Plan Review Details - Permit 01121162
Plan Review Stops For Permit 01121162
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-01-05 Cont ID  
Sent By jwitmer Date 2002-01-05 Time 14:12 Rev Time 2.00
Received By jwitmer Date 2002-01-05 Time 14:12 Sent To  
Notes
2002-01-05 00:00:00BUILDING PLAN REVIEW
 PERMIT # 10021162
 1301 SUMMIT BLVD
 CONT: PCL CONSTRUCTION
 TEL: (407)363-0059
  
 SBC= 1997 STANDARD BUILDING CODE
 SBC*= AMENDMENTS STANDARD BUILDING CODE
 FL ACC= 1997 FLORIDA ACCESSIBILITY CODE
  
 1)- PERMIT APPLICATION INDICATES STEEL
 STRUCTURE TO BE A PRE- ENGINEERED BUILD-
 ING. SBC 2203.1 THE DESIGN, FABRICATION
 AND ERECTION OF STRUCTURAL STEEL BUILD-
 INGS SHALL CONFORM TO THE REQUIREMENTS
 OF EITHER AISC SPECIFICATIONS FOR STRUC-
 TURAL BUILDINGS - ALOWABLE STRESS DESIGN
 OR THE AISC LOAD AND RESISTANCE FACTOR
 DESIGN SPECIFICATION FOR STRUCTURAL
 STEEL BUILDINGS.
 APROFESSIONAL ENGINEER SHALL SIGN HIS NA
 ME AND AFFIX HIS SEAL TO ALL PLANS ,
 SPECIFICATIONS, REPORTS, OR OTHER DOCUME
 NTS PREPAREDOR ISSUED BY SAID REGIS-
 TRAUNT AND BEING FILED FOR PUBLIC
 DOCUMENT. THERE IS NO STRUCTURAL ENGINE-
 ERING PLANS FOR THE PRE-ENGINEERED
 STRUCTURE.
 IF THIS IS A BUILDING (MODULAR)WAS APP-R
 OVED BY THE DEPARTMENT OF COMMUNITY
 AFFAIRS, THERE WOULD ALSO BE ENGINEERED
 PLANS.
 2)- SBC 1804.2.7.2(3) SOILS REPORT
 INDICATING THE BEARING VALUE.
 3)- BLOCK INFILL WALLS INDICATE OPENINGS
 SBC 1606.2.6.2 COMPONENTS & CLADDING
 SHALL REQUIRE (2 COPIES) OF PRODUCT
 APPROVAL REPORTS FOR ALL GLAZED OPENINGS
 SWING DOORS, OVERHEAD DOORS, SKYLIGHT
 ETC. EITHER SBCCI OR DADE COUNTY PRODUCT
 REPORTS ARE ACCEPTED.
 4)- INDICATE THE POS/ NEG PRESURE FOR
 EACH OF THE OPENINGS, INCLUDING END ZONE
 5)- MEZZANINE: SEE 503.2.3 FOR AREA OF
 MEZZANINE, ONLY 1/3 OF THE SQ FT OR 420
 SQ FT ALLOWABLE, PLANS INDICATE 549 S F
 SEE ATTACHMENT, ALSO MEZZANINE USEAGE
 ISNOT LISTED. IF NOT STORAGE, VERTICAL
 ACCESSIBILITYSHALL BE A CONCERN.
 6)- PLANS DO NOT INDICATE DOOR NOR
 WINDOW BUCK ATTACHMENT?
 7)- SBC104.2.2 ADDITIONAL INFORMATION
 REQUIRED, SHEET A-2 INDICATES A SIDEWALK
 AND HANDICAPPED ENTRY RAMP TO THE PARKI
 NG AREA, WHEN VIEWED ON ELEVATION SHEET
 A-4 IT CUTS THE HANDICAPPED RAMP OFF
 TOTALLY?
 8)- ADD INFO FOR DOCK LEVELER FOR HAY
 ROOM.
 9)- DETAIL FOR RATED WALLS, UL LISTING
 AND HOW WILL A FIRESTOP SYSTEM SEAL
 AGAINST THE METAL ROOF. SBC 705.5.1.2
 REQUIRES A MINIMUM POSITIVE PRESSURE DIF
 FERENTIAL OF 0.01 INCH OF WATER AND
 SHALL HAVE AN F RATING NOT LESS THAN THE
 RATING OF THE WALL.
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096X8412

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-12-31 Cont ID  
Sent By dpalmer Date 2001-12-31 Time 06:36 Rev Time 0.00
Received By dpalmer Date 2001-12-31 Time 06:32 Sent To  
Notes
2001-12-31 00:00:00******************* UNSAT *************
  
 1)NOTE: PLEASE NOTE THAT E-1 SHOWS
 3-SET-S OF PIPE AND NOTES ON E-2
 MENTIONS
 ONLY 2 SETS?PLEASE CORRELATE.
  
