| 2002-01-05 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT # 01121242 |
| | 1400 NORTHPOINT PARKWAY # 40 |
| | CONT BUTTERS CONSTRUCTION |
| | TEL: (954)570-8111 |
| | |
| | SBC= 1997 STANDARD BUILDING CODE |
| | FL ACC= 1997 FLORIDA ACCESSIBILITY CODE |
| | |
| | 1)- WAREHOUSE- BSC 104.2.2. ADDITIONAL |
| | INFORMATION REQUIRED, THE TYPES OF MATER |
| | IALS TO BE STORED, QUANITIES, TYPE OF |
| | STORAGE UNITS, RACKS, THE HEIGTH OF THE |
| | RACKS, WILL FIRE SPRINKLERS BE INCORP- |
| | ARATED INTO THE RACK SYSTEMS? THIS ADDI- |
| | TIONAL INFORMATION SHALL BE NECESSARY |
| | BEFORE WE WILL BE ABLE TO CLASSIFY THE |
| | OCCUPANCY OF THE WAREHOUSE. |
| | |
| | 2)- ROOM # 144 SHOWROOM, WITHOUT A LAY- |
| | OUT OF FURNATURE OR BETTER DISCRIPTION |
| | OF THE USE OF THIS ROOM, IT MAY APPEAR |
| | TO BE A, A-2 SMALL ASSEMBLY USAGE, |
| | 1840 SQ FT @ 15 FT/PERSON= 122 OCCUPANTS |
| | IN THIS CASE (2) PROBLEMS OCCUR: (1) |
| | SBC TABLE 704.1 SHALL REQUIRE 2 HR SEPER |
| | ATION/ W 1 1/2 HR OPENING PROTECTION. |
| | 704.1.2.2 THIS SPACE DOES NOT FALL UNDER |
| | EXEMPTIONS FOR ACCESSORY UES.(2) DOOR |
| | 144B WOULD HAVE TO REVERSE THE SWING OF |
| | THE DOORS PER SBC 1004.1.2.(ROOMS WITH |
| | AN OCC LOAD > 50. |
| | |
| | 3)- SHEET A-8 DETAIL "A" DEPICTS A 2 HR |
| | WALL ASSEMBLY, A UL LISTING OR U.S. |
| | GYPSUM NUMBER REQUIRED. SBC 705.1.2. |
| | WHAT TYPE OF FIRESTOP SYSTEM WILL BE |
| | USED AT THE METAL ROOF DECK ? |
| | |
| | 4)- WAREHOUSE EGRESS:SBC 1001.1.3: |
| | IT IS CRITICAL THAT THE REQUIRED MEANS |
| | OF EGRESS BE DESIGNATED AND MAINTAINED |
| | TO INSURE THAT THESE OBSTRUCTIONS ARE |
| | ELIMINATED, SPECIAL MARKINGS OR SOME |
| | TYPE OF RAILING OR SCREENING MAY BE USED |
| | TO SEPERATE THEDESIGNATED MEANS OF |
| | EGRESS FROM THE STORAGE USE. |
| | |
| | 5)- SHEET A-6/2 STAIR DETAIL, MORE |
| | INFORMATION SHALL BE REQUIRED. THERE IS |
| | NO INFORMATION ON THE SIDE WALLS OF THE |
| | ELEVATED LANDING. THE DETAIL ALSO INDICA |
| | TES AN EXISTING SLAB THAT CONTINUES |
| | UNDER THE BUILDING?!! |
| | GIVE THE CORRECT RISE & RUN SBC 1007.3.1 |
| | NOT 7T@6 25/32. FOR THE GAURDRAIL INFOR- |
| | MATION LOOK AT THE 4" SPHERE DETAILED |
| | VS. SBC 1015.3, BOTTOM RAIL OF GUARDRAIL |
| | CLEARENCE FROM LANDING 2" NOT 4". |
| | |
| | 6)- SHEET A-4 DETAIL A6/1 NEW EXTERIOR |
| | DOORWAY, SBC 1606.2.6.2 COMPONENTS AND |
| | CLADDING, PROVIDE 2 COPIES OF PRODUCT |
| | TESTING REPORT FOR LARGE MISSLE IMPACT |
| | RESISTANCE TESTING.EITHER SBCCI OR DADE |
| | COUNTY REPORTS ARE ACCEPTED. |
| | |
| | 7)- PUBLIC RESTROOMS: SBC 1204.2 |
| | SCHEDULE MISSING INFORMATION FOR CT-2? |
| | |
| | FLORIDA ACCESSIBILITY CODE: |
| | 8)- DOOR 104-A 4.22.2/4.23.2 DOORS |
| | ACCESSIBILE TO BATHROOM SHALL COMPLY |
| | WITH 4.13 DOORS SHALL NOT SWING INTO THE |
| | FLOOR SPACE REQUIRED FOR ANY FIXTURE. |
| | |
| | 9)- DOOR114-A SAME AS ABOVE. |
| | |
| | 10)- MENS RESTROOM WATERCLOSET STALLS: |
| | 4.17.3(2) SIZE & ARRANGEMENT ACCESSIBLE |
| | WATER CLOSET SHALL BE LOCATED IN THE |
| | CORNER DIAGONAL TO THE DOOR. |
| | |
| | SHEET# 5 DETAIL #1 UPPER CABINETS & THE |
| | MICROVAWE ARE OUT OF REACH, 4.2 SPACE |
| | & REACH RANGE, SEE ALSO A-5-10 & |
| | A-5 SEC 11. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | (561)659-8096 X8412. |