Plan Review Details - Permit 01121423
Plan Review Stops For Permit 01121423
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2001-12-24 Cont ID  
Sent By dpalmer Date 2001-12-24 Time 14:08 Rev Time 0.00
Received By dpalmer Date 2001-12-24 Time 14:08 Sent To FIRE
Notes
2001-12-24 00:00:00***************** NOTE ****************
  
 PLEASE NOTE, NO ELECTRICAL FOR REVIEW.
 ELECTRICAL WAS REVIEWED ON MAIN MASTER
 PLAN.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2002-01-02 Cont ID  
Sent By dpalmer Date 2001-12-24 Time 14:09 Rev Time 0.00
Received By mcarsill Date 2002-01-02 Time 15:55 Sent To  
Notes
2002-01-02 00:00:001) PLEASE PROVIDE CUT-SHEETS FOR FUEL
 TANK. THE ONLY LITERATURE IS A SALES
 ORDER FORM WHICH IS NOT ACCEPTABLE TO
 THIS OFFICE.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2002-01-03 Cont ID  
Sent By pkrauss Date 2002-01-03 Time 08:23 Rev Time 0.40
Received By pkrauss Date 2002-01-03 Time 07:21 Sent To  
Notes
2002-01-03 00:00:00 
  
 THIS PERMIT IS FOR ELECTRICAL.PLEASE
 SUBMIT MECHANICAL PLANS & MANUFACTURER
 SUBMITTAL DATAL FOR GENERATOR/FUEL TANK
 WITH MECHANICAL PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.