Plan Review Details - Permit 01121475
Plan Review Stops For Permit 01121475
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2002-05-24 Cont ID  
Sent By hpiskura Date 2002-05-24 Time 13:20 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2002-05-24 00:00:00REVISION #4 DATED 4/26/02

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2002-04-09 Cont ID  
Sent By rmcdouga Date 2002-04-09 Time 09:27 Rev Time 3.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-04-09 00:00:00************BUILDING PROVISO************
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) SUBMIT SHOP DRAWINGS FOR THE
 GUARDRAILS AT THE SECOND FLOOR COVERED
 PORCHES FOR APPROVAL PRIOR TO
 INSTALLATION.
  
 4) PROVIDE (2) PRODUCT APPROVALS, KEY
 PLANS AND INSTALLATION SCHEDULES
 INDICATING THE SPECIFIC TYPES OF ANCHORS
 TO BE USED FOR STORM PANELS, UNDER A
 SEPARATE PERMIT. IMPACT RESISTANT
 GLAZING OR PERMANENTLY AFFIXED
 PROTECTIVE DEVICES ARE REQUIRED ABOVE
 THE FIRST LEVEL. (PERMANENTLY AFFIXED
 PROTECTIVE DEVICES REQUIRE THE WRITTEN
 APPROVAL OF THE BUILDING OFFICIAL.)

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2002-03-22 Cont ID  
Sent By rmcdouga Date 2002-03-22 Time 08:56 Rev Time 4.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-03-22 00:00:00*************BUILDING UNSAT*************
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) THE DOORS TO THE DEN ON THE ALAMANDA
 MODEL ARE REQUIRED TO HAVE BOTH LEAFS
 ACTIVE TO COMPLY WITH FAIR HOUSING.
  
 4) THE FIRE RATED DOORS BETWEEN THE
 UNITS AND THE GARAGES ARE REQUIRED TO
 HAVE APPROVED CLOSERS PER 97 SBC SECT.
 705.1.3.5.
  
 5)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - DOUBLE OUTSWING FRENCH DOORS WITH
 SIDELITES ON EACH SIDE (SALES OFFICE)
 - ARCHED WINDOWS AS SHOWN ON PLANS (THE
 PRODUCT APPROVAL SUBMITTED IS FOR CIRCLE
 TOP WINDOWS,THIS IS NOT THE WINDOWS THAT
 ARE INDICATED ON THE PLANS)
  
 6) THE SUBMITTAL FOR THE BALCONY RAIL
 DETAIL IS FOR A SCREEN ROOM. PLEASE
 SUBMIT SHOP DRAWINGS FOR THE GUARDRAILS
 AT THE 2ND FLOOR COVERED PORCHES PRIOR
 TO INSTALLING.
  
 7) PROVIDE A KEY PLAN AND INSTALLATION
 SCHEDULE FOR THE STORM PANELS OR SUPPLY
 THE REQUIRED INFORMATION UNDER A
 SEPARATE PERMIT AT A LATER DATE. THE
 MARKING OF THE OPENINGS ON THE PLANS IS
 NOT ACCEPTABLE. A SEPARATE KEY PLAN IS
 WHICH IS CLEAR AND READABLE IS REQUIRED.
 REMOVABLE STORM PANELS CAN NOT BE USED
 ABOVE THE GROUND FLOOR. IMPACT RESISTANT
 GLAZING OR PERMANENTLY AFFIXED
 PROTECTIVE DEVICES SHALL BE INSTALLED.
 SEE ATTACHED.
  
 8) PROVIDE WINDOW, DOOR AND GARAGE DOOR
 BUCK FASTENING DETAILS.
  
 9) DETAILS 13 AND 23 ON A-11 ARE
 MISLABELED AS A-17. PLEASE CORRECT.
  
 10) DETAIL 23 ON A-11 MUST INDICATE THAT
 ONE HOUR TENANT SEPARATION IS MAINTAINED
 TO THE UNDERSIDE OF THE ROOF SHEATHING.
  
 11) THE 9.5" STAIR TREAD DIMENSION ON
 A-7 SHOULD BE EXCLUSIVE OF THE NOSING.
 HOWEVER IT APPEARS TO INCLUDE THE
 NOSING AS DRAWN. SEE 97 SBC SECT.
 1007.3.1 AND 1007.3.2.
  
 12)THE BUILDING OFFICIAL WAS UNAVAILABLE
 AT TIME OF THIS REVIEW. IN ORDER TO
 EXPEDIATE THE REVIEW PROCESS I WILL
 REVIEW A COPY OF THE LETTER REQUESTING A
 TEMPORARY SALES OFFICE WITH HIM WHEN HE
 RETURNS. THIS WILL ALLOW YOU TO ADDRESS
 THE OTHER ISSUES IN THE INTERIM.
  
 TRUSSES
  
 1) THE PA23 CONNECTOR LISTED IN DETAIL
 19 ON A-11 FOR TRUSS GT2, IS A PURLIN
 ANCHOR AND IS NOT DESIGNED TO BE USED AS
 A TRUSS ANCHOR. PLEASE CORRECT.
  
 2) THERE IS NO CONNECTOR OR CONNECTION
 DETAIL INDICATED FOR TRUSS GT1. DETAIL
 32 ON A-11 INDICATES THE ATTACHMENT OF
 THE WOOD FRAME WALL TO THE MASONRY.
  
 3) THE TRUSS DRAWINGS, LETTERS FROM THE
 TRUSS ENGINEER AND DETAILS REQUIRE THE
 TRUSS ENGINEERS SIGNATURE, EMBOSSED SEAL
 AND THE DATE ON EACH SHEET.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-02-07 Cont ID  
Sent By rmcdouga Date 2002-02-07 Time 14:44 Rev Time 12.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-02-07 00:00:00*************BUILDING UNSAT*************
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) BUILDINGS, WHICH THE PERMITS ARE
 APPLIED FOR AFTER MARCH 1,2002, ARE
 REQUIRED TO BE DESIGNED TO COMPLY WITH
 THE 2001 FLORIDA BUILDING CODE. THIS IS
 REQUIRE TO BE LISTED ON THE PLANS.
  
 4) TEMPORARY SALES OFFICE IN GARAGE OF
 MODEL MUST BE APPROVED BY THE PLANNING
 AND ZONING DEPT. AND THE BUILDING
 OFFICIAL. SALES OFFICE MUST MEET
 ACCESSIBILITY REQUIREMENTS, INCLUDING
 ACCESSIBLE TOILET FACILITIES. A
 CONDITIONAL CERTIFICATE OF OCCUPANCY
 WILL BE REQUIRED BEFORE THE OFFICE CAN
 BE OPENED. THE FINAL C.O. FOR THE
 RESIDENCE WILL BE ISSUED AFTER THE
 TEMPORARY COMPONENTS HAVE BEEN REMOVED
 AND THE PERMANENT COMPONENTS ARE
 INSTALLED. YOU MUST SUBMIT A LETTER FROM
 ONE OF THE PRINCIPLES WITH THE COMPANY
 (NOTARIZED OR WITH CORPORATE SEAL) TO
 THE BUILDING OFFICIAL WITH YOUR REQUEST,
 INDICATING THE LENGTH OF TIME THIS
 CONDITION WILL EXIST, THAT THE TEMPORARY
 WALLS,ETC. WILL BE REMOVED AND THE
 GARAGE DOORS,ETC. WILL BE INSTALLED.
 TEMPORARY EXTERIOR WALLS AND DOORS MUST
 MEET WINDLOAD REQUIREMENTS AND MISSLE
 IMPACT PROTECTION IS REQUIRED.
  
 5) THE IMPORTANCE FACTOR ON SHEET C-1 IS
 INCORRECT.
  
 6) DETAIL 2B ON SHEET A-2 REFERENCED FOR
 F-10 ON THE FOOTING SCHEDULE DOES NOT
 SHOW THE SHOWER RECESS.
  
 7) THE 97 SBC CLASSIFIES DOORS AS 3-HOUR
 1-1/2-HOUR, 1-HOUR, 3/4-HOUR OR
 20-MINUTES, NOT BY LETTER LABELS.
 INDICATE ON PLANS THE ONE YOU ARE
 SPECIFYING FOR RATED DOOR AT GARAGE.
  
 8) THE BEDROOM WINDOWS MUST COMPLY WITH
 SECTION 1005.4 FOR EMERGENCY EGRESS.
 PLEASE PROVIDE THE CLEAR OPENING SIZES
 FOR THE 8'X 5' H.S. AND THE SH 34+4
 WINDOWS.
  
 9) PROVIDE DETAILS FOR THE GUARDRAIL AT
 THE 2ND FLOOR FOYER.
  
 10) THE SOIL REPORT RECOMMENDS THE
 EXTERIOR FOUNDATIONS BEAR 18" BELOW
 ADJACENT OUTSIDE FINAL GRADE. THE PLANS
 INDICATE 16" FOOTINGS.
  
 11) THE EXTERIOR WALL SECTIONS ON A-8
 INDICATE 6" MIN. ABOVE GRADE AND THE
 97 SBC REQUIRES BOTTOM OF FOOTINGS TO
 BE A MINIMUM OF 12" BELOW FINISH GRADE.
 THIS CAN NOT BE ACCOMPLISHED WITH 16"
 FOOTERS.
  
 12) THE ORNAMENTAL PATTERNS ON THE
 GUARDRAILS AT THE VERANDAS ARE REQUIRED
 TO REJECT THE PASSAGE OF A 4" DIAMETER
 SPHERE THROUGH ANY OPENING AND THE
 BOTTOM RAIL SHALL REJECT THE PASSAGE OF
 A 2" DIA. SPHERE PER 97 SBC 1015.3.
 INDICATE THE METHODS THAT WILL BE USED
 TO ATTACH THE GUARDRAILS TO THE
 STRUCTURE.
  
 13) DETAIL 29 ON A-11 APPEARS TO BE IN
 ERROR. SHEET A-9 INDICATES A MASONRY
 COLUMN AT THIS LOCATION. PLEASE CORRECT.
  
 14) DETAILS 16 & 17 ON A-11 ARE MARKED
 INCORRECTLY AS A-16.
  
 15) INDICATE THE RISER AND TREAD
 DIMENSIONS OF THE STAIRS ON THE PLANS.
  
 16) THE DESIGN INFORMATION THAT IS GIVEN
 ON THE DESIGN CERTIFICATION COMPLIANCE
 FORM IS REQUIRED TO BE ON THE PLANS. THE
 SEPARATE FORM WILL NO LONGER BE ACCEPTED
  
 17) INDICATE THE POSITIVE AND NEGATIVE
 WIND PRESSURES FOR EXTERIOR WINDOWS AND
 DOORS ON THE PLANS.
  
 18) THE ELEVATORS ARE REQUIRED TO COMPLY
 WITH ANSI/ASME A17.1 AND ANSI A117.1.
  
 19) PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - SINGLE HUNG WINDOWS (ONES SUBMITTED
 WERE EXPIRED)
 - HORIZONTAL SLIDING WINDOWS
 - ARCHED FIXED GLASS WINDOWS
 - RECTANGULAR FIXED GLASS WINDOWS
 - FRENCH DOORS WITH & WITHOUT SIDELITES
 (SALES OFFICE)
  
 20) THE 9606C SBCCI EVALUATION REPORT
 (PRODUCT APPROVAL) TO ACCOMPANY THE
 DRAWING FOR THE CLOPAY GARAGE DOOR.
  
 21) THE SITE SPECIFIC PRODUCT APPROVALS
 FOR THE FRONT DOOR ARE REQUIRED TO BE
 ORIGINALS; SIGNED, SEALED AND DATED BY
 THE ENGINEER FOR THE PRODUCT AND BY THE
 DESIGNER OF THE STRUCTURE INTO WHICH IT
 WILL BE INSTALLED.
  
 22) PROVIDE KEY PLAN AND INSTALLATION
 SCHEDULE FOR STORM PANELS. INDICATE ON
 THE DRAWINGS THE MOUNTING ANCHORS THAT
 WILL BE USED.
  
 23)SHOW COMPLIANCE WITH FAIR HOUSING ACT
 ALL BUILDING ENTRANCES ARE REQUIRED TO
 BE ACCESSIBLE AND BE ON AN ACCESSIBLE
 ROUTE.
 - THE PRIMARY ENTRANCE DOOR MUST
 MEET THE REQUIREMENTS FOR ACCESSIBLE
 DOORS (32" CLEAR OPENING,LOW OR NO
 THRESHOLD 3/4"MAX.,HARDWARE COMPLYING
 WITH ANSI 4.13.9, ETC.)
 - DOORS WITHIN UNIT MUST BE USEABLE
 DOORS. MUST PROVIDE AT LEAST A 31-5/8"
 CLEAR OPENING.
 - INDICATE THE SIZE OF MASTER BATHROOM
 DOOR ON PLANS.
 - THE WALK-IN CLOSET IN BEDROOM #3 OF
 UNIT "D" REQUIRES A DOOR WITH A 32"
 NOMINAL OPENING (2'10" DOOR).
 - BOTH LEAFS OF THE DOUBLE DOOR AT DEN
 IN UNIT "D" ARE REQUIRED TO BE ACTIVE.
 - THE WALK-IN CLOSET IN BEDROOM #3 OF
 UNIT "C" REQUIRES A 2'10" DOOR.
 - THE STEP UP SHOWN AT THE PRIMARY ENTRY
 DOOR AND AT GARAGE ON SECTION A-A AND
 B-B ARE NOT PERMITTED.
 - LIGHT SWITCHES, ELECTRICAL OUTLETS,
 THERMOSTATS AND CONTROLS SHALL BE IN
 ACCESSIBLE LOCATIONS.
 - INDICATE MINIMUM CLEAR FLOOR SPACES AT
 FIXTURES AND APPLIANCES IN THE KITCHEN.
 - IN UNITS "A" AND "D", 40" CLEARANCE
 MUST BE MAINTAINED BETWEEN THE FACE OF
 THE KITCHEN ISLAND AND ALL OPPOSING
 FEATURES.
 - THE FAIR HOUSING ACT REQUIRES THE
 BATHROOMS TO BE DESIGNED TO COMPLY
 WITH SPECIFICATION A OR B BATHROOMS.
 INDICATE WHICH ONE WILL BE USED AND SHOW
 COMPLIANCE WITH DESIGN METHOD SELECTED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2002-09-30 Cont ID  
Sent By btrobaug Date 2002-09-30 Time 17:09 Rev Time 0.50
Received By btrobaug Date 2002-09-27 Time 06:43 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2002-07-31 Cont ID  
Sent By btrobaug Date 2002-07-31 Time 17:22 Rev Time 0.00
Received By btrobaug Date 2002-07-31 Time 16:41 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2002-05-24 Cont ID  
Sent By dpalmer Date 2002-05-24 Time 06:47 Rev Time 0.00
Received By dpalmer Date 2002-05-24 Time 06:47 Sent To  
Notes
2002-05-24 00:00:00****************** UNSAT *************
  
 1)NOTE: PLEASE NOTE THAT RISER DIAGRAM
 SHOWS MAIN DISC`S AND NOT SHOWN ON PLANS
 PLEASE CLARIFY.
  
 2)NOTE: PLEASE CLARIFY EQUIPMENT GROUND
 BETWEEN MAIN AND PANEL.250-122
  
 3)NOTE: PLEASE NOTE AIC CALCS MENTION
 RATINGS OF EACH PANEL AT 10,000. IS THIS
 THE SAME FOR MAIN DISC`S SHOWN?
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-04-11 Cont ID  
Sent By btrobaug Date 2002-04-11 Time 12:41 Rev Time 0.00
Received By btrobaug Date 2002-03-15 Time 12:42 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-02-04 Cont ID  
Sent By btrobaug Date 2002-02-04 Time 18:18 Rev Time 0.00
Received By btrobaug Date 2002-02-05 Time 09:42 Sent To  
Notes
2002-02-04 00:00:00******************UNSAT!****************
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION AND RESUBMIT:
  
 1) A.I.C. RATING AT FIRST MEANS OF
 DISCONNECT,ALL UNITS.
  
 2) "A" & "B" UNITS CONFORM TO 230-3.
  
 3) BATH ROOMS TO COMPLY WITH
 210-52D.INCLUDE SAME IN PANEL SCHEDULES
 AND LOAD CALCULATIONS.
  
 4) GROUND LEVEL UNITS COMPLY WITH
 210-52E.
  
 5) CONDENSING UNITS GFCI,210-63 NEC &
 309.2.
 6) UNIT "D" BED ROOMS 2&3 AND UNIT"C"
 BED ROOM #3 TO COMPLY WITH NFPA-72
 2-2.1.1.1.
  
 7) ALL WIRING TO CONFORM TO THE FAIR
 HOUSING ACT,CHAPTER 5.24 CFR 100-205.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 (561) 659-8096
 EXT.8392

