Plan Review Details - Permit 01120694
Plan Review Stops For Permit 01120694
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2003-06-11 Cont ID  
Sent By jwitmer Date 2003-06-11 Time 15:32 Rev Time 2.00
Received By jwitmer Date 2003-06-11 Time 15:30 Sent To  
Notes
2003-06-11 00:00:00BUILDING PLAN REVIEW
 PERMIT: 01120694
 ADD: 2901 TUXEDO DRIVE
 CONTRACTOR: E. O. KOCH
 CONTACT: H P TOMPKINS
 TEL: (561)998-0955
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 SUBMITTAL:DENIED
  
 1) FROM THE LAST REVIEW, THE REQUEST FOR
 SITE SPECIFIC ENGINEERING USING THE CITY
 FORM WAS NOT ADHERRED TO. 2ND IT IS SITE
 SPECIFIC REQUIRING A ADDRESS THE COVER
 SHEET HAS JOBSITE ADDRESS BUT NOT THE
 DETAIL SHEET D-408764.
  
 THE DESIGN PROFESSIONAL FOR THE SITE.
 EITHERTHE ENGINEER FOR AMERICAN
 BUILDING COMPANY (JUDSON D. SMITH, P.E.)
 OR H.P. TOMPKINSWHO DESIGNED THE FOUNDAT
 ION, SIGN AND SEAL A LETTER ATTESTING
 THAT THE SITE SPECIFIC ENGINEERING SUP-
 PLIED BY OVERHEAD DOOR CO.(D-408764)
 WILL MEET THE POSITIVE & NEGATIVE WIND
 PRESSURES THAT WILL OCCUR ON THESE
 OPENINGS.
  
 SINCE WE HAVE RECEIVED A PRODUCT TESTING
 REPORT, THIS REPORT INDICATES THE USE OF
 GLAZING, REQUIRING STORM SHUTTERS. PRO-
 VIDE ADDITIONAL INFORMATION ON LARGE
 MISSLE IMPACT RESISTANT GLAZING OR STORM
 SHUTTERS.
  
 THE FINAL COMMENT IS THIS DOOR SYSTEM
 IS NOT COVERED UNDER THIS PERMIT.
 A SEPERATE PERMIT WILL BE REQUIRED SINCE
 PRODUCT TESETING WAAS NOT PART OF THE
 ORIGINAL PERMIT PACKAGE.
 BUILDING PLAN REVIEW
 JIM WITMER
 (561)805-6715

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2003-04-22 Cont ID  
Sent By shernand Date 2003-06-05 Time 13:58 Rev Time 1.25
Received By jwitmer Date   Time   Sent To  
Notes
2003-04-22 00:00:00 
 BUILDING PLAN REVIEW
 PERMIT: 01120694
 ADD: 2901 TUXEDO DRIVE
 CONT: E. O. KOCH
 TEL: (561)998-0955
 1997 SBC= 1997 STANDARD BUILDING CODE
  
 REVISION: DENIED
  
 THIS BUILDING WAS DESIGNED UNDER THE
 1997 STANDARD BUILDING CODE.THE CITIES
 INTERPRETATION FOR THE IMPLEMENTATION
 OF HURRICANE MISSLE IMPACT PROTECTION
 STANDARD AUSUST 1,2001 WAS IN AFFECT.
 THE STANDARD ALLOWS FOR SITE SPECIFIC
 ENGINEERING WHEN A MODEL CODE EVALUATION
 & COMPLIANCE REPORT IS NOT AVAILABLE.
  
 A COPY OF THE SITE SPECIFIC ENGINEERING
 FORM IS ATTACHED. SEE QUESTION 17 B AND
 ALTERNATE METHOD # 2. BOTH THE CERTIFICA
 TE OF COMPLIANCE AND INSTALLATION AFFI-
 DAVIT ARE TO BE ON THE APPROVED FORMS
 PROVIDED BY THE CITY OF WEST PALM BEACH.
  
 THE ENGINEER THAT TESTED THE OVERHEAD
 DOOR FILLS OUT THE REQUIRED INFORMATION
 ON THE LEFT SIDE OF THE FORM, AND SIGNS
 AND SEALS THE BOTTOM LEFT ATTESTING TO
 THE TESTING OF THE PRODUCT.
 THE ENGINEER OF RECORD FILLS OUT THE
 RIGHT SIDE, BUCK ATTACHMENT ENCLUDED.
 THE DESIGN PROFESSIONAL SEALS THE RIGHT
 SIDE OF THE FORM ATTESTING THIS PRODUCT
 WILL WORK IN THIS STRUCTURE.
  
 A SEPERATEPERMIT WILL BE REQUIRED
 FOR THE OVERHEAD DOORS. SEE BOTTOM OF
 PAGE 7 OF STANDARD. WHEN PRODUCT APPROVA
 LS NOR ENGINEERED DRAWING ARE SUBMITTED
 WITH THE PERMIT APPLICATION, THEN A
 SEPERATE PERMIT WILL BE REQUIRED.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)659-8096 X 8412
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2003-03-03 Cont ID  
Sent By shernand Date 2003-04-11 Time 14:52 Rev Time 0.33
Received By jwitmer Date 2003-03-03 Time 07:01 Sent To  
Notes
2003-03-03 00:00:00REVISION: FEB 27/03

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2002-12-05 Cont ID  
Sent By btrobaug Date 2003-02-28 Time 16:22 Rev Time 1.50
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2002-06-21 Cont ID  
Sent By jwitmer Date 2002-06-21 Time 08:37 Rev Time 0.00
Received By jwitmer Date 2002-06-21 Time 10:33 Sent To  
Notes
2002-06-21 00:00:00 
 BUILDING PLAN REVIEW
 PERMIT: 01120694
 ADD: 2901 TUXEDO AVE
 CONT: H. P. TOMPINS
 TEL: (561)998-0955
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1) PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
 ENGINEER FOR AMERICAN BUILDING CO. TO
 SIGN SEAL ALL PLANS,ETC.
  
 2) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORT, SBCCI OR DADE COUNTY
 REPORT ARE ACCEPTED.THERE IS NO CURRENT
 PRODUCT TESTING REPORT FROM SBCCI OR
 DADE COUTNY, SITE SPECIFIC ENGINEERING
 SHALL BE REQUIRED FOR STRUCTURE:
 SITE SPECIFIC ENGINEERING (PRODUCT
 APPROVAL) REQUIRES THE WET SIGNATURE,
 DATE AND EMBOSSED SEAL OF THE ENGINEER
 CERTIFYING THE PRODUCT AND SIGNATURE
 AND SEAL OF THE DESIGN PROFESSIONAL
 OF RECORD.
  
 3) NOTE: AMERICAN BUILDING CO. THIS
 CERTIFICATION IS LIMITED TO THE STRUC-
 TURAL DESIGN OF THE FRAMING AND COVERING
 PARTS MANUFACTURED BY AMERICAN BUILDING
 CO.
 PRODUCT APPROVAL REPORTS SHALL BE
 REQUIRED FOR ALL WINDOWS, DOORS AND EXTