| 2002-04-24 00:00:00 | DENIED |
| | REFERENCE: SPC-94 - SGC-97 |
| | |
| | 1) SHT A-4 KITCHEN / LAUNDRY ROOM SANT. |
| | RISER DIAGRAM DOES NOT REFLECT FLOOR |
| | PLAN. SHOWS KITCHEN SINK BEING TAKEN OFF |
| | BEFORE SALAD SINK. |
| | 2) SHT A-4 SHOWS CLOUD AT RISER DIAGRAM |
| | FOR SANT., 2ND FLOOR W/C - BIDET BUT |
| | NOT ON FLOOR PLAN. PLEASE CLARIFY. |
| | 3) SEPARATE PERMIT REQUIRED FOR GAS. |
| | PLEASE PROVIDE GAS PERMIT APPLICATION |
| | REQUIREMENT INFORMATION AS FOLLOWS. |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER STANDARD |
| | GAS CODE. |
| | B. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE BEING USED. |
| | C. TYPE OF GAS, (LP OR NATURAL) |
| | D. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE STANDARD GAS CODE SECS. 305.2 THRU |
| | 305.4 AND TABLES 305.4(A) THRU 305.4(E). |
| | E. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | THE STANDARD GAS CODE SEC. 305.4(I). |
| | F. SUBMIT CALCULATIONS FOR COMBUSTION |
| | AIR (IF APPLICABLE) PER THE STANDARD GAS |
| | CODE SECS. 402.4 THRU 402.4.4.7. |
| | G. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER STANDARD GAS CODE SEC. 305.2. IF |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | H. SUBMIT A DETAIL SHOWING THE TYPE, |
| | LOCATION, SIZE AND TERMINATION OF THE |
| | GAS VENTS PER THE STANDARD GAS CODE SECS |
| | 602 THRU 612. |
| | I. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | STANDARD GAS CODE SEC. 402. |
| | J. CLEARLY SHOW THE LOCATION AND CAP- |
| | ACITY OF LP TANK(S), TYPE OF TANK (DOT |
| | OR ASME), THE DISTANCE OF THE TANK FROM |
| | THE BUILDING AND ADJACENT PROPERTY LINES |
| | THE DISTANCE OF THE TANK FROM ALL SOUR- |
| | CES OF IGNITION, OTHER CONTAINERS, BUILD |
| | INGS, AND THE LOCATION OF ANY BUILDING |
| | OPENINGS BELOW THE RELIEF VALVE OF THE |
| | TANK PER NFPA 58, TABLE 3-2.2.2. |
| | K. CLEARLY INDICATE ON THE PLAN IF THE |
| | LP TANK IS ABOVE OR BELOW GROUND, AND |
| | SHOW REQUIRED PROTECTION OF THE TANK AND |
| | APPURTENANCES PER NFPA 58. IF THE TANK |
| | IS BELOW GROUND THE CONTAINER SHALL BE |
| | SECURILY ANCHORED PER NFPA 58 SECTION |
| | 3-2.2.7(H). |
| | |
| | REVIEW BY KEN STEVENS |