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2002-02-08 Cont ID  
Sent By rmcdouga Date 2002-02-08 Time 13:58 Rev Time 0.00
Received By rmcdouga Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-03-20 Cont ID  
Sent By mcarsill Date 2002-03-20 Time 11:10 Rev Time 0.00
Received By mcarsill Date 2002-03-20 Time 11:10 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-02-06 Cont ID  
Sent By mcarsill Date 2002-02-06 Time 08:12 Rev Time 0.00
Received By mcarsill Date 2002-02-06 Time 08:11 Sent To  
Notes
2002-02-06 00:00:001) BUILDING ADDRESSES REQUIRED.
 2) WET FIRE HYDRANTS ARE REQUIRED PRIOR
 TO,DURING AND AFTER CONSTRUCTION.
 3) PORTABLE FIRE EXTINGUISHERS REQUIRED.
 4) ELECTRIC POWERED SMOKE DETECTORS
 ARE REQUIRED. IT APPEARS THAT REQUIRED
 SMOKE DETECTORS WITHIN THE BEDROOMS HAVE
 BEEN OMITTED FROM THE PLANS.
 5) PLEASE IDENTIFY ALL EGRESS WINDOWS
 ON THE PLANS AND MAXIMUM SILL HEIGHTS.
 6) PLEASE INDENTIFY INTERIOR FINISH
 CLASSIFICATIONS FOR WALLS AND CEILINGS.
 7) THE C LABELED FIRE DOORS ARE
 REQUIRED TO BE EQUIPPED WITH
 SELF-CLOSING DEVICES.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-04-16 Cont ID  
Sent By pkrauss Date 2002-04-16 Time 09:35 Rev Time 0.50
Received By pkrauss Date 2002-04-16 Time 09:35 Sent To  
Notes
2002-04-16 00:00:00PROVISO:MECHANICAL PERMIT 02040996
  
 CONTRACTOR (E.N.SUTTIN) TO SUBMIT
 MANUFACTURER SUBMITTAL FOR DRYERS.
 (G.E. LARGE CAPACITY DRYERS TO BE USED
 - SCHEDULE ON PLAN SHEET A3 DETAIL 3).
 AC NOTES ON PLAN SHEET A3.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2002-02-05 Cont ID  
Sent By pkrauss Date 2002-02-05 Time 07:23 Rev Time 1.20
Received By pkrauss Date 2002-02-05 Time 07:23 Sent To  
Notes
2002-02-05 00:00:00 
 NO MECHANICAL PLANS SUBMITTED FOR
 REVIEW.PLEASE PROVIDE THE FOLLOWING
 INFORMATION WITH MECHANICAL PLANS AND
 PERMIT.
  
  
 1.DUCT LAYOUT - SIZE, MATERIAL, R -
 VALUE, AND CFM DISTRIBUTION.
  
 2.PROVIDE GRILLE SIZE.
  
 3.HVAC EQUIPMENT SCHEDULE - MAKE,
 MODEL, BTU, KW HEAT STRIP AND SEER
 OF THE CONDENSER.
  
 4.INDICATE SIZE OF THE REFRIGERATION
 AND CONDENSATE LINES.PROVIDE
 PIPING LAYOUT FROM AHU TO CONDENSER.
  
 5.CONDENSATE FROM UNITS LARGER THAN
 3 TON SHALL TERMINATE INTO AN
 APPROVED DRY WELL OR STORM DRAIN.
  
 6.PROVIDE DETAIL OF DRYER EXHAUST.
 INDICATE TERMINATION (ROOF OR WALL),
 ARE DUCTS IN A FIRE RATED CHASE?
 PLEASE NOTE AS PER 1997 SMC 509.3,
 MINIMUM SIZE 4" WITH A MAXIMUM
 LENGTH OF 25' (5' REDUCTION FOR EACH
 90 DEGREE BEND & 2 1/2 REDUCTION FOR
 EACH 45 DEGREE BEND).WALL OR ROOF
 CAP SHALL BE NON SCREENED WITH A
 BACKDRAFT DAMPER.
  
 7.BATHROOM EXHAUST - INDICATE DUCT
 SIZE, MATERIAL, AND TERMINATION.
  
 ALL ENVIRONMENTAL CONTROLS SHALL COMPLY
 WITH THE FAIR HOUSING ACT REGULATIONS,
 CHAPTER 5 FOR ACCESSIBLE LOCATION AND
 HEIGHT REQUIRMENTS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 4 Status P Date 2002-06-03 Cont ID  
Sent By kstevens Date 2002-06-03 Time 18:39 Rev Time 0.00
Received By kstevens Date 2002-06-03 Time 18:39 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2002-04-17 Cont ID  
Sent By kstevens Date 2002-04-17 Time 10:46 Rev Time 0.00
Received By kstevens Date 2002-04-17 Time 10:46 Sent To  
Notes
2002-04-17 00:00:00PASSED/PROVISO
  
 REVISION REQUIRED BEFORE INSPECTIONS

Review Stop P PLUMBING
Rev No 2 Status F Date 2002-03-15 Cont ID  
Sent By kstevens Date 2002-03-15 Time 10:03 Rev Time 0.50
Received By kstevens Date 2002-03-15 Time 10:03 Sent To  
Notes
2002-03-15 00:00:00DENIED
 REFERENCE: SPC-94 - FHA AMEND-98 DESIGN
 MANUAL
  
 SEE REVIEW COMMENTS FROM PERMIT 01121474
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-02-05 Cont ID  
Sent By kstevens Date 2002-02-05 Time 15:16 Rev Time 0.00
Received By kstevens Date 2002-02-05 Time 15:15 Sent To  
Notes
2002-02-05 00:00:00DENIED
 REFERENCE: SPC-94 - FHA AMEND-98 DESIGN
 MANUAL
  
 1) SEE REVIEW NOTES FROM PERMIT 01121474
  
  
 REVIEW BY KEN STEVENS
 (561) 549-8096 EXT 8377

Review Stop R ROOF PLAN REVIEW
Rev No 4 Status F Date 2002-07-31 Cont ID  
Sent By rmcdouga Date 2002-07-31 Time 16:50 Rev Time 1.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-07-31 00:00:00DENIED
 SHOP DRAWINGS FOR SECOND FLOOR COVERED
 PORCH GUARDRAILS
 SAME COMMENTS AS PERMIT # 01121474

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status F Date 2002-06-12 Cont ID  
Sent By rmcdouga Date 2002-06-12 Time 10:37 Rev Time 1.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-06-12 00:00:00SHOP DRAWINGS FOR THE SECOND FLOOR
 GUARDRAILS ARE DENIED. ADDITIONAL
 INFORMATION IS REQUIRED ON THE DRAWINGS.
 SEE COMMENTS FOR PERMIT # 01121474 R1.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2002-04-17 Cont ID  
Sent By aneil Date 2002-04-17 Time 15:44 Rev Time 0.00
Received By aneil Date   Time   Sent To  
Notes
2002-04-17 00:00:00OK PER R. MCDOUGAL

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2002-02-08 Cont ID  
Sent By rmcdouga Date 2002-02-08 Time 11:29 Rev Time 2.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-02-08 00:00:00TRUSSES DENIED
  
 LOWER ROOF
  
 1) THE TRUSS LAYOUT IS REQUIRED TO BE
 REVIEWED AND APPROVED BY THE DESIGNER OF
 RECORD FOR THE STRUCTURE. THIS MUST BE
 NOTED ON THE LAYOUT IN ADDITION TO THE
 ENGINEER'S SEAL, SIGNATURE AND DATE.
  
 2) TRUSS H7L; UPLIFT EXCEEDS CONNECTOR
 CAPACITY AT BEARING POINT K.
  
 3) TRUSS M3L; UPLIFT EXCEEDS CONNECTOR
 AT B.PT. A.
  
 4) TRUSS M1L; UPLIFT EXCEEDS CONNECTOR
 AT B.PT. A.
  
 5) TRUSS M2L; UPLIFT EXCEEDS CONNECTOR
 AT B.PT. A.
  
 UPPER ROOF
  
 6) THE AMOUNT OF TRUSS ANCHOR STRAPS
 LISTED AT SEVERAL LOCATIONS ON THE ROOF
 FRAMING PLAN ARE NOT ACCEPTABLE WITHOUT
 A LETTER FROM THE CONNECTOR MANUFACTURER
 'S ENGINEER STATING THE LOAD VALUES FOR
 THESE CONNECTORS WHEN MULTIPLE STRAPS
 ARE USED IN SUCH CLOSE PROXIMITY TO
 EACH OTHER. (4,5 AND 7 TAPR STRAPS AT
 ONE LOCATION)
  
 7) BEARING POINT D FOR TRUSSES SH11 AND
 SH11A IS GIVEN AS A STEEL COLUMN AT
 DETAIL 17 ON A-11, BUT (4) TC-8
 CONNECTORS ARE INDICATED ON A-13. PLEASE
 CLARIFY.
  
 8) NO CONNECTORS ARE INDICATED FOR
 EITHER END OF TRUSS MS4H.
  
 9) BOTH ENDS OF TRUSS TCT1 ARE INDICATED
 AS HAVING (7) CONNECTOR STRAPS ON SHEET
 A-13. HOWEVER, DETAIL 20 ON A-11
 INDICATES A HANGER. PLEASE CLARIFY.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop Z ZONING
Rev No 1 Status P Date 2002-02-04 Cont ID  
Sent By sgraham Date 2002-02-04 Time 14:05 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***