Plan Review Details - Permit 01121500
Plan Review Stops For Permit 01121500
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2002-06-03 Cont ID  
Sent By shernand Date 2003-05-28 Time 14:29 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2002-06-03 00:00:00SUBJECT TO SIGNED SEALED AND DATED FIRE
 PROTECTION INFORMATION BEING PROVIDED
 FOR RECORD.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2002-04-04 Cont ID  
Sent By hpiskura Date 2002-04-04 Time 10:06 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2002-04-04 00:00:00A PERMIT TO CONSTRUCT MAY NOT BE ISSUED
 UNLESS THE FIRE PROTECTION DESIGN IS
 INCLUDEDWITH THE PLANS AND REVIEWED
 FOR CODE COMPLIANCE.THIS INCLUDES THE
 FIRE ALARM SYSTEM, FIRE SPRINKLER
 SYSTEM AND ANY OTHER PERTINENT ITEMS.
 THIS IS IN ACCORDANCE WITH FLORIDA
 STATUTES TITLE XXXIII CHAPTER 553
 SECTION 553.79 (2)
  
 FURTHER, THE FIRE PROTECTION PLANS MUST
 BE PREPARED, SIGNED, SEALED AND DATE BY
 FLORIDA REGISTERED FIRE PROTECTION
 ENGINEER.SEE CHAPTER 61-G15-32,
 RESPONSIBILITY RULES OF PROFESSIONAL
 ENGINEERS CONCERNING THE DESIGN OF
 FIRE PROTECTION SYSTEMS OF THE FLORIDA
 ADMINISTRATIVE CODE.
  
 THE PREVIOUS REQUEST FOR THE TYPE AND
 QAUNTITIES OF THE COMMODITIESTO BE
 STORED AS DESCRIBED IN SBC AND NFPA
 PUBLICATIONS, A GROUP H OCCUPANCY MUST
 BE ASSUMEDAS IS DISCUSSED IN THE TVA
 LETTER DATED FEBRUARY 14, 2002.A
 "PERFORMANCE BASED" DESIGN MUST BE
 APPROVED BY THE BUILDING OFFICIAL AS
 PROVIDED FOR IN SBC 103.7, ALTERNATE
 MATERIALS AND METHODS.
  
 THE MULVANNY G2 PERMIT PLAN PREVIEW
 COMMENTS RESPONSES, (NON DATE) IN
 ADDRESSINGTHE QUESTION OF QUANTITY OF
 PALLET STORAGE MAKES REFERENCE TO
 PARAGRAPH 6.4 OF THE TVA REPORT WHICH
 IN TURNPROVIDES ONLY ONE DIMENSION,
 HEIGHT, WHICH IS INSUFFICIENT
 INFORMATION AS TO THE VOLUME OF IDLE
 PALLET STORAGE.
  
 TEST AND ACCEPTANCE REPORTS WILL BE
 NECESSARY FOR THE "BRISTOL SKYLIGHTS"
 AS WELL AS THE REMINDER OF THE WINDOWS
 AND THE DOORS TO BE USED IN THE
 BUILDING.
  
 STRUCTURAL CALCULATIONS BY ENGINEERS
 NORTHWEST, OF SEATTLE, WA. INDICATE A
 REVIEW FOR ASCE 7-95, THE MULVANNY
 RESPONSE BOOK DECLARES ASCE 7-95, AND
 SHEET S1.0 REMAINS SOMEWHAT NEBULOUS AS
 TO WHICH METHOD OF WIND DESIGN WAS
 USED.THE SPECIFICATIONS HAVE A
 REFERENCE TO ICBO. THE VP (METAL
 BUILDING) DECLARE SBC 110 MPH.
  
 SEE SBC 1606.1.2.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-01-22 Cont ID  
Sent By hpiskura Date 2002-01-22 Time 12:41 Rev Time 0.00
Received By hpiskura Date 2002-01-16 Time 10:57 Sent To  
Notes
2002-01-22 00:00:00THE FIRE PROTECTION PLANS ARE
 INCOMPLETE.PLEASE PROVIDE PLANS IN
 ACCORDANCE WITH CHAPTER 8 OF NFPA 13-99.
  
 GIVEN THAT THE COMMODITIES TO BE STORED
 ARE CLASS IV, SOME OF THE QUANTITIES MAY
 NEED TO BE STORED IN CONTROL AREAS AS
 PROVIDED FOR IN SBC 312.2.3 AND SBC 407.
 1.
  
 PLEASE SHOW DETAILS FOR
 THE BATTERY STORAGE RACKS AS TO
 VENTILATION AND SUPPORTING STRUCTURE.
 SEE SBC 411.1.2 (NEC 480)
  
 SHEETS A1.02, 1.03 AND 1.04.WHAT ARE
 THE PARALLEL LINES IN THE VICINITY OF
 GRID LINES A & B INDICATIVE OF?
  
 SHEET A1.02, KEY NOTE 15.WHERE IS THE
 PALLET STORAGE AREA? WHAT QUANTITY,
 VOLUME?
  
 PROVIDE INFORMATION FOR THE VINYL FACED
 INSULATION THAT WILL BE EXPOSED AS
 INTERIOR FINISH.SEE SBC 803.3
  
 THE ROOF SKYLIGHTS MUST COMPLY WITH SBC
 2604.6 AND THE CITY'S HURRICANE MISSILE
 IMPACT RESISTANCE REQUIREMENTS.
  
 SHEET S1.01 GENERAL NOTES IS NOT CLEAR
 AS TO WHICH DESIGN METHOD FOR WIND WAS
 USED, SBC 1606.2 OR ASCE 7-95. PLEASE
 DECLARE ONE.SEE SBC 1606.1.2.
  
 THE SPECIFICATIONS AND SOIL REPORTS
 WERE NOT INCLUDED WITH THE APPLICATION
 SO A COMPLETE CODE REVIEW IS NOT
 POSSIBLE.
  
 A RESIDENT INSPECTOR WILL BE REQUIRED
 FOR THIS PROJECT.CONTACT DON NEELY,
 ASSISTANT BUILDING OFFICIAL FOR MORE
 INFORMATION.561-659-8096 X 8333.
  
 BEFORE A PERMIT TO CONSTRUCT MAY BE
 ISSUED IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY FOR THE CITY, THE PERMIT
 PLANS STAMPED BY THAT OFFICE, AND A
 COPY OF THE PAID RECEIPT ATTACHED TO
 THE PERMIT APPLICATION.CALL
 561-233-5025 FOR MORE INFORMATION.
  
 PLEASE PROVIDE A RECENT SIGNED, SEALED
 AND DATED PROPERTY SURVEY.

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2003-02-19 Cont ID  
Sent By dpalmer Date 2003-02-19 Time 06:36 Rev Time 0.75
Received By dpalmer Date 2003-02-19 Time 06:36 Sent To  
Notes
2003-02-19 00:00:00REV FOR DELETING HYDRAULIC LIFTS.

Review Stop E ELECTRICAL
Rev No 4 Status N Date 2003-02-18 Cont ID  
Sent By dpalmer Date 2003-02-18 Time 09:19 Rev Time 0.25
Received By dpalmer Date 2003-02-18 Time 09:19 Sent To  
Notes
2003-02-18 00:00:00SUBMITTALS FOR SERVICE EQUIPMENT NOT
 REQ`D FOR REVIEW OR SUBMITTAL.
 BACK TO CONT.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2002-05-30 Cont ID  
Sent By dpalmer Date 2002-05-30 Time 12:55 Rev Time 0.00
Received By dpalmer Date 2002-05-30 Time 12:55 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2002-03-21 Cont ID  
Sent By dpalmer Date 2002-03-21 Time 06:11 Rev Time 0.00
Received By dpalmer Date 2002-03-20 Time 20:04 Sent To  
Notes
2002-03-21 00:00:00**************** UNSAT **************
  
 1)NOTE: PLEASE SHOW GROUNDING FOR GUARD
 BOOTH AND PUMP BLDG ON LINE DIAGRAM.IT
 IS NOTED GRND DETAIL IS SHOWN ON 4.2
  
 2)NOTE: PLEASE PROVIDE INFORMATION
 ON FIRE PUMP. PLEASE CLARIFY PUMP SHOWN
 COMING FROM PANEL P-10? PLEASE SEE
 695-3A. PLEASE CLARIFY SHOWN ONLY AS
 20A 1POLE?
  
  
  
  
 3)NOTE: PLEASE CLARIFY IF THERE IS
 GOING TO BE ANY EMERGENCY GENERATOR ON
 SITE? IF POWER GOES DOWN, HOW IS ALL
 COLD STORAGE GOING TO GET POWER?
  
 4)NOTE: PLEASE SEE FIRE REVIEW COMMENTS
 FOR ANYTHING THAT MAY DIRECTLY LINK ANY
 CHANGES IN ELECTRICAL PLANS. IE, GENER.
 FIRE PUMP, ETC.
  
 5)NOTE: PLEASE NOTE, NOTE #4 FROM FIRST
 REVIEW. PLEASE CLARIFY WHERE CONTINUOUS
 LOADS ARE SHOWN AT 125% AND LARGEST
 MOTOR LOAD.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372
  
 6)NOTE: PLEASE NOTE WRONG COLOR CODING
 FOR CONDUCTORS IN SPEC BOOKS. PLEASE
 NOTE THAT PER LOCAL AMENDMENTS(215)
 277/480 IS BROWN/ PURPLE/ YELLOW..

