| Plan Review Stops For Permit 01121260 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2002-02-11 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2002-02-11 |
Time |
14:34 |
Rev Time |
1.00 |
| Received By |
jwitmer |
Date |
2002-02-11 |
Time |
14:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2002-01-03 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2002-01-03 |
Time |
15:05 |
Rev Time |
1.50 |
| Received By |
jwitmer |
Date |
2002-01-03 |
Time |
15:04 |
Sent To |
|
|
| Notes |
| 2002-01-03 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT # 01121260 | | | 3111 45TH STRET | | | PLAN REVIEW | | | QUIZUOS SUBS | | | CONTACT STEVE JOHNSON | | | TEL (954) 557-2177 | | | | | | 1)- COVER SHEET,CODE REVIEW: NOT THE | | | 1999 SOUTH FLORIDA BUILDING CODE, | | | PLANS SUBMITTED FOR PLAN REVIEW AS OF | | | DEC. 18,2001 WILL BE REVIEWED UNDER | | | THE 1997 STANDARD BUILDING CODE. PLANS | | | SUBMITTED FOR PERMIT APPLICATION FROM | | | JAN 1/2002 THROUGH FEBRUARY 28/2002 | | | MAY BE REVIEWED UNDER EITHER THE 1997 | | | STANDARD BUILDING CODE OR THE 2001 | | | FLORIDA CODE. THE DESIGNER OF RECORD | | | SHALL BE REQUIRED TO IDENTIFY WHICH CODE | | | WAS USED IN DEVELOPING THE PROJECT. | | | PLANS SUBMITTED FOR PERMIT APPLICATION | | | AFTER MARCH 1ST/ 2002 SHALL BE REVIEWED | | | UNDER THE 2001 FLORIDA CODE. | | | | | | 2)- SBC 1003.1.2. OCCUPANT LOAD, | | | DISCREPANCY: THE COVER SHEET INDICATES A | | | OCC. LOAD FOR THE DINING ROOM OF 16 VS. | | | THE FLOOR PLAN OF 22. | | | | | | 3)- FL ACCESSIBILITY CODE 5.1. WHEERE | | | FIXED TABLES ARE PROVIDED, AT LEAST 5% | | | BUT NOT LESS THAN ONE, OF THE FIXED | | | TABLES( OR A PORTION OF THE DINING | | | COUNTER) SHALL BE ACCESSIBLE & SHALL | | | COMPLY WITH 4.32. | | | | | | 4)- SHEET # 2: | | | A) INDICATES A SECTION 4/C A UL LIST- | | | ING U-419, FOR A NONBEARING WALL EITHER | | | 1-4 HR. RATING. WHAT OCCUPANCIES ARE ON | | | EACH SIDE OF THIS PROPOSED OCCUPANCY? | | | THIS WILL BE THE DETERMINING FACTOR AS | | | TO THE OCCUPANCY SEPERATION. SBC | | | TABLE 704.1.WHAT TYPE OF ROOF DECK ABOVE | | | B) NOTE FOR SOLID BACKING IN TENANT | | | SEPERATION WALLS, SEE SECTION 707.1 | | | COMBUSTIBLES IN CONCEALED SPACES. | | | C) NOTE "ALANCE ABOVE SHEET 5 OF 5": | | | DETAILS DO NOT SPECIFY THE SIZE OF THE | | | ALL THREAD, NOTE PAGE 5 INDICATES | | | SECURE STRUCTURE, VERIFY INSTALLATION, | | | WHO? | | | | | | 5)- SHEET 4 INDICATES INTERIOR FINISHES | | | BUT THERE IS NO INFORMATION AS TO SBC | | | TABLE 803.3 MINIMUM INTERIOR FINISH | | | CLASSIFICATION. FLAMESPREAD/ SMOKE | | | DEVELOPMENT. | | | | | | 6)- SHEET 4 HARDWARE NOTES INDICATES THE | | | USE OF THE "UNIFORM BUILDING CODE" THE | | | SECTION SHOULD BE FROM SBC 1997, SEC. | | | 1020.2.(1). | | | | | | 7)- SHEET M-1 ROOF TOP UNITS, ATTACHMENT | | | MAKES REFRENCE TO BLDG. STRUCTURAL PLANS | | | FOR ADDITIONAL INFORMATION? MISSING? | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561)659-8096X8412 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2002-02-12 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-02-12 |
Time |
07:12 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-02-12 |
Time |
07:12 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2001-12-28 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-12-28 |
Time |
12:56 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-12-28 |
Time |
12:24 |
Sent To |
|
|
| Notes |
| 2001-12-28 00:00:00 | ****************** UNSAT *********** | | | | | | 1)NOTE: PLEASE NOTE THAT THE NOTES ON | | | PLANS MENTION "96" NEC AND PLANS | | | NOTES MENTION A "97" NEC ?? PLEASE NOTE | | | THAT THERE IS NOT A 97 NEC AND WE ARE | | | CURRENTLY UNDER THE "99" NEC. PLEASE | | | CORRECT. | | | | | | 2)NOTE: PLEASE NOTE THAT COLOR CODING | | | FOR FEEDERS (277/480) MUST BE BROWN, | | | PURPLE, YELLOW. | | | 215-8 | | | | | | 3)NOTE: PLEASE NOTE THAT ALL AIC RATINGS | | | ARE TO BE SUBMITTED BY THE ENGINEER OF | | | RECORD. | | | | | | PLEASE MAKE THE ABOVE CORRECTIONS AND | | | SUBMIT FOR REVIEW. IF THERE ARE ANY | | | QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
N |
Date |
2002-02-06 |
|
|
Cont ID |
|
| Sent By |
lsmith |
Date |
2002-02-06 |
Time |
12:00 |
Rev Time |
0.00 |
| Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2002-02-06 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-02-06 |
Time |
15:25 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-02-06 |
Time |
15:24 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2001-12-27 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-12-27 |
Time |
09:44 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-12-27 |
Time |
09:44 |
Sent To |
|
|
| Notes |
| 2001-12-27 00:00:00 | 1) WRONG BUILDING CODE REFERENCED ON | | | THE PLANS. | | | 2) A DISCREPANCY EXISTS BETWEEN THE | | | OCCUPANT LOAD LISTED AND THE FURNITURE | | | LAYOUT. THERE ARE MORE THAN 18 SEATS | | | PROVIDED ON THE FURNITURE LAYOUT. PLEASE | | | CORRECT INFORMATION. | | | 3) NO INTERIOR FINISH CLASSIFICATION | | | INFORMATION PROVIDED WITH PLANS FOR | | | THE WALLS AND CEILINGS. | | | 4) EXITING WIDTH CACULATION INCORRECT. | | | 5) SEPARATE PLANS AND PERMITS REQUIRED | | | FOR THE HOOD,DUCT AND FIRE SUPPRESSION | | | SYSTEM PLANNED FOR USE. | | | 6) PLEASE INDICATE ON THE PLANS THE | | | TENANT SEPARATION DEMISING WALLS. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2002-02-28 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-02-28 |
Time |
11:13 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2002-02-28 |
Time |
11:05 |
Sent To |
|
|
| Notes |
| 2002-02-28 00:00:00 | | | | | | | PROVISO: | | | | | | BATHROOM EXHAUST TERMINATION SHALL BE: | | | | | | 1.10 FT ABOVE THE ADJOINING GRADE | | | LEVEL. | | | | | | 2.10 FT FROM ANY ADJACENT BUILDING, | | | PARKING AREA, PROPERTY LINE, WINDOW, | | | DOOR OR FRESH AIR INTAKE (OR 2 FT | | | ABOVE WINDOW, DOOR, OR FRESH AIR | | | INTAKE.) | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2002-02-14 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-02-14 |
