| 2001-12-20 00:00:00 | 1) NO SMOKE DETECTORS OBSERVED IN |
| | ELEVATOR LOBBIES ON THE SIXTH AND |
| | SEVENTH FLOORS. |
| | 2) PLEASE INDICATE ON THE PLANS WHAT |
| | THE VOICE EVACUATION PORTION OF THE |
| | FIRE ALARM SYSTEM WILL ADVISE PERSONS |
| | TO DO IN THE EVENT OF AN EMERGENCY. |
| | 3) NO MANUAL PULL STATIONS SHOWN ON |
| | THE PLANS FOR THE UPPER FLOORS OF |
| | THE BUILDING. |
| | 4) NO MANUAL PULL STATIONS NEAR STAIRS |
| | 2 AND 3 IN THE GARAGE AREA. |
| | 5) NO SMOKE DETECTOR PROVIDED ABOVE |
| | FIRE ALARM CONTROL PANELS. |
| | 6) PLEASE EXPLAIN RATIONALE FOR SMOKE |
| | DETECTORS IN THE LAUNDRIES AND THE |
| | TRASH ROOMS. |
| | 7) PLEASE INDICATE ON THE PLANS FIRE |
| | PUMP RUN, FIRE PUMP FAIL, AND PHASE |
| | REVERSAL. |
| | 8) THE FIRE ALARM SYSTEM IS TO BE |
| | MONITORED BY A LICENSED UL LISTED |
| | CENTRAL STATION APPROVED BY THE FIRE |
| | RESCUE DEPARTMENT. |
| | 9) DUCT SMOKE DETECTORS REQUIRED IN |
| | HVAC UNITS OVER 2000 CFM. |
| | 10) ADDITIONAL FIRE ALARM EQUIPMENT |
| | WILL BE REQUIRED IN THE FUTURE RETAIL |
| | SPACES OF THE BUILDING. |
| | 11) PLEASE INDICATE ON THE PLANS WHAT |
| | AREAS OF THE BUILDING WILL GO INTO |
| | GENERAL ALARM MODE. WILL IT BE THE |
| | ENTIRE BUILDING OR CERTAIN AREAS OF |
| | THE BUILDING. |
| | |
| | MIKE CARSILLO, CAPTAIN |
| | 659-8096,EXT.8497 |
| | 835-2910 |