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-01-09 Cont ID  
Sent By dpalmer Date 2002-01-09 Time 12:41 Rev Time 0.00
Received By dpalmer Date 2002-01-08 Time 18:58 Sent To  
Notes
2002-01-09 00:00:00******************UNSAT **************
  
 1)NOTE: PLEASE NOTE METHOD GROUNDING
 TRANSFORMER PER 250-30 PLANS SHOW COLD
 WATER PIPE. PLEASE NOTE THAT BREAKS IN
 THE LINE FOR WATER FROM REPAIRS ETC TO
 PVC AND CAUSE IMPROPER GOUNDING. PLEASE
 HAVE GROUNDING OF TRANSFOMER GO TO A
 NEAREST BLDG.STRUC STEEL.
  
 2)NOTE: PLEASE CLARFIY, PLAN SHOWS
 FROM "MSB-1" COMPRESSORS BY HUSSMAN?
 PLEASE NOTE DETAIL NEEDS TO BE SHOWN
 ON THESE PLANS OR SEPARATE PLANS AND
 PERMIT APPLICATION NEED TO BE SUBMITTED
 FOR REVIEW. PLEASE CLARIFY IF THESE
 ARE FOR FUTURE OR WILL BE INSATLLED
 AT THE SAME TIME OF THIS BEING BUILT?
  
 3)NOTE: PLEASE OCP FOR PANEL "P8", SHOWS
 A 200A/3P AND 110 AF. PLEASE CLARIFY
 "AF" AND NOTE CONDUCTOR SIZE RATED AT
 130AMPS.
  
 4)NOTE: PLEASE NOTE, LOAD CALCUALTIONS
 NEED TO BE SHOWN PER 220-2,220-10,220-11
 220-13.
 PLEASE NOTE THAT ALL CONTINUOUS LOADS
 NEED TO BE SHOWN AT 125%. PER 230-42,
 215-3.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2002-03-12 Cont ID  
Sent By mamini Date 2002-03-12 Time 13:58 Rev Time 1.00
Received By mamini Date 2002-03-12 Time 13:58 Sent To  
Notes
2002-03-12 00:00:00PASSED:
 1. REVISION TO CIVIL/SITE PLANS AS
 SUBMITTED APPROVED.
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2002-01-18 Cont ID  
Sent By mamini Date 2002-01-02 Time 15:02 Rev Time 1.00
Received By mamini Date 2002-01-02 Time 15:02 Sent To  
Notes
2002-01-02 00:00:00FAILED :
 1. UNDERGROUND UTILITIES / SITE WORK
 PLANS WERE REVIEWED UNDER PERMIT NUMBER
 01020979 ( PLAN REVIEW ).
 2. REVISIONS TO UNDERGROUND UTILITIES /
 SITE WORK PLANS MUST BE SUBMITTED TO THE
 BUILDING DEPARTMENT FOR REVIEW AND
 APPROVAL.
 3. EMPLOYEE PARKING STALLS MUST BE
 PAINTED WITH DOUBLE 4" WIDE, WHITE
 FOR REGULAR AND BLUE FOR H.C.
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2003-10-28 Cont ID  
Sent By nmccray Date 2003-10-28 Time 13:48 Rev Time 0.00
Received By nmccray Date 2003-10-28 Time 13:48 Sent To  
Notes
2003-10-28 00:00:00REVISION TO FIRE SPRINKLER RISERS DATED
 10-27-03

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2002-07-30 Cont ID  
Sent By csiegber Date 2003-10-27 Time 14:24 Rev Time 0.00
Received By mcarsill Date 2002-07-30 Time 09:16 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2002-03-21 Cont ID  
Sent By mcarsill Date 2002-03-21 Time 10:31 Rev Time 0.00
Received By hpiskura Date 2002-03-21 Time 10:31 Sent To  
Notes
2002-03-21 00:00:00A) PLEASE INDICATE HOW THE PRESCRIPTIVE
 CODE REQUIREMENTS OF NFPA 51B, THE
 STANDARD FOR FIRE PREVENTION, DURING
 WELDING, CUTTING, AND OTHER HOT WORK
 WILL BE ACCOMPLISHED WITHIN THE
 BUILDING. FURTHER DEFINE "LIGHT DUTY
 REPAIR WORK" AS NOTED IN PLAN REVIEW
 RESPONSE. IS ANY ACETYLENE GAS PLANNED
 TO BE USED OR STORED IN THE BUILDING.
 B) COMPLAINCE WITH CITY CODE 3206-99
 "HAZARDOUS MATERIALS MAY BE APPLICABLE
 TO THE SITE. A COMPLETE LIST OF
 POTENTIAL HAZARDOUS MATERIALS FROM
 COSTCO HAS NOT YET BEEN RECEIVED.
 C) THE AMMONIA TANK MECHANICAL
 REFRIGERATION SYSTEM MUST COMPLY WITH
 NFPA 1, CHAPTER 23, MECHANICAL
 REFRIGERATION.
 D) A MINIMUM OF TWO FIRE HYDRANTS ARE
 TO BE PROVIDED ON THE 12" WATER MAIN
 OUTSIDE OF THE COSTCO WAREHOUSE FOR
 THE FUTURE EDITIONS OF THE BUILDING.
 E) PALLET STORAGE AREA- ARE THESE
 EMPTY, FULL, PLASTIC, OR WOOD PALLETS.
 F) COULD NOT LOCATE ANY FIRE ALARM
 HORN STROBES IN WAREHOUSE AREA.
 G) IS AN EMERGENCY GENERATOR PLANNED
 FOR THE SITE IN THE EVENT OF LOSS OF
 POWER.
 H) THE FIRE ALARM SYSTEM TO BE CLASS A
 OR FULLY ADDRESSABLE.
 I) IT IS RECOMMENDED THAT ANOTHER TAP
 BE MADE ON THE 12" LINE SO A REDUNCY
 IS PRESENT AND ALSO WITH THE FUTURE
 EDITIONS ANTICIPATED.
 K) PLEASE CLEARLY INDICATE ALL EMERGENCY
 LIGHT FIXURES IN MAIN WAREHOUSE AREA.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-12-26 Cont ID  
Sent By mcarsill Date 2001-12-26 Time 15:41 Rev Time 0.00
Received By mcarsill Date 2001-12-26 Time 15:41 Sent To  
Notes
2001-12-26 00:00:001) WET FIRE HYDRANTS ARE REQUIRED PRIOR
 TO,DURING AND AFTER CONSTRUCTION.
 2) SUITABLE ROADS ARE TO BE PROVIDED
 AT THE SITE FOR EMERGENCY PURPOSES FOR
 FIRE AND PARAMEDICAL EQUIPMENT.
 3) GUARD BOOTH CANOPY SHALL BE AT LEAST
 13'- 6" HIGH IF FIRE APPARATUS ARE
 EXPECTED TO PASS UNDERNEATH IT.
 4) FIRE HYDRANTS ARE TO BE INSTALLED TO
 UTILITY AND FIRE RESCUE STANDARDS.
 5) ALL SECURITY GATES ARE TO BE PROPERLY
 PERMITTED. ANY ELECTRIC GATES MUST
 HAVE PROVISIONS FOR WHEN LOSS OF POWER
 OCCURS.
 6) TAMPER SWITCHES, CHAINS AND LOCKS
 WILL BE REQUIRED ON ALL BACKFLOW
 DEVICES.
 7) FIRE HYDRANT THREADS ARE TO BE
 COMPATIBLE WITH WEST PALM BEACH FIRE
 RESCUE STANDARDS.
 8) SEPARATE PLANS AND PERMITS REQUIRED
 FOR UNDERGROUND TANK SHOWN ON PAGE A1.01
 9) MORE DETAILS NEEDED ON BATTERY
 CHARGING AREA. ARE ANY NOXIUOS FUMES
 OR PRODUCTS PRODUCED WHILE THE BATTERIES
 ARE BEING CHARGED.
 10) PLEASE INDICATE HOW ITEMS WILL BE
 STORED. WHAT WILL THE MAXIMUM STORAGE
 HEIGHTS BE.
 11) PLEASE EXPLAIN WELDING RECEPTACLES.
 12) PLEASE PROVIDE INTERIOR FINISH
 CLASSIFICATION INFORMATION FOR ALL
 AREAS OF THE BUILDING.
 13) PLEASE EXPLAIN DRY SPRINKLER SYSTEMS
 WHY IS A WET FIRE SPRINKLER SYSTEM NOT
 SHOWN THROUGHOUT THE BUILDING.
 14) NO HYDRAULIC CALCULATIONS PROVIDED
 WITH PLANS.
 15) PLEASE EXPLAIN THE REASON FOR ALL
 OF THE END OF LINE RESISTORS SHOWN.
 16) NOTES ON FP1 WITH REGARDS TO
 WATER STORAGE TANK NOT CLEAR. PLEASE
 EXPLAIN RATIONALE. WHAT BASIS IS THESE
 NOTES PROVIDED FOR.
 17) WILL THE GUARD HOUSE BE STAFFED
 FULL TIME, PART TIME, ETC.
 18) PLEASE PROVIDE A LIST OF ANY AND
 ALL HAZARDOUS MATERIALS PLANNED FOR
 THE BUILDING.
 19) SEPARATE PLANS AND PERMITS REQUIRED
 FOR FIRE SPRINKLER SYSTEM. IT APPEARS
 THAT A MEETING WILL BE REQUIRED WITH
 REGARDS TO THE FIRE SPRINKLER DESIGN
 PLANNED FOR THE BUILDING.
 20) SEPARATE PLANS AND PERMITS REQUIRED
 FOR FIRE ALARM SYSTEM. CUT SHEETS,
 WIRING DIAGRAMS, BATTERY CALCULATIONS
 WILL BE REQUIRED.
 21) SEPARATE PLANS AND PERMITS REQUIRED
 FOR FUEL TANK.
 22) A DESIGNATED FIRE LANE WILL BE
 REQUIRED FOR THE BUILDING.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 18 Status N Date 2003-10-27 Cont ID  
Sent By csiegber Date 2003-10-27 Time 14:24 Rev Time 0.00
Received By csiegber Date 2003-10-27 Time 14:23 Sent To FIRE
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 17 Status N Date 2003-08-25 Cont ID  
Sent By csiegber Date 2003-08-25 Time 14:42 Rev Time 0.00
Received By csiegber Date 2003-08-25 Time 14:42 Sent To M
Notes
2003-08-25 00:00:00TO PK DESK