 2)NOTE: PLEASE NOTE THAT E-1 SHOWS 800A
 GOING TO PANEL "P-2", PLEASE SEE E-6,
 "P-2" IS SHOWN AT 600A? PLEASE CORRELATE
 WHICH ONE IT WILL BE. WIRE RATED FOR
 800A`S.
  
 3)NOTE: PLEASE NOTE THAT LOAD
 CALCULATIONS NEED TO BE SHOWN. PLEASE
 SHOW WATTS/ PER SQ FT, OUTLETS AT 180VA
 ETC ETC.
 PLEASE SHOW ALL CONTINUOUS LOADS AT
 125%EVERYTHING IS SHOWN AT CONNECTED
 LOAD. 220-13,230-42,215-2/3,220-3, ETC.
  
 4)NOTE: PLEASE NOTE LARGEST MOTOR LOADS
 AT 125% ALSO.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS.
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-12-27 Cont ID  
Sent By mcarsill Date 2001-12-27 Time 15:44 Rev Time 0.00
Received By mcarsill Date 2001-12-27 Time 15:44 Sent To  
Notes
2001-12-27 00:00:001) WRONG EDITION OF THE LIFE SAFETY
 CODE REFERENCED. SHOULD READ 1985
 EDITION INSTEAD OF 1997 EDITION.
 2) NO HYDRAULIC CALCULATIONS PROVIDED
 WITH FIRE SPRINKLER DRAWINGS.ALSO NO
 PIPE SIZES OR HANGER LOCATIONS PROVIDED.
 3) A KNOX-BOX RAPID ENTRY SYSTEM WILL
 BE REQUIRED.
 4) PLEASE EXPLAIN WELDING AREA 102.
 PLEASE REVIEW NFPA 51B WITH REGARDS
 TO WELDING AND CUTTING OPERATIONS.
 5) IT APPEARS THAT EXITING TAKES PLACE
 THRU CARPENTRY,SHOP,AND WELDING. THIS
 IS NOT ALLOWED.
 6) PLEASE EXPLAIN FIRE ALARM SEQUENCE
 OF OPERATION NOTES"RELEASE DOOR HOLDS
 AND ELECTRIC LOCKS".
 7) PROVIDE SEPARATE PLANS AND PERMITS
 FOR HOOD,DUCT, FIRE SUPPRESSION AND
 FIRE ALARM SYSTEM.
 8) KITCHEN EXHAUST FAN DISPLAYS 700 CFM.
 A MINIMUM OF 1500 AIR VELOCITY IS
 REQUIRED.
 9) BUILDING ADDRESS IS REQUIRED.
 10) PROVIDE UL NUMBERS FOR RATED WALLS.
 11) PLEASE PROVIDE PRODUCT APPROVAL FOR
 COILING DOOR 120B.
 12) NO SMOKING OR OPEN FLAME SIGNS WILL
 BE REQUIRED IN HAY ROOM.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-12-27 Cont ID  
Sent By ndenmark Date 2001-12-27 Time 12:48 Rev Time 0.50
Received By ndenmark Date 2001-12-27 Time 12:48 Sent To  
Notes
2001-12-27 00:00:00****************DENIED******************
 1. PROVIDE REQUIRED VENTILATION FOR HAY
 STORAGE ROOM
 2. PROVIDE AIR BALANCE SCHEDULE SHOWING
 COMPLIANCE W/ SMC 501.2
 3. PROVIDE OUTSIDE AIR CALCULATIONS
 SHOWING COMPLIANCE WITH ASHRAE 62-89
 4. ROOF MOUNTED EQUIPMENT MOUNTED HIGHER
 THAN 20 FOOT ABOVE FINISHED GRADE SHALL
 REQUIRE A PERMENANT MEANS OF ACCESS TO
 THE ROOF
 5. ROOF SLOPE ON MECHANICAL PLANS
 APPEARS GREATER THAN 4:12. IF SO
 COMPLIANCE WITH SMC 304.6.2 WILL BE
 REQUIRED
 6. SEPARATE PLANS AND PERMITS WILL BE RE
 QUIRED FOR WALK IN COOLER/FREEZER, KITCH
 EN HOOD AND SUPPRESSION SYSTEM.

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-01-10 Cont ID  
Sent By kstevens Date 2002-01-10 Time 11:39 Rev Time 0.00
Received By kstevens Date 2002-01-09 Time 19:55 Sent To  
Notes
2002-01-10 00:00:00DENIED
 REFERENCE: SPC-94-FACBC-97
  
 1) PLANS SHALL BE ROUTED TO PALM BEACH
 COUNTY HEALTH UNIT DIVISION OF ENVIRON-
 MENTAL HEALTH, 901 EVERNIA WPB 33401,
 (561) 355-3018 EXT 1194 BEFORE RESUB-
 MITTING PLANS FOR PLUMBING REVIEW.
 2) PLEASE SUPPLY CALCULATIONS FOR MINI-
 MUM FACILITIES PER SPC SEC 407 AND TABLE
 407.
 3) SHT A-2/A-7 PLEASE SHOW CLEAR FLOOR
 SPACE FOR HDCP FIXTURES IN RMS #105A,
 106A, AND 107 PER FACBC SEC 4.2.4.1,
 AND SEC'S 4.16.2, 4.18.3, 4.19.3.
 4) SHT A-2/A-7 TURNING RADIUS TO BE
 SHOWN IN TOILET ROOM NOT STALL FOR MENS
 AND WOMENS RESTROOMS. SEE FIG 30(E)
 5) SHT A-7 DETAIL #4 W/C TO BE 18" NOT
 18"MIN. LAV TO BE MINIMUM OF 15" TO C/L
 OFF WALL NOT 18" FROM WALL TO SIDE OF
 LAV AS SHOWN.
 6) SHT P-1 FD-2 FUNNEL FLOOR DRAIN NOT
 APPROVED. ALL INDIRECT WASTE TO FLOOR
 SINK. SPC SEC 804.
 7) SHT P-2 KITCHEN EQUIP. PLBG NOTES #3
 ALL INDIRECT WASTE TO FLOOR SINK NOT
 FLOOR DRAINS. SPC SEC 804
 8) SHT P-2 CONDENSATE SHALL DRAIN TO
 STORM OR DRYWELL NOT SANITARY AS SHOWN.
 UTILITY ORD. ALSO CUT SHEETS FOR EACH
 AIR HANDLER IS REQUIRED SHOWING CONDEN-
 SATE DRAIN SIZE. SHOW DETAIL FOR DRYWELL
 9) SHT P-2 CAN WASH SHALL BE PIPED TO
 GREASY WASTE NOT SANITARY.
 10) SHT P-2 GREASE TRAP TO BE SIZED AND
 LOCATED BY WASTE TREATMENT AND ENVIRON-
 MENTAL SERVICES. PLEASE CONTACT R. COMPO
 (561) 837-4074. WASTE ORD. #2938-96
 11) SHT P-2 DRY VENT ON GREASY WASTE NOT
 PER CODE. (COL LINE 1 BETWEEN COL'S E &
 F & BY DISHWASHER) SPC SEC 906.2.1
 12) SHT P-2 FLOOR SINKS IN DRY FOOD
 STORAGE AREA TO BE FLOOR DRAINS AND
 SHALL HAVE TRAP PRIMERS.
 13) SHT P-3 RPZ BACKFLOW REQUIRED ON
 WATER SERVICE FOR THIS BLDG.
 14) SHT P-3 PLUMBING DRAWING NOTES #3 &
 SHT P-4 WATER RISER DIAGRAM, WATER HAMM-
 ER ARRESTORS SHALL BE LOCATED CLOSE TO
 FIXTURES IN "AN EFFECTIVE RANGE" NOT AT
 THE TOP OF DROPS AS STATED OR SHOWN.
 REF. PDI-WH 201 AND MANUFACTURE INSTALLA
 TION INSTRUCTIONS.
 15) SHTS P-2 & P-4 DISHWASHER SHALL BE
 DISCHARGED INTO SANITARY NOT GREASE LINE
 PER UTILITY ORD.
 16) SHT P-4 VENT GOOSENECK FOR GREASE
 TRAP NOT APPROVED. PLEASE VENT GREASE
 LINE IN WALL AS IT ENTERS THE BLDG.
 17) SHT P-4 2 WAY CLEAN OUTS REQUIRED ON
 INLET AND DISCHARGE SIDES OF GREASE TRAP
 18) SHT P-4 CONDENSATE TO VENT THRU ROOF
 SEPARATELY FROM SANITARY. NO CROSS CON-
 NECTION OF SYSTEMS.
 19) SHT P-5 GREASE TRAP DETAIL NOT APP-
 ROVED. SEE ATTACHED SHEET FOR APPROVED
 GREASE TRAP.
 20) SHT P-5 WATER HEATER DETAIL, P&T
 AND PAN DRAIN TO BE PIPED SEPARATELY
 SPC SEC 507.8.4.-PAN AND RELIEF LINE
 TO DISCHARGE INDIRECTLY INTO A FLOOR
 SINK NOT FLOOR DRAIN. SPC SEC 804 AND
 SHALL HAVE A TRAP PRIMER.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***