Plan Review Details - Permit 01121511
| Plan Review Stops For Permit 01121511 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2002-01-30 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2002-01-29 |
Time |
16:17 |
Rev Time |
0.00 |
| Received By |
mamini |
Date |
2002-01-25 |
Time |
15:37 |
Sent To |
Z |
|
| Notes |
| 2002-01-29 00:00:00 | | | | | | | A LICENSED GENERAL CONTRACTOR MUST APPLY | | | FOR THE PERMIT.NEITHER THE "THE CITY | | | OF WEST PALM BEACH" NOR THE "ECRWWTP" | | | QUALIFY FOR THE "OWNER BUILDER | | | EXEMPTION" OF THE STATE LICENSING LAWS. | | | | | | FURTHER THE DECLARED VALUATION OF | | | $17,120,000.00 EXCEEDS THE $25,000.00 | | | ALLOWED BY THAT EXCEPTION TO THE | | | LICENSING LAWS. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2002-01-11 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-01-11 |
Time |
06:00 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-01-11 |
Time |
06:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
P |
Date |
2001-12-28 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2001-12-28 |
Time |
16:16 |
Rev Time |
5.00 |
| Received By |
mamini |
Date |
2001-12-28 |
Time |
15:04 |
Sent To |
|
|
| Notes |
| 2001-12-28 00:00:00 | PASSED WITH PROVISOS : | | | "FACILITY PLAN SET" | | | 1. SHEET CD-2 ,GENERAL NOTES | | | DEFINITION OF DEPARTMENT SHOULD BE CITY | | | OF WEST PALM BEACH, PLEASE VERIFY. | | | 2. SHEET M-3 ,HANDRAIL NOTES | | | DESIGN SHOULD MEET SBCCI 97, PLEASE | | | VERIFY. | | | 3. SHEET S-1 , GENERAL-STRUCTURAL NOTES | | | NO. 1 NOTE, ALL WORKS SHALL CONFORM TO | | | THE SBCCI 97, PLEASE VERIFY. | | | "INJECTION WELL SET" | | | 1. SHEET M-2 , PLEASE INDICATE SHEET NO. | | | FOR CONCRETE WELL PAD DETAILS . | | | | | | IF ANY QUESTIONS PLEASE CONTACT 659-8096 | | | EXT. 8492 MOHAMMAD R. AMINI |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2002-01-02 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-01-02 |
Time |
15:24 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-01-02 |
Time |
15:24 |
Sent To |
|
|
| Notes |
| 2002-01-02 00:00:00 | 1) BOLLARDS INSTALLED NEAR FIRE HYDRANTS | | | SHALL NOT INTERFERE WITH THE | | | REQUIRED OPERATION OF THEM. | | | 2) THE CHLORINE BUILDING IS TO COMPLY | | | WITH NFPA 430. EXAMPLES INCLUDE AN | | | EMERGENCY PLAN, APPROPRIATE SIGNAGE, | | | NO SMOKING SIGNAGE, EMPLOYEE | | | INSTRUCTIONS, MANUAL FIREFIGHTING | | | EQUIPMENT, WATER SUPPLIES AT 750 GALLONS | | | PER MINUTE OF WATER OR 500 GALLONS | | | PER MINUTE OF WATER IF SPRINKLER SYSTEMS | | | ARE PLANNED. PLEASE REVIEW NFPA 430 | | | AND MAKE THE NECESSARY COMMENTS ON THE | | | PLANS. | | | 3) PLEASE SEE STAIR DETAILS ON S-19. | | | MAXIMUM RISE ON STAIRS IS 7 INCHES, AND | | | MINIMUM TREADS TO BE AT LEAST 11 INCHES. | | | 4) PLEASE PROVIDE MORE DETAILS ON 5 | | | MILLION GALLON EQUALIZER TANK. PLEASE | | | CLEARLY INDCATE WHAT IS STORED IN THE | | | TANK, AND ANY ASSOCIATED PRESSURES, | | | HEALTH HAZARDS, ETC. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2002-01-24 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-01-08 |
Time |
08:36 |
Rev Time |
3.00 |
| Received By |
pkrauss |
Date |
2002-01-05 |
Time |
10:02 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2002-01-14 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-01-14 |
Time |
16:43 |
Rev Time |
2.50 |
| Received By |
kstevens |
Date |
2002-01-14 |
Time |
16:43 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2002-01-30 |
Time |
07:10 |
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
|