Review Stop I INCOMING/PROCESSING
Rev No 16 Status N Date 2003-05-28 Cont ID  
Sent By shernand Date 2003-05-28 Time 14:29 Rev Time 0.00
Received By shernand Date 2003-05-28 Time 14:29 Sent To B
Notes
2003-05-28 00:00:00HP DESK, SUBMITTAL.

Review Stop I INCOMING/PROCESSING
Rev No 15 Status N Date 2003-05-05 Cont ID  
Sent By shernand Date 2003-05-05 Time 11:49 Rev Time 0.00
Received By shernand Date 2003-05-05 Time 11:49 Sent To B
Notes
2003-05-05 00:00:00HP DESK, 2 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2003-04-01 Cont ID  
Sent By sthyng Date 2003-04-01 Time 16:22 Rev Time 0.00
Received By sthyng Date 2003-04-01 Time 16:22 Sent To B
Notes
2003-04-01 00:00:00SUBMITTALS TO HP DESK
 1.)GUARD BOOTH BLDG PAD CERIFICATION,
 FORM BOARD ELEVATION, TIE IN SURVEY
 2.)SKYLIGHT TEST DATA

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2003-03-31 Cont ID  
Sent By sthyng Date 2003-03-31 Time 16:18 Rev Time 0.00
Received By sthyng Date 2003-03-31 Time 16:18 Sent To B
Notes
2003-03-31 00:00:00TO HP DESK

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2003-03-25 Cont ID  
Sent By sthyng Date 2003-03-25 Time 13:28 Rev Time 0.00
Received By sthyng Date 2003-03-25 Time 13:28 Sent To B
Notes
2003-03-25 00:00:00TO HP DESK
 SKYLIGHT PRODUCT DATA

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2003-02-18 Cont ID  
Sent By dpalmer Date 2003-02-18 Time 14:50 Rev Time 0.00
Received By dpalmer Date 2003-02-18 Time 14:50 Sent To B
Notes
2003-02-18 00:00:00TO HHP DESK, TILT PANEL DETAIL.

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2003-02-18 Cont ID  
Sent By dpalmer Date 2003-02-18 Time 14:48 Rev Time 0.00
Received By dpalmer Date 2003-02-18 Time 14:48 Sent To B
Notes
2003-02-18 00:00:00TO HHP DESK, BOND BRKR.

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2003-02-18 Cont ID  
Sent By dpalmer Date 2003-02-18 Time 14:47 Rev Time 0.00
Received By dpalmer Date 2003-02-18 Time 14:47 Sent To B
Notes
2003-02-18 00:00:00TO HHP DESK, GROUT.

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2003-02-18 Cont ID  
Sent By dpalmer Date 2003-02-18 Time 14:46 Rev Time 0.00
Received By dpalmer Date 2003-02-18 Time 14:46 Sent To B
Notes
2003-02-18 00:00:00TO HHP DESK, BONDING.

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2003-02-18 Cont ID  
Sent By dpalmer Date 2003-02-18 Time 14:45 Rev Time 0.00
Received By dpalmer Date 2003-02-18 Time 14:45 Sent To B
Notes
2003-02-18 00:00:00TO HHP DESK, SPEED DOWELS.

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2003-02-18 Cont ID  
Sent By dpalmer Date 2003-02-18 Time 14:45 Rev Time 0.00
Received By dpalmer Date 2003-02-18 Time 14:45 Sent To B
Notes
2003-02-18 00:00:00TO HHP SLAB SAW JOINTS.

