| 2002-01-10 00:00:00 | DENIED |
| | REFERENCE: SPC-94-FACBC-97 |
| | |
| | 1) PLANS SHALL BE ROUTED TO PALM BEACH |
| | COUNTY HEALTH UNIT DIVISION OF ENVIRON- |
| | MENTAL HEALTH, 901 EVERNIA WPB 33401, |
| | (561) 355-3018 EXT 1194 BEFORE RESUB- |
| | MITTING PLANS FOR PLUMBING REVIEW. |
| | 2) PLEASE SUPPLY CALCULATIONS FOR MINI- |
| | MUM FACILITIES PER SPC SEC 407 AND TABLE |
| | 407. |
| | 3) SHT A-2/A-7 PLEASE SHOW CLEAR FLOOR |
| | SPACE FOR HDCP FIXTURES IN RMS #105A, |
| | 106A, AND 107 PER FACBC SEC 4.2.4.1, |
| | AND SEC'S 4.16.2, 4.18.3, 4.19.3. |
| | 4) SHT A-2/A-7 TURNING RADIUS TO BE |
| | SHOWN IN TOILET ROOM NOT STALL FOR MENS |
| | AND WOMENS RESTROOMS. SEE FIG 30(E) |
| | 5) SHT A-7 DETAIL #4 W/C TO BE 18" NOT |
| | 18"MIN. LAV TO BE MINIMUM OF 15" TO C/L |
| | OFF WALL NOT 18" FROM WALL TO SIDE OF |
| | LAV AS SHOWN. |
| | 6) SHT P-1 FD-2 FUNNEL FLOOR DRAIN NOT |
| | APPROVED. ALL INDIRECT WASTE TO FLOOR |
| | SINK. SPC SEC 804. |
| | 7) SHT P-2 KITCHEN EQUIP. PLBG NOTES #3 |
| | ALL INDIRECT WASTE TO FLOOR SINK NOT |
| | FLOOR DRAINS. SPC SEC 804 |
| | 8) SHT P-2 CONDENSATE SHALL DRAIN TO |
| | STORM OR DRYWELL NOT SANITARY AS SHOWN. |
| | UTILITY ORD. ALSO CUT SHEETS FOR EACH |
| | AIR HANDLER IS REQUIRED SHOWING CONDEN- |
| | SATE DRAIN SIZE. SHOW DETAIL FOR DRYWELL |
| | 9) SHT P-2 CAN WASH SHALL BE PIPED TO |
| | GREASY WASTE NOT SANITARY. |
| | 10) SHT P-2 GREASE TRAP TO BE SIZED AND |
| | LOCATED BY WASTE TREATMENT AND ENVIRON- |
| | MENTAL SERVICES. PLEASE CONTACT R. COMPO |
| | (561) 837-4074. WASTE ORD. #2938-96 |
| | 11) SHT P-2 DRY VENT ON GREASY WASTE NOT |
| | PER CODE. (COL LINE 1 BETWEEN COL'S E & |
| | F & BY DISHWASHER) SPC SEC 906.2.1 |
| | 12) SHT P-2 FLOOR SINKS IN DRY FOOD |
| | STORAGE AREA TO BE FLOOR DRAINS AND |
| | SHALL HAVE TRAP PRIMERS. |
| | 13) SHT P-3 RPZ BACKFLOW REQUIRED ON |
| | WATER SERVICE FOR THIS BLDG. |
| | 14) SHT P-3 PLUMBING DRAWING NOTES #3 & |
| | SHT P-4 WATER RISER DIAGRAM, WATER HAMM- |
| | ER ARRESTORS SHALL BE LOCATED CLOSE TO |
| | FIXTURES IN "AN EFFECTIVE RANGE" NOT AT |
| | THE TOP OF DROPS AS STATED OR SHOWN. |
| | REF. PDI-WH 201 AND MANUFACTURE INSTALLA |
| | TION INSTRUCTIONS. |
| | 15) SHTS P-2 & P-4 DISHWASHER SHALL BE |
| | DISCHARGED INTO SANITARY NOT GREASE LINE |
| | PER UTILITY ORD. |
| | 16) SHT P-4 VENT GOOSENECK FOR GREASE |
| | TRAP NOT APPROVED. PLEASE VENT GREASE |
| | LINE IN WALL AS IT ENTERS THE BLDG. |
| | 17) SHT P-4 2 WAY CLEAN OUTS REQUIRED ON |
| | INLET AND DISCHARGE SIDES OF GREASE TRAP |
| | 18) SHT P-4 CONDENSATE TO VENT THRU ROOF |
| | SEPARATELY FROM SANITARY. NO CROSS CON- |
| | NECTION OF SYSTEMS. |
| | 19) SHT P-5 GREASE TRAP DETAIL NOT APP- |
| | ROVED. SEE ATTACHED SHEET FOR APPROVED |
| | GREASE TRAP. |
| | 20) SHT P-5 WATER HEATER DETAIL, P&T |
| | AND PAN DRAIN TO BE PIPED SEPARATELY |
| | SPC SEC 507.8.4.-PAN AND RELIEF LINE |
| | TO DISCHARGE INDIRECTLY INTO A FLOOR |
| | SINK NOT FLOOR DRAIN. SPC SEC 804 AND |
| | SHALL HAVE A TRAP PRIMER. |
| | |