Plan Review Details - Permit 01121058
Plan Review Stops For Permit 01121058
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-02-12 Cont ID  
Sent By btrobaug Date 2002-02-12 Time 18:00 Rev Time 0.00
Received By btrobaug Date 2002-02-12 Time 18:00 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-12-28 Cont ID  
Sent By btrobaug Date 2001-12-28 Time 10:20 Rev Time 0.00
Received By btrobaug Date 2001-12-28 Time 09:54 Sent To  
Notes
2001-12-28 00:00:00NOT ENOUGH INFORMATION FOR REVIEW,PLEASE
 RESUBMIT WITH THE FOLLOWING:
 1)AIC RATING AS PER 110-9&110-10.
 2)LOAD CALCULATIONS PER INDIVIDUAL UNITS
 3)TOTAL LOAD CALCULATION FOR SERVICE.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 (561) 659-8096 EXT. 8392