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2003-02-18 Cont ID  
Sent By dpalmer Date 2003-02-18 Time 14:32 Rev Time 0.00
Received By dpalmer Date 2003-02-18 Time 14:32 Sent To B
Notes
2003-02-18 00:00:00TO HHP'S DESK. TILT UP DETAIL.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-02-18 Cont ID  
Sent By dpalmer Date 2003-02-18 Time 14:24 Rev Time 0.00
Received By dpalmer Date 2003-02-18 Time 14:24 Sent To B
Notes
2003-02-18 00:00:00TO HHP'S DESK, ANCHOR BOLTS.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-01-27 Cont ID  
Sent By dpalmer Date 2003-01-27 Time 10:45 Rev Time 0.00
Received By dpalmer Date 2003-01-27 Time 10:44 Sent To B
Notes
2003-01-27 00:00:00SUBMITTAL TO DON NEELY`S DESK.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-01-17 Cont ID  
Sent By btrobaug Date 2003-01-17 Time 15:41 Rev Time 0.00
Received By btrobaug Date 2003-01-17 Time 15:41 Sent To B
Notes
2003-01-17 00:00:00TO HHP./WRT

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-12-24 Cont ID  
Sent By dpalmer Date 2002-12-24 Time 10:45 Rev Time 0.00
Received By dpalmer Date 2002-12-24 Time 10:45 Sent To B
Notes
2002-12-24 00:00:00TO HHP DESK. SUBMITTAL.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2003-08-27 Cont ID  
Sent By pkrauss Date 2003-08-27 Time 12:54 Rev Time 0.40
Received By pkrauss Date 2003-08-27 Time 12:54 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2003-04-08 Cont ID  
Sent By csiegber Date 2003-08-25 Time 14:43 Rev Time 0.45
Received By pkrauss Date 2003-04-08 Time 09:44 Sent To  
Notes
2003-04-08 00:00:00SUBMITTAL ON THE ROOF CURBS

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2002-06-05 Cont ID  
Sent By pkrauss Date 2002-06-05 Time 09:32 Rev Time 0.50
Received By pkrauss Date 2002-06-05 Time 08:52 Sent To  
Notes
2002-06-05 00:00:00APPROVED - HVAC ONLY
  
 REFRIGERATION ON SEPARATE PERMIT.
 PLEASE PROVIDE PLANS AND SHOW
 COMPLIANCE WITH CHAPTER 11 OF THE 1997
 SMC & ASHRAE 15-199.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-03-26 Cont ID  
Sent By pkrauss Date 2002-03-26 Time 08:55 Rev Time 1.00
Received By pkrauss Date 2002-03-26 Time 07:52 Sent To  
Notes
2002-03-26 00:00:00 
 REVIEW FOR THE HVAC ONLY.SEPARATE
 PERMIT FOR THE REFRIGERATION & TANK.
  
 REFRIGERATION REQUIREMENTS:
  
 PROVIDE LOCATION OF ALL EQUIPMENT AS
 SHOWN ON R-1.
  
 PROVIDE DETAIL OF STANDS FOR THE
 CONDENSER UNITS.
  
 SHOW COMPLIANCE WITH CHAPTER 11 OF
 THE 1997 SMC
 - INDICATE CLASSIFICATION
 - COMPLY WITH CLASSIFICATION REQUIREMENT
 AS PER TABLE 1104A & TYPE OF SYSTEM
 PER 1103.
 - SHOW ALL CALCULATIONS FOR VENTILATION
 NORMAL & EMERGENCY.
 - INDICATE LOCATIONS FOR LEAK DETECTORS
 AND BREATHING APPARATUS.
  
 WILL THERE BE A GENERATOR FOR EMERGENCY
 POWER?
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-01-12 Cont ID  
Sent By pkrauss Date 2002-01-12 Time 08:55 Rev Time 4.00
Received By pkrauss Date 2002-01-12 Time 08:55 Sent To  
Notes
2002-01-12 00:00:00 
 PHASE I
  
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 FOR REVIEW:
  
 1.OUTSIDE AIR CALCULATIONS AS PER
 ASHRAE 62-89. (FOR ALL AREAS)
  
 2.AIR BALANCE SCHEDULE SHOWING
 COMPLIANCE WITH 1997 SMC 501.2.
  
 3.PLAN SHEET M4.1 AC 2 IS SERVICING
 THE SHIPPING OFFICE.AC 1 IS
 SERVING THE RECEIVING OFFICE.THE
 SCHEDULE ON M-6.1 EQUIPMENT SCHEDULE
 DOES NOT COINCIDE WITH FLOOR PLAN.
  
