Plan Review Details - Permit 01121255
Plan Review Stops For Permit 01121255
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-04-09 Cont ID  
Sent By mcarsill Date 2002-04-09 Time 16:52 Rev Time 0.00
Received By mcarsill Date 2002-04-09 Time 16:52 Sent To  
Notes
2002-04-09 00:00:00CALLED STRYKER ELECTRIC AND ADVISED THEM
 THAT THEY NEED A NOTICE OF COMMENCEMENT.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-12-20 Cont ID  
Sent By mcarsill Date 2001-12-20 Time 17:17 Rev Time 0.00
Received By mcarsill Date 2001-12-20 Time 17:17 Sent To  
Notes
2001-12-20 00:00:001) NO SMOKE DETECTORS OBSERVED IN
 ELEVATOR LOBBIES ON THE SIXTH AND
 SEVENTH FLOORS.
 2) PLEASE INDICATE ON THE PLANS WHAT
 THE VOICE EVACUATION PORTION OF THE
 FIRE ALARM SYSTEM WILL ADVISE PERSONS
 TO DO IN THE EVENT OF AN EMERGENCY.
 3) NO MANUAL PULL STATIONS SHOWN ON
 THE PLANS FOR THE UPPER FLOORS OF
 THE BUILDING.
 4) NO MANUAL PULL STATIONS NEAR STAIRS
 2 AND 3 IN THE GARAGE AREA.
 5) NO SMOKE DETECTOR PROVIDED ABOVE
 FIRE ALARM CONTROL PANELS.
 6) PLEASE EXPLAIN RATIONALE FOR SMOKE
 DETECTORS IN THE LAUNDRIES AND THE
 TRASH ROOMS.
 7) PLEASE INDICATE ON THE PLANS FIRE
 PUMP RUN, FIRE PUMP FAIL, AND PHASE
 REVERSAL.
 8) THE FIRE ALARM SYSTEM IS TO BE
 MONITORED BY A LICENSED UL LISTED
 CENTRAL STATION APPROVED BY THE FIRE
 RESCUE DEPARTMENT.
 9) DUCT SMOKE DETECTORS REQUIRED IN
 HVAC UNITS OVER 2000 CFM.
 10) ADDITIONAL FIRE ALARM EQUIPMENT
 WILL BE REQUIRED IN THE FUTURE RETAIL
 SPACES OF THE BUILDING.
 11) PLEASE INDICATE ON THE PLANS WHAT
 AREAS OF THE BUILDING WILL GO INTO
 GENERAL ALARM MODE. WILL IT BE THE
 ENTIRE BUILDING OR CERTAIN AREAS OF
 THE BUILDING.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910