Plan Review Details - Permit 01121691
Plan Review Stops For Permit 01121691
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-02-04 Cont ID  
Sent By hpiskura Date 2002-02-04 Time 15:51 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2002-02-04 00:00:00SEE 01121700 FOR COMMENTS

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-01-28 Cont ID  
Sent By dpalmer Date 2002-01-28 Time 14:51 Rev Time 0.00
Received By dpalmer Date 2002-01-28 Time 14:51 Sent To  
Notes
2002-01-28 00:00:00******************** UNSAT *************
  
  
 1)NOTE: PLEASE NOT ALL PANELS/SERVICE
 EQUIPMENT ARE SHOWN ON PLANS.
 PLEASE SHOW EXACT LOCATION OF MAIN SERV-
 ICE ON FLOOR PLAN. SHOWS 1LC,1LB, NO
 2LA AND 1LA.?
 2)NOTE: PLEASE NOTE CIRCUITS #`S NEED TO
 BE IDENTIFIED TO PANELS AND SHOWN ON
 FLOOR PLANS.
  
 3)NOTE: PLEASE NOTE THAT ALL CONTINUOUS
 LOADS FOR HOUSE PANELS NEED TO BE SHOWN
 AT 125%
  
 4)NOTE: PLEASE CLARIFY "SHUNT TRIP" FOR
 MAIN. PLEASE SEE 230-76 AND 230-79 FOR
 MANUAL MEANS OF DISC REQ`D.
  
 5)NOTE: PLEASE CLARIFY 30' GROUND ROD
 SHOWN ON RISER DIAGRAM.
  
 6)NOTE: PLEASE NOTE ALL HEIGHT REQ`MENTS
 NEED TO BE SHOWN ON PLANS. PLEASE SEE
 FHAR, 24 CFR 100.205 CHAPTER 5.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS ,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2002-01-14 Cont ID  
Sent By mamini Date 2002-01-14 Time 14:10 Rev Time 0.00
Received By mamini Date 2002-01-14 Time 14:10 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-01-25 Cont ID  
Sent By pkrauss Date 2002-01-24 Time 15:58 Rev Time 6.00
Received By pkrauss Date 2002-01-24 Time 12:54 Sent To  
Notes
2002-01-24 00:00:00APARTMENTS TYPE I, II, III, IVA
  
 1.PLAN SHEET A8.04 DETAIL #16, REF.
 DETAIL #11 & 12 ON PLAN SHEET A8.05,
 DETAIL #11 DRYWALL RETURN @ BATHTUB
 & #12 DOES NOT EXIST.PLEASE
 CLARIFY.
  
 2.DRYER VENT WILL NOT COMPLY WITH 1997
 SBC 705.2.3.3,DRYER VENT CONTAINS
 COMBUSTIBLE LINT.
  
 3.DETAIL OF DUCT PENETRATING SHAFT
 (A8.04), SHOWS DUCT PENETRATION AT
 A 45 DEGREE ANGLE.UL LISTING DOES
 NOT INDICATE THIS APPLICATION AS
 BEING APPROVED.
  
 4.PLEASE PROVIDE ELEVATION DETAIL OF
 SHAFTS OF THE DRYER AND TOILET
 EXHAUST, SPECIFY IF THE DUCTSARE
 RUNNING INDIVIDUALLY IN THE SHAFT.
  
 DRYER VENTS SHALL BE NON-SCREENED
 WITH A BACKDRAFT DAMPER. TOILET
 EXHAUST SHALL BE SCREENED.

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-01-29 Cont ID  
Sent By kstevens Date 2002-01-29 Time 08:37 Rev Time 0.00
Received By kstevens Date 2002-01-29 Time 08:37 Sent To  
Notes
2002-01-29 00:00:00DENIED
 REFERENCE: SPC-94-FHA-AMEND 98
 DESIGN MANUAL
  
 1) SHT A4.01 NOTE STATES THAT 1ST FLOOR
 ONLY WILL BE ADAPTABLE. ALL UNITS OF ALL
 FLOORS SHALL BE ADAPTABLE PER FHA DESIGN
 MANUAL. (SEE PAGE #7 OF DESIGN MANUAL).
 2) DESIGN OPTION "A" OR "B" SHALL BE
 NOTED ON PLANS FOR ALL BATHROOMS.
 3) REQUIREMENTS 1 THRU 7 OF THE FHA-98
 DESIGN MANUAL SHALL BE REQUIRED FOR ALL
 UNITS.
 4) PLEASE SHOW CLEAR FROOR SPACE FOR ALL
 FIXTURES REQUIRED TO BE ADAPTABLE.
 5) SHT A8.03 DETAIL 14 BACKING IN BACK
 OF TUB/SHOWER NOT AS REQUIRED IN CHAPT.
 6 PAGE 6.9 OF FHA DESIGN MANUAL.
 6) SHTS P-1/P-3/P-5/P-7 CLEAN-OUTS SHALL
 BE MAXIMUM OF 80' PER SPC SEC 710.2.4(2)
 7) SHTS P-1/P-3/P-5/P-7 RELIEF VENT RE-
 QUIRED ON AT LEAST ONE CONDENSATE LINE
 PER BLDG.
 8) SHTS P-9 THRU P-17 WATER ISOMETRIC
 RISERS. AIR CHAMBERS SHALL NOT BE USED,
 SEE SHT P-25 NOTE #16. WATER HAMMER
 ARRESTORS SHALL BE LOCATED NEAR FIXTURES
 IN AN "EFFECTIVE RANGE" NOT ON TOP OF
 DROPS AS SHOWN. INSTALL PER PDI-WH 201
 AND MANUFACTURES INSTALLATION INSTRUCT-
 IONS.
 9) SHT P-3 BRIDGEPORT DELUX MODEL IS K2
 OR 12 RISER PICKING UP LAV IN POWDER RM?
 10) SHT P-19 RISER "E" HAS 2" ON FLAT
 AND 3" RISER. PLEASE CLAIRFY
 11) SHT P-3 RISER "D1" 3 WATER CLOSETS
 ON 3" BLDG DRAIN NOT ALLOWED SPC TABLE
 714.1 FOOTNOTE #3
 12) SHT P-18 RISER "R" AIR CHAMBER SHALL
 BE ACCESSIBLE AND RECHARGEABLE PER PDI-
 WH 201 AND SPC SEC 607.8.3. PLEASE SHOW
 DETAILS.
 13) SHT P-18 RISERS, CONDENSATE VENT
 SHALL NOT TERMINATE IN PLENUM FOR A/C
 PLEASE SHOW DETAIL FOR TERMINATION OF
 VENT FOR CONDENSATES.
  
 REVIEW BY KEN STEVENS
 (561)659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***