 PLEASE INDICATE DUCT SMOKE DETECTORS
 ON PLAN SHOWING COMPLIANCE WITH 1997
 SMC 406.1
  
 5.CLARIFY RGF- SCHEDULE REFLECTS RGF
 AS BEING A RETURN GRILL WITH FIRE
 DAMPER.PLAN SHEET M-4.1 INDICATES
 2 TOTAL RGF ONE IN RECEIVING & 1 IN
 SHIPPING.ARE THEY FIRE DAMPERS OR
 BACKDRAFT DAMPERS?INDICATE ANY &
 ALL FIRE DAMPERS ON PLAN AS PER 1997
 SMC 610.6.
  
 6.PROVIDE INFORMATION ON THE ENGINE
 ROOM.INDICATE VENTILATION REQUIRE-
 MENTS FOR NORMAL OPERATION AS WELL
 AS EMERGENCY OPERATIONS.PROVIDE
 SEQUENCE OF OPERATION.
  
 ADDITIONAL PERMITS REQUIRED FOR ANY
 HOOD, FIRE SUPRESSION, FUEL AND WALK-IN
 COOLERS/FREEZERS.PLEASE PROVIDE PLAN
 AND MANUFACTURER SUBMITTAL DATA WITH
 PERMIT APPLICATION.
  
 PLEASE NOTE REFRIGERATION SHALL COMPLY
 WITH 1997 SMC CHAPTER 11 AND ASHRAE 15.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 3 Status P Date 2002-06-05 Cont ID  
Sent By kstevens Date 2002-06-05 Time 17:13 Rev Time 0.00
Received By kstevens Date 2002-06-05 Time 17:13 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2002-03-22 Cont ID  
Sent By kstevens Date 2002-03-22 Time 14:44 Rev Time 4.00
Received By kstevens Date 2002-03-22 Time 14:44 Sent To  
Notes
2002-03-22 00:00:00DENIED
 REFERENCE: SPC-94 - SGC-97 - FACBC-97
  
 1) SHTS A5.01/A5.02/M3.1/M3.2 FROM PRE-
 VIOUS REVIEW, PLEASE SHOW CLEAR FLOOR
 SPACE FOR ALL HDCP FIXTURES. LAV SHALL
 BE CENTERED ON 30X48 CLEAR FLOOR SPACE.
 2) SHTS A5.01/A5.02/M3.1/M3.2 DOOR SHALL
 NOT SWING INTO CLEAR FLOOR SPACE OF HDCP
 FIXTURES. FACBC SEC 4.17.5
 3) SHT M2.2 GAS PERMIT APPLICATION RE-
 QUIREMENTS #2, WELDERS CERTIFICATION AND
 WELDING PROCEDURE REQUIRED BEFORE GAS
 PERMIT ISSUED.
 4) SHT M2.2 GAS PERMIT APPLICATION RE-
 QUIREMENTS #7 GAS PRESSURE NOT DELIVERED
 AT 7" OF WATER COLUUM BUT 12" TO 14".
 PLEASE CHECK WITH GAS PROVIDER.
 5) SHT M2.2 GAS PERMIT APPLICATION RE-
 QUIREMENTS #9 UNABLE TO FIND SHTS SM-1
 AND SKM-4 AND MANUFACTURE CUT SHEETS.
 THEY WERE NOT ON BLUE PRINTS, VENDOR EQ-
 UIPMENT MANUAL OR PROJECT MANUAL. PLEASE
 INDICATE WHERE I MIGHT FIND THESE SHEETS
 6) SHT M2.2 COLS B/15-17-19-21. AIR GAP-
 1 FITTINGS ARE FOR CONDENSATE LINES.
 CONDENSATE SHALL NOT DRAIN INTO WASTE
 AS SHOWN ON CIVIL PLANS. ALL CONDENSATE
 SHALL DRAIN TO STORM OUTSIDE BLDG.
 PLEASE GIVE DETAIL OF ALL CONDENSATE
 TYING INTO STORM WITH A RELIEF VENT ON
 CONDENSATE AS IT EXITS BLDG.
 7) SHTS M3.1/M3.2/M3.3 FROM PREVIOUS RE-
 VIEW, PLEASE SHOW DETAIL OF CONDENSATE
 TYING INTO STORM OUTSIDE BLDG. WITH RE-
 LIEF VENT ON CONDENSATE AS IT EXITS BLDG
 8) SHT M3.3 OVER FLOW FROM REFRIGATION
 EQUIPMENT ON ROOF AS INDICATED IN RES-
 PONCE SHALL DRAIN TO STORM NOT SANITARY
 AS INDICATED. PLEASE SHOW OVERFLOW TYING
 INTO STORM OUTSIDE BLDG.
 9) PER SPC TABLE 407 AN EMERGENCY SHOWER
 IS REQUIRED. THIS IS A NEW COMMENT.
 10) WORK SHEET FROM RODNEY COMPO ENVIRON
 MENTAL COMPLIANCE STILL REQUIRED FOR
 SAND INTERCEP. & DILUTION TANK BEFORE
 ISSUANCE OF PERMIT.
  
