| 2002-01-29 00:00:00 | DENIED |
| | REFERENCE: SPC-94-FHA-AMEND 98 |
| | DESIGN MANUAL |
| | |
| | 1) SHT A4.01 NOTE STATES THAT 1ST FLOOR |
| | ONLY WILL BE ADAPTABLE. ALL UNITS OF ALL |
| | FLOORS SHALL BE ADAPTABLE PER FHA DESIGN |
| | MANUAL. (SEE PAGE #7 OF DESIGN MANUAL). |
| | 2) DESIGN OPTION "A" OR "B" SHALL BE |
| | NOTED ON PLANS FOR ALL BATHROOMS. |
| | 3) REQUIREMENTS 1 THRU 7 OF THE FHA-98 |
| | DESIGN MANUAL SHALL BE REQUIRED FOR ALL |
| | UNITS. |
| | 4) PLEASE SHOW CLEAR FROOR SPACE FOR ALL |
| | FIXTURES REQUIRED TO BE ADAPTABLE. |
| | 5) SHT A8.03 DETAIL 14 BACKING IN BACK |
| | OF TUB/SHOWER NOT AS REQUIRED IN CHAPT. |
| | 6 PAGE 6.9 OF FHA DESIGN MANUAL. |
| | 6) SHTS P-1/P-3/P-5/P-7 CLEAN-OUTS SHALL |
| | BE MAXIMUM OF 80' PER SPC SEC 710.2.4(2) |
| | 7) SHTS P-1/P-3/P-5/P-7 RELIEF VENT RE- |
| | QUIRED ON AT LEAST ONE CONDENSATE LINE |
| | PER BLDG. |
| | 8) SHTS P-9 THRU P-17 WATER ISOMETRIC |
| | RISERS. AIR CHAMBERS SHALL NOT BE USED, |
| | SEE SHT P-25 NOTE #16. WATER HAMMER |
| | ARRESTORS SHALL BE LOCATED NEAR FIXTURES |
| | IN AN "EFFECTIVE RANGE" NOT ON TOP OF |
| | DROPS AS SHOWN. INSTALL PER PDI-WH 201 |
| | AND MANUFACTURES INSTALLATION INSTRUCT- |
| | IONS. |
| | 9) SHT P-3 BRIDGEPORT DELUX MODEL IS K2 |
| | OR 12 RISER PICKING UP LAV IN POWDER RM? |
| | 10) SHT P-19 RISER "E" HAS 2" ON FLAT |
| | AND 3" RISER. PLEASE CLAIRFY |
| | 11) SHT P-3 RISER "D1" 3 WATER CLOSETS |
| | ON 3" BLDG DRAIN NOT ALLOWED SPC TABLE |
| | 714.1 FOOTNOTE #3 |
| | 12) SHT P-18 RISER "R" AIR CHAMBER SHALL |
| | BE ACCESSIBLE AND RECHARGEABLE PER PDI- |
| | WH 201 AND SPC SEC 607.8.3. PLEASE SHOW |
| | DETAILS. |
| | 13) SHT P-18 RISERS, CONDENSATE VENT |
| | SHALL NOT TERMINATE IN PLENUM FOR A/C |
| | PLEASE SHOW DETAIL FOR TERMINATION OF |
| | VENT FOR CONDENSATES. |
| | |