Time |
07:52 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2002-02-14 |
Time |
07:52 |
Sent To |
|
|
| Notes |
| 2002-02-14 00:00:00 | *******************DENIED*************** | | | | | | | | | 1.PROVIDE OUTSIDE AIR CALCULATIONS AS | | | PER ASHRAE 62-89. | | | | | | 2.PROVIDE AIR BALANCE SCHEDULE SHOWING | | | COMPLIANCE WITH 1997 SMC 501.2. | | | | | | 3.INDICATE CONDENSATE TERMINATION. | | | | | | PLEASE NOTE, SEPARATE PERMIT REQUIRED | | | FOR HOOD, FIRE SUPRESSION, AND WALKIN | | | COOLERS.PROVIDE PLANS AND | | | MANUFACTURERS SUBMITTAL DATA WITH | | | PERMIT APPLICATION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2001-12-20 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-12-20 |
Time |
14:10 |
Rev Time |
0.50 |
| Received By |
pkrauss |
Date |
2001-12-20 |
Time |
14:10 |
Sent To |
|
|
| Notes |
| 2001-12-20 00:00:00 | ********************DENIED************** | | | | | | | | | PLEASE PROVIDE THE FOLLOWING INFORMATION | | | FOR REVIEW. | | | | | | 1.OUTSIDE AIR CALCULATIONS AS PER | | | ASHRAE 62-1989. | | | | | | 2.CONDENSATE SHALL TERMINATE TO EITHER | | | AN APPROVED DRYWELL OR TO STORM | | | DRAINAGE SYSTEM AS PER COUNTYWIDE | | | AMENDMENTS 1994 SPC 804.3. | | | | | | PLEASE NOTE ADDITIONAL PERMITS REQUIRED | | | FOR HOOD, FIRE SUPRESSION AND WALK-IN | | | COOLER/FREEZER.PROVIDE PLANS WITH | | | PERMIT APPLICATION. | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
P |
Date |
2002-05-01 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-04-21 |
Time |
16:15 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2002-04-21 |
Time |
16:14 |
Sent To |
|
|
| Notes |
| 2002-05-01 00:00:00 | FAILED 4-22 UNTILL ALL PAGES SIGNED & | | | SEALED. CHECKED 5-2 ALL PAGES OK - NOW | | | CONTRACTOR NEEDS TO APPLY FOR PERMIT. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
F |
Date |
2002-03-27 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-03-27 |
Time |
13:43 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2002-03-27 |
Time |
13:43 |
Sent To |
|
|
| Notes |
| 2002-03-27 00:00:00 | DENIED | | | REFERENCE: SPC-94 - FACBC-97 | | | | | | 1) FROM PREVIOUS REVIEWS SEPARATE GREASE | | | LINE REQUIRED BEFORE SAMPLE POINT. AFTER | | | SAMPLE POINT, TIE GREASE LINE INTO SANIT | | | ARY SYSTEM | | | 2) NOT SAMPLE POINT SHOWN ON PLANS | | | 3) RPZ BACK FLOW FOR WATER SERVICE SHALL | | | NOT BE MORE THAN 4' MAX OFF FLOOR FOR | | | SERVICE. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2002-02-26 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-02-26 |
Time |
18:46 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2002-02-26 |
Time |
18:46 |
Sent To |
|
|
| Notes |
