Plan Review Details - Permit 01121260
Plan Review Stops For Permit 01121260
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-02-11 Cont ID  
Sent By jwitmer Date 2002-02-11 Time 14:34 Rev Time 1.00
Received By jwitmer Date 2002-02-11 Time 14:34 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-01-03 Cont ID  
Sent By jwitmer Date 2002-01-03 Time 15:05 Rev Time 1.50
Received By jwitmer Date 2002-01-03 Time 15:04 Sent To  
Notes
2002-01-03 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01121260
 3111 45TH STRET
 PLAN REVIEW
 QUIZUOS SUBS
 CONTACT STEVE JOHNSON
 TEL (954) 557-2177
  
 1)- COVER SHEET,CODE REVIEW: NOT THE
 1999 SOUTH FLORIDA BUILDING CODE,
 PLANS SUBMITTED FOR PLAN REVIEW AS OF
 DEC. 18,2001 WILL BE REVIEWED UNDER
 THE 1997 STANDARD BUILDING CODE. PLANS
 SUBMITTED FOR PERMIT APPLICATION FROM
 JAN 1/2002 THROUGH FEBRUARY 28/2002
 MAY BE REVIEWED UNDER EITHER THE 1997
 STANDARD BUILDING CODE OR THE 2001
 FLORIDA CODE. THE DESIGNER OF RECORD
 SHALL BE REQUIRED TO IDENTIFY WHICH CODE
 WAS USED IN DEVELOPING THE PROJECT.
 PLANS SUBMITTED FOR PERMIT APPLICATION
 AFTER MARCH 1ST/ 2002 SHALL BE REVIEWED
 UNDER THE 2001 FLORIDA CODE.
  
 2)- SBC 1003.1.2. OCCUPANT LOAD,
 DISCREPANCY: THE COVER SHEET INDICATES A
 OCC. LOAD FOR THE DINING ROOM OF 16 VS.
 THE FLOOR PLAN OF 22.
  
 3)- FL ACCESSIBILITY CODE 5.1. WHEERE
 FIXED TABLES ARE PROVIDED, AT LEAST 5%
 BUT NOT LESS THAN ONE, OF THE FIXED
 TABLES( OR A PORTION OF THE DINING
 COUNTER) SHALL BE ACCESSIBLE & SHALL
 COMPLY WITH 4.32.
  
 4)- SHEET # 2:
 A) INDICATES A SECTION 4/C A UL LIST-
 ING U-419, FOR A NONBEARING WALL EITHER
 1-4 HR. RATING. WHAT OCCUPANCIES ARE ON
 EACH SIDE OF THIS PROPOSED OCCUPANCY?
 THIS WILL BE THE DETERMINING FACTOR AS
 TO THE OCCUPANCY SEPERATION. SBC
 TABLE 704.1.WHAT TYPE OF ROOF DECK ABOVE
 B) NOTE FOR SOLID BACKING IN TENANT
 SEPERATION WALLS, SEE SECTION 707.1
 COMBUSTIBLES IN CONCEALED SPACES.
 C) NOTE "ALANCE ABOVE SHEET 5 OF 5":
 DETAILS DO NOT SPECIFY THE SIZE OF THE
 ALL THREAD, NOTE PAGE 5 INDICATES
 SECURE STRUCTURE, VERIFY INSTALLATION,
 WHO?
  
 5)- SHEET 4 INDICATES INTERIOR FINISHES
 BUT THERE IS NO INFORMATION AS TO SBC
 TABLE 803.3 MINIMUM INTERIOR FINISH
 CLASSIFICATION. FLAMESPREAD/ SMOKE
 DEVELOPMENT.
  
 6)- SHEET 4 HARDWARE NOTES INDICATES THE
 USE OF THE "UNIFORM BUILDING CODE" THE
 SECTION SHOULD BE FROM SBC 1997, SEC.
 1020.2.(1).
  
 7)- SHEET M-1 ROOF TOP UNITS, ATTACHMENT
 MAKES REFRENCE TO BLDG. STRUCTURAL PLANS
 FOR ADDITIONAL INFORMATION? MISSING?
 BUILDING PLAN REVIEW
 JIM WITMER
 (561)659-8096X8412

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-02-12 Cont ID  
Sent By dpalmer Date 2002-02-12 Time 07:12 Rev Time 0.00
Received By dpalmer Date 2002-02-12 Time 07:12 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-12-28 Cont ID  
Sent By dpalmer Date 2001-12-28 Time 12:56 Rev Time 0.00
Received By dpalmer Date 2001-12-28 Time 12:24 Sent To  
Notes
2001-12-28 00:00:00****************** UNSAT ***********
  
 1)NOTE: PLEASE NOTE THAT THE NOTES ON
 PLANS MENTION "96" NEC AND PLANS
 NOTES MENTION A "97" NEC ?? PLEASE NOTE
 THAT THERE IS NOT A 97 NEC AND WE ARE
 CURRENTLY UNDER THE "99" NEC. PLEASE
 CORRECT.
  
 2)NOTE: PLEASE NOTE THAT COLOR CODING
 FOR FEEDERS (277/480) MUST BE BROWN,
 PURPLE, YELLOW.
 215-8
  
 3)NOTE: PLEASE NOTE THAT ALL AIC RATINGS
 ARE TO BE SUBMITTED BY THE ENGINEER OF
 RECORD.
  
 PLEASE MAKE THE ABOVE CORRECTIONS AND
 SUBMIT FOR REVIEW. IF THERE ARE ANY
 QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2002-02-06 Cont ID  
Sent By lsmith Date 2002-02-06 Time 12:00 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-02-06 Cont ID  
Sent By mcarsill Date 2002-02-06 Time 15:25 Rev Time 0.00
Received By mcarsill Date 2002-02-06 Time 15:24 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-12-27 Cont ID  
Sent By mcarsill Date 2001-12-27 Time 09:44 Rev Time 0.00
Received By mcarsill Date 2001-12-27 Time 09:44 Sent To  
Notes
2001-12-27 00:00:001) WRONG BUILDING CODE REFERENCED ON
 THE PLANS.
 2) A DISCREPANCY EXISTS BETWEEN THE
 OCCUPANT LOAD LISTED AND THE FURNITURE
 LAYOUT. THERE ARE MORE THAN 18 SEATS
 PROVIDED ON THE FURNITURE LAYOUT. PLEASE
 CORRECT INFORMATION.
 3) NO INTERIOR FINISH CLASSIFICATION
 INFORMATION PROVIDED WITH PLANS FOR
 THE WALLS AND CEILINGS.
 4) EXITING WIDTH CACULATION INCORRECT.
 5) SEPARATE PLANS AND PERMITS REQUIRED
 FOR THE HOOD,DUCT AND FIRE SUPPRESSION
 SYSTEM PLANNED FOR USE.
 6) PLEASE INDICATE ON THE PLANS THE
 TENANT SEPARATION DEMISING WALLS.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2002-02-28 Cont ID  
Sent By pkrauss Date 2002-02-28 Time 11:13 Rev Time 0.45
Received By pkrauss Date 2002-02-28 Time 11:05 Sent To  
Notes
2002-02-28 00:00:00 
  
 PROVISO:
  
 BATHROOM EXHAUST TERMINATION SHALL BE:
  
 1.10 FT ABOVE THE ADJOINING GRADE
 LEVEL.
  
 2.10 FT FROM ANY ADJACENT BUILDING,
 PARKING AREA, PROPERTY LINE, WINDOW,
 DOOR OR FRESH AIR INTAKE (OR 2 FT
 ABOVE WINDOW, DOOR, OR FRESH AIR
 INTAKE.)
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2002-02-14 Cont ID  
Sent By pkrauss Date 2002-02-14 Time 07:52 Rev Time 0.40
Received By pkrauss Date 2002-02-14 Time 07:52 Sent To  
Notes
2002-02-14 00:00:00*******************DENIED***************
  
  
 1.PROVIDE OUTSIDE AIR CALCULATIONS AS
 PER ASHRAE 62-89.
  
 2.PROVIDE AIR BALANCE SCHEDULE SHOWING
 COMPLIANCE WITH 1997 SMC 501.2.
  
 3.INDICATE CONDENSATE TERMINATION.
  
 PLEASE NOTE, SEPARATE PERMIT REQUIRED
 FOR HOOD, FIRE SUPRESSION, AND WALKIN
 COOLERS.PROVIDE PLANS AND
 MANUFACTURERS SUBMITTAL DATA WITH
 PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-12-20 Cont ID  
Sent By pkrauss Date 2001-12-20 Time 14:10 Rev Time 0.50
Received By pkrauss Date 2001-12-20 Time 14:10 Sent To  
Notes
2001-12-20 00:00:00********************DENIED**************
  
  
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 FOR REVIEW.
  
 1.OUTSIDE AIR CALCULATIONS AS PER
 ASHRAE 62-1989.
  
 2.CONDENSATE SHALL TERMINATE TO EITHER
 AN APPROVED DRYWELL OR TO STORM
 DRAINAGE SYSTEM AS PER COUNTYWIDE
 AMENDMENTS 1994 SPC 804.3.
  
 PLEASE NOTE ADDITIONAL PERMITS REQUIRED
 FOR HOOD, FIRE SUPRESSION AND WALK-IN
 COOLER/FREEZER.PROVIDE PLANS WITH
 PERMIT APPLICATION.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 5 Status P Date 2002-05-01 Cont ID  
Sent By kstevens Date 2002-04-21 Time 16:15 Rev Time 0.00
Received By kstevens Date 2002-04-21 Time 16:14 Sent To  
Notes
2002-05-01 00:00:00FAILED 4-22 UNTILL ALL PAGES SIGNED &
 SEALED. CHECKED 5-2 ALL PAGES OK - NOW
 CONTRACTOR NEEDS TO APPLY FOR PERMIT.

Review Stop P PLUMBING
Rev No 4 Status F Date 2002-03-27 Cont ID  
Sent By kstevens Date 2002-03-27 Time 13:43 Rev Time 0.00
Received By kstevens Date 2002-03-27 Time 13:43 Sent To  
Notes
2002-03-27 00:00:00DENIED
 REFERENCE: SPC-94 - FACBC-97
  
 1) FROM PREVIOUS REVIEWS SEPARATE GREASE
 LINE REQUIRED BEFORE SAMPLE POINT. AFTER
 SAMPLE POINT, TIE GREASE LINE INTO SANIT
 ARY SYSTEM
 2) NOT SAMPLE POINT SHOWN ON PLANS
 3) RPZ BACK FLOW FOR WATER SERVICE SHALL
 NOT BE MORE THAN 4' MAX OFF FLOOR FOR
 SERVICE.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 3 Status F Date 2002-02-26 Cont ID  
Sent By kstevens Date 2002-02-26 Time 18:46 Rev Time 0.50
Received By kstevens Date 2002-02-26 Time 18:46 Sent To  
Notes
2002-02-26 00:00:00DENIED
 REFERENCE: SPC-94-FACBC-97
  
 1) ALL COMMENTS FROM PREVIOUS REVIEW
 HAVE NOT BEEN ADDRESSED (1 THRU 4) OR
 NOT ADDRESSED PROPERLY #5.
 2) FROM PREVIOUS REVIEWS - UNDERSINK
 GREASE TRAP IS NOT APPROVED WEATHER OR
 NOT THE GREASE TRAP IS WAIVED. SHT P-1
 3) SHT P-1 SEPARATE GREASE LINE SHALL BE
 INSTALLED SO THE SAMPLE POINT CAN BE
 MONITERED BEFORE TYING INTO THE SANITARY
 4) IF AN EMERGENCY PAN IS INSTALLED ON
 A WATER HEATER THAN IT SHALL HAVE A
 DRAIN LINE INSTALLED. SPC SEC 507.8.2
 5) SUBMIT AN EXISTING FLOOR PLAN FOR
 DEMO. DEMO PERMIT REQUIRED
 6) SHT P-1 RPZ BACKFLOW REQUIRED ON
 WATER SERVICE.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 2 Status F Date 2002-02-12 Cont ID  
Sent By kstevens Date 2002-02-12 Time 11:22 Rev Time 0.50
Received By kstevens Date 2002-02-12 Time 11:22 Sent To  
Notes
2002-02-12 00:00:00DENIED
 REFERENCE: SPC-94-FACBC-97
  
 1) FROM PREVIOUS PLAN REVIEW #2, UNDER
 SINK GREASE TRAP IS NOT APPROVED. MINIM-
 UM SIZE GREASE TRAP IS 750 GAL.
 2) SHT P-1 SEPARATE GREASY WASTE LINE
 SHALL BE INSTALLED. TO MONITOR SAMPLE
 POINT, SAMPLE POINT SHALL BE INSTALLED
 PRIOR TO TYING GREASE LINE TO SANITARY.
 3) FROM PREVIOUS PLAN REVIEW #8, 1"
 DRAIN LINE IS REQUIRED FOR EMERGENCY PAN
 4) FROM PREVIOUS PLAN REVIEW #10, PLEASE
 SUBMIT AN EXISTING FLOOR PLAN FOR DEMO.
 EXISTING FIXTURES NEED TO BE SHOWN SO
 INSPECTORS CAN SEE IF THEY ARE CAPPED
 PROPERLY DURING DEMO INSPECTIONS. PLUMB.
 DEMO PERMIT REQUIRED.
 5) SHT P-1 RPZ BACKFLOW REQUIRED ON
 WATER SERVICE. (NEW COMMENT)
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-01-12 Cont ID  
Sent By kstevens Date 2002-01-12 Time 14:56 Rev Time 1.50
Received By kstevens Date 2002-01-12 Time 16:17 Sent To  
Notes
2002-01-12 00:00:00DENIED
 REFERENCE: SPC-94-FACBC-97
  
 1) COVER PAGE, CODE REVIEW SHOULD READ
 SBCCI SPC-94
 2) PLANS TO BE ROUTED TO DEPT OF BUSIN-
 ESS HOTEL & RESTURANT DIVISION FOR PLAN
 REVIEW BEFORE RESUBMITTING.
 3) GREASE TRAP TO BE SIZED AND LOCATED
 BY UTILITY DEPT REGONIAL WASTE WATER
 TREATMENT. PLEASE CALL RODNEY COMPO
 (561) 837-4074 - WASTE ORD. #2938-96
 4) SHT P-1 UNDER SINK GREASE TRAP DETAIL
 NOT APPROVED.
 5) SHT P-1 GREASY WASTE SHALL BE SEPAR-
 ATETED FROM SANITARY.
 6) SHT P-1 FLOOR SINK REQUIRED FOR IN-
 DIRECT WASTE FROM WATER HEATER. SEC 804
 7) SHT P-1 CONDENSATE TO FLOOR SINK NOT
 FLOOR DRAIN. SPC SEC 804.5
 8) SHT P-1 WATER HEATER DETAIL, PLUMBING
 KEYNOTE #2. HEATER PAN NOT REQUIRED, BUT
 IF USED A 1" PAN DRAIN IS REQUIRED. SPC
 SEC 507.8.2
 9) SHT P-1 WATER HAMMER ARRESTORS SHALL
 BE LOCATED BY FIXTURES IN AN "EFFECTIVE
 RANGE", NOT AT TOP OF DROPS AS SHOWN.
 10) PLEASE SUBMIT A SHEET SHOWING DEMO
 OF EXISTING SPACE.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status N Date 2002-02-06 Cont ID  
Sent By lsmith Date 2002-02-06 Time 12:00 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved