Plan Review Details - Permit 01121511
Plan Review Stops For Permit 01121511
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-01-30 Cont ID  
Sent By hpiskura Date 2002-01-29 Time 16:17 Rev Time 0.00
Received By mamini Date 2002-01-25 Time 15:37 Sent To Z
Notes
2002-01-29 00:00:00 
  
 A LICENSED GENERAL CONTRACTOR MUST APPLY
 FOR THE PERMIT.NEITHER THE "THE CITY
 OF WEST PALM BEACH" NOR THE "ECRWWTP"
 QUALIFY FOR THE "OWNER BUILDER
 EXEMPTION" OF THE STATE LICENSING LAWS.
  
 FURTHER THE DECLARED VALUATION OF
 $17,120,000.00 EXCEEDS THE $25,000.00
 ALLOWED BY THAT EXCEPTION TO THE
 LICENSING LAWS.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-01-11 Cont ID  
Sent By dpalmer Date 2002-01-11 Time 06:00 Rev Time 0.00
Received By dpalmer Date 2002-01-11 Time 06:00 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2001-12-28 Cont ID  
Sent By mamini Date 2001-12-28 Time 16:16 Rev Time 5.00
Received By mamini Date 2001-12-28 Time 15:04 Sent To  
Notes
2001-12-28 00:00:00PASSED WITH PROVISOS :
 "FACILITY PLAN SET"
 1. SHEET CD-2 ,GENERAL NOTES
 DEFINITION OF DEPARTMENT SHOULD BE CITY
 OF WEST PALM BEACH, PLEASE VERIFY.
 2. SHEET M-3 ,HANDRAIL NOTES
 DESIGN SHOULD MEET SBCCI 97, PLEASE
 VERIFY.
 3. SHEET S-1 , GENERAL-STRUCTURAL NOTES
 NO. 1 NOTE, ALL WORKS SHALL CONFORM TO
 THE SBCCI 97, PLEASE VERIFY.
 "INJECTION WELL SET"
 1. SHEET M-2 , PLEASE INDICATE SHEET NO.
 FOR CONCRETE WELL PAD DETAILS .
  
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-01-02 Cont ID  
Sent By mcarsill Date 2002-01-02 Time 15:24 Rev Time 0.00
Received By mcarsill Date 2002-01-02 Time 15:24 Sent To  
Notes
2002-01-02 00:00:001) BOLLARDS INSTALLED NEAR FIRE HYDRANTS
 SHALL NOT INTERFERE WITH THE
 REQUIRED OPERATION OF THEM.
 2) THE CHLORINE BUILDING IS TO COMPLY
 WITH NFPA 430. EXAMPLES INCLUDE AN
 EMERGENCY PLAN, APPROPRIATE SIGNAGE,
 NO SMOKING SIGNAGE, EMPLOYEE
 INSTRUCTIONS, MANUAL FIREFIGHTING
 EQUIPMENT, WATER SUPPLIES AT 750 GALLONS
 PER MINUTE OF WATER OR 500 GALLONS
 PER MINUTE OF WATER IF SPRINKLER SYSTEMS
 ARE PLANNED. PLEASE REVIEW NFPA 430
 AND MAKE THE NECESSARY COMMENTS ON THE
 PLANS.
 3) PLEASE SEE STAIR DETAILS ON S-19.
 MAXIMUM RISE ON STAIRS IS 7 INCHES, AND
 MINIMUM TREADS TO BE AT LEAST 11 INCHES.
 4) PLEASE PROVIDE MORE DETAILS ON 5
 MILLION GALLON EQUALIZER TANK. PLEASE
 CLEARLY INDCATE WHAT IS STORED IN THE
 TANK, AND ANY ASSOCIATED PRESSURES,
 HEALTH HAZARDS, ETC.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-01-24 Cont ID  
Sent By pkrauss Date 2002-01-08 Time 08:36 Rev Time 3.00
Received By pkrauss Date 2002-01-05 Time 10:02 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-01-14 Cont ID  
Sent By kstevens Date 2002-01-14 Time 16:43 Rev Time 2.50
Received By kstevens Date 2002-01-14 Time 16:43 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status   Date   Cont ID  
Sent By hpiskura Date 2002-01-30 Time 07:10 Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***