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-01-24 Cont ID  
Sent By kstevens Date 2002-01-24 Time 19:31 Rev Time 5.50
Received By kstevens Date 2002-01-23 Time 19:52 Sent To  
Notes
2002-01-24 00:00:00DENIED
 REFERENCE: SPC-94-FACBC-97
  
 1) SHT G1.01 SINGLE ACCOMMODATION TOILET
 FACILITIES. #'7 & 8, CENTER LINE OF W/C
 TO BE 18" OFF WALL NOT 15" TO 19" OFF
 GRAB BAR. FACBC FIG. 28.
 2) SHT IR 7 OF 7. SEPARATE IRRIGATION
 PERMIT REQUIRED. BACKFLOW INSTALLED BY
 PLUMBING CONTRACTOR REQUIRED.
 3) SHT A1.05. WATER HEATER REQUIRES A
 PERMINATE SHIPS LADDER TO MAKE IT READ-
 ILY ACCESSIBLE. SPC SEC 501.7
 4) SHTS A5.01/A5.02/M3.1/M3.2. STALL FOR
 HANDICAP SHALL HAVE A LAV INSIDE STALL.
 FACBC FIG 30(E). SHOW CLEAR FLOOR SPACE
 FOR ALL HDCP FIXTURES.
 5) SHT M2.2 SEPARATE GAS PERMIT REQUIRED
 SEE ATTACHED SHEET FOR GAS PERMIT APPLI-
 CATION REQUIREMENTS. PLEASE PROVIDE ALL
 INFORMATION FOR PLAN REVIEW.
 6) SHT M2.2 COLS. B/15-17-19-21, UNABLE
 TO IDENTIFY AG-1. PLEASE CLAIRFY DESIGN-
 ATION FOR.
 7) SHT M3.1 SHIPPING EMPLOYEES REST ROOM
 PLUMBING PLAN, GAS OVERHEAD SHOWS 3/4",
 BUT DROP TO HEATER SHOWS 1" PLEASE
 CLAIRFY.
 8) SHTS M3.1/M3.2/M3.3 ALL CONDENSATE
 SHALL BE PIPED TO DRYWELL OR STORM OUT-
 SIDE OF BLDG NOT INTO SANITARY AS SHOWN.
 A RELIEF VENT 6" ABOVE GRADE IS REQUIRED
 9) SHT M3.1 SHIPPING EMPLOYEES REST ROOM
 WASTE AND VENT PLAN, ALL FLOOR DRAINS
 SHALL BE A MINIMUM OF 3" PER SPC SEC
 409.4.1.1 (SEE SHTS M6.1 & M6.3 [D-1] &
 [D-3] ALSO). THIS IS TYPICAL FOR RECIEV-
 ING EMPLOYEES REST ROOM ALSO.
 10) SHT M2.2 SAND INTERCEPTOR, AND SHT
 M3.3 TRENCH DRAIN FOR ENGINE ROOM AND
 BATTERY CHARGING AREA. PLEASE CONTACT
 RODNEY COMPO, (561) 837-4074, ENVIRON-
 MENTAL COMPLIANCE AT THE REGIONAL SEWER
 AND WASTE WATER TREATMENT PLAND FOR SIZ-
 ING OF THE SAND INTERCEPTOR AND TO SEE
 IF A DILLUTION TANK IS REQUIRED FOR
 POSSIBLE ACID SPILL FROM BATTERIES.
 11) SHT M3.3 ENGINE ROOM, BACKFLOW TO BE
 MAXIMUM OF 4' OFF THE FLOOR FOR SERVICE.
 12) SHT M3.3 ENGINE ROOM PLUMBING PLAN,
 PLEASE INDICATE WHAT IS BEING DRAINED IN
 THE -W- LINE FROM ROOM OVERHEAD.
 13) DRINKING FOUNTAINS SHALL COMPLY WITH
 FACBC SEC 4.15 AND SEC 4.1.3(10) FOR
 THOSE WHO HAVE DIFFICULTY BENDING OR
 STOOPING.
 14) PER SPC TABLE 407 PLEASE SUBMIT
 OCCUPANT CONTENT PER SHIFT, SUBSTANTIAT-
 ED BY OWNER, FOR DRY/COLD STORAGE COMBO.
 ALSO SEE SEC 407.3.2
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status P Date 2002-01-02 Cont ID  
Sent By sgraham Date 2002-01-02 Time 09:40 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
2002-01-02 00:00:00HANDI-CAP SPACES MUST BE DEIGNATED ON
 THE SITE PLAN AS NEAR AS POSSIBLE TO THE
 BUILDING