| 2002-02-26 00:00:00 | DENIED | | | REFERENCE: SPC-94-FACBC-97 | | | | | | 1) ALL COMMENTS FROM PREVIOUS REVIEW | | | HAVE NOT BEEN ADDRESSED (1 THRU 4) OR | | | NOT ADDRESSED PROPERLY #5. | | | 2) FROM PREVIOUS REVIEWS - UNDERSINK | | | GREASE TRAP IS NOT APPROVED WEATHER OR | | | NOT THE GREASE TRAP IS WAIVED. SHT P-1 | | | 3) SHT P-1 SEPARATE GREASE LINE SHALL BE | | | INSTALLED SO THE SAMPLE POINT CAN BE | | | MONITERED BEFORE TYING INTO THE SANITARY | | | 4) IF AN EMERGENCY PAN IS INSTALLED ON | | | A WATER HEATER THAN IT SHALL HAVE A | | | DRAIN LINE INSTALLED. SPC SEC 507.8.2 | | | 5) SUBMIT AN EXISTING FLOOR PLAN FOR | | | DEMO. DEMO PERMIT REQUIRED | | | 6) SHT P-1 RPZ BACKFLOW REQUIRED ON | | | WATER SERVICE. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2002-02-12 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-02-12 |
Time |
11:22 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2002-02-12 |
Time |
11:22 |
Sent To |
|
|
| Notes |
| 2002-02-12 00:00:00 | DENIED | | | REFERENCE: SPC-94-FACBC-97 | | | | | | 1) FROM PREVIOUS PLAN REVIEW #2, UNDER | | | SINK GREASE TRAP IS NOT APPROVED. MINIM- | | | UM SIZE GREASE TRAP IS 750 GAL. | | | 2) SHT P-1 SEPARATE GREASY WASTE LINE | | | SHALL BE INSTALLED. TO MONITOR SAMPLE | | | POINT, SAMPLE POINT SHALL BE INSTALLED | | | PRIOR TO TYING GREASE LINE TO SANITARY. | | | 3) FROM PREVIOUS PLAN REVIEW #8, 1" | | | DRAIN LINE IS REQUIRED FOR EMERGENCY PAN | | | 4) FROM PREVIOUS PLAN REVIEW #10, PLEASE | | | SUBMIT AN EXISTING FLOOR PLAN FOR DEMO. | | | EXISTING FIXTURES NEED TO BE SHOWN SO | | | INSPECTORS CAN SEE IF THEY ARE CAPPED | | | PROPERLY DURING DEMO INSPECTIONS. PLUMB. | | | DEMO PERMIT REQUIRED. | | | 5) SHT P-1 RPZ BACKFLOW REQUIRED ON | | | WATER SERVICE. (NEW COMMENT) | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2002-01-12 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-01-12 |
Time |
14:56 |
Rev Time |
1.50 |
| Received By |
kstevens |
Date |
2002-01-12 |
Time |
16:17 |
Sent To |
|
|
| Notes |
| 2002-01-12 00:00:00 | DENIED | | | REFERENCE: SPC-94-FACBC-97 | | | | | | 1) COVER PAGE, CODE REVIEW SHOULD READ | | | SBCCI SPC-94 | | | 2) PLANS TO BE ROUTED TO DEPT OF BUSIN- | | | ESS HOTEL & RESTURANT DIVISION FOR PLAN | | | REVIEW BEFORE RESUBMITTING. | | | 3) GREASE TRAP TO BE SIZED AND LOCATED | | | BY UTILITY DEPT REGONIAL WASTE WATER | | | TREATMENT. PLEASE CALL RODNEY COMPO | | | (561) 837-4074 - WASTE ORD. #2938-96 | | | 4) SHT P-1 UNDER SINK GREASE TRAP DETAIL | | | NOT APPROVED. | | | 5) SHT P-1 GREASY WASTE SHALL BE SEPAR- | | | ATETED FROM SANITARY. | | | 6) SHT P-1 FLOOR SINK REQUIRED FOR IN- | | | DIRECT WASTE FROM WATER HEATER. SEC 804 | | | 7) SHT P-1 CONDENSATE TO FLOOR SINK NOT | | | FLOOR DRAIN. SPC SEC 804.5 | | | 8) SHT P-1 WATER HEATER DETAIL, PLUMBING | | | KEYNOTE #2. HEATER PAN NOT REQUIRED, BUT | | | IF USED A 1" PAN DRAIN IS REQUIRED. SPC | | | SEC 507.8.2 | | | 9) SHT P-1 WATER HAMMER ARRESTORS SHALL | | | BE LOCATED BY FIXTURES IN AN "EFFECTIVE | | | RANGE", NOT AT TOP OF DROPS AS SHOWN. | | | 10) PLEASE SUBMIT A SHEET SHOWING DEMO | | | OF EXISTING SPACE. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
2002-02-06 |
|
|
Cont ID |
|
| Sent By |
lsmith |
Date |
2002-02-06 |
Time |
12:00 |
Rev Time |
0.00 |
| Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|