Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2001-12-14 Cont ID  
Sent By mamini Date 2001-12-14 Time 09:54 Rev Time 0.50
Received By mamini Date 2001-12-14 Time 09:26 Sent To  
Notes
2001-12-14 00:00:00PASSED WITH PROVISOS:
 1. ANY NEW CONNECTION TO CITY SERVICES
 WILL REQUIRE A SEPARATE PERMIT AND
 APPROVAL THROUGH PUBLIC UTILITIES
 ENGINEERING SERVICES ,659-8040.
 2. ANY WORK WITHIN PUBLIC R.O.W WILL
 REQUIRE A SEPARATE PERMIT THROUGH CITY
 ENGINEER'S OFFICE, 659-8040.
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop FS  
Rev No 2 Status P Date 2001-12-19 Cont ID  
Sent By mcarsill Date 2001-12-19 Time 14:34 Rev Time 0.00
Received By mcarsill Date 2001-12-19 Time 14:34 Sent To  
Notes
***NONE***

Review Stop FS  
Rev No 1 Status F Date 2001-12-13 Cont ID  
Sent By mcarsill Date 2001-12-13 Time 16:31 Rev Time 0.00
Received By mcarsill Date 2001-12-13 Time 16:31 Sent To  
Notes
2001-12-13 00:00:001) IT APPEARS THAT THE FDC IS LOCATED
 BETWEEN THE POST INDICATOR VALVE AND
 THE DCDA. THE FDC SHALL HAVE NO SHUT OFF
 VALVES BETWEEN IT AND THE SYSTEM.
 2) THE POST INDICATOR VALVE SHOWN
 ON THE SYSTEM REQUIRES SUPERVISION.
 3) THE UNDERGROUND FIRE LINE IS TO BE
 INSTALLED IN ACCORDANCE WITH NFPA 24.
 ALL FIRE PROTECTION SYSTEM PIPING IS
 TO BE PRESSURE TESTED FOR TWO HOURS
 AT 200 PSI.
 4) PLEASE PROVIDE CUT-SHEETS FOR FIRE
 SPRINKLER HEADS PLANNED FOR USE.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2001-12-19 Cont ID  
Sent By mcarsill Date 2001-12-19 Time 14:35 Rev Time 0.00
Received By mcarsill Date 2001-12-19 Time 14:35 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved