | | | | 5)NOTE: PLEASE SEE LOADS FOR PANELS | | | P2EC,ED,EE EXCEEDS RATING OF EQUIPMENT. | | | PLEASE NOTE CONDUCTOR SIZE WON'T BE | | | LARGE ENOUGH. | | | | | | 6) NOTE: SMOKE DETECTORS ARE REQUIRED | | | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. | | | ALSO ON EACH LEVEL OF A MULTI-LEVEL | | | DWELLING UNIT. ROOMS WITH BATHS AND OR | | | CLOSETS ARE CONSIDERED SLEEPING ROOMS. | | | PER NFPA-72 2-2.1.1.1. | | | CLARIFY IF COMPLETE FIRE ALARM WILL | | | CARRY SD`S.? | | | | | | 7)NOTE: PLEASE NOTE SHUNT TRIPS SHOWN | | | ON EDP NEED TO BE CLARIFIED. SEE | | | NEC 230-76 AND 230-79. | | | | | | 8)NOTE: PLEASE NOTE/ PROVIDE MORE DETAIL | | | FOR TYPES OF MOTORS FOR ELEVATORS AND | | | TYPE OF BRKR OCP. | | | 430-148(TABLES) | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR' | | | REVIEW. IF THERE ARE NAY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-65-8096 EXT8372 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
N |
Date |
2002-01-14 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2002-01-14 |
Time |
14:08 |
Rev Time |
0.00 |
| Received By |
mamini |
Date |
2002-01-14 |
Time |
14:08 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2002-01-15 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-01-15 |
Time |
12:51 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-01-15 |
Time |
12:51 |
Sent To |
|
|
| Notes |
| 2002-01-15 00:00:00 | 1) SITE PLAN FOR THE BUILDING SHOULD | | | PROVIDE INFORMATION ON FIRE HYDRANT | | | LOCATIONS, SIZE AND LOCATIONS OF FIRE | | | MAINS, ETC. | | | 2) HOW IS FIRE RESCUE EXPECTED TO ENTER | | | THE COMPLEX. WILL THE GUARD HOUSE | | | BE STAFFED FULL OR PART TIME OR WILL | | | THEIR BE CERTAIN TIMES THAT IT WILL | | | BE STAFFED. | | | 3) WHERE ARE THE ARCHITECTURAL PLANS FOR | | | THE ADULT LIVING FACILITY. | | | 4) SEPARATE PLANS AND PERMITS REQUIRED | | | FOR GENERATOR INSTALLATION. | | | 5) DUCT SMOKE DETECTORS WHEN ACTIVATED | | | SHALL CAUSE THE FIRE ALARM SYSTEM TO | | | ACTIVATE. | | | 6) PLEASE EXPLAIN DRY SYSTEM NOTES ON | | | PAGE E6.6. | | | 7) KITCHEN FIRE SUPPRESSION NOTES ON | | | E6.4 NEEDS TO IDENTIFY THAT WHEN THE | | | HOOD SYSTEM ACTIVATES, THE EXHAUST | | | FAN IS TO RUN AND THE MAKE-UP AIR | | | SHUT DOWN. | | | 8) NO FIRE SPRINKLER OR HYDRAULIC | | | CALCULATIONS PROVIDED FOR ADULT LIVING | | | FACILITY. | | | 9) PLEASE CORRELATE THE PLANS THAT | | | WERE SUBMITTED. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2002-01-29 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-01-29 |
Time |
10:50 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2002-01-29 |
Time |
10:50 |
Sent To |
|
|
| Notes |
| 2002-01-29 00:00:00 | | | | ASSISTED LIVING PERMIT 01121693 | | | | | | | | | NO MECHANICAL PLANS SUBMITTED FOR REVIEW | | | FOR THIS PERMIT. | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2002-01-29 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-01-29 |
Time |
18:29 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2002-01-29 |
Time |
18:26 |
Sent To |
|
|
| Notes |
| 2002-01-29 00:00:00 | DENIED | | | REFERENCE: SPC-94 - FHA-AMENDED-98 | | | DESIGN MANUAL | | | | | | NO ARCHITECTUAL OR PLUMBING PLANS FOUND | | | FOR ASSISTED LIVING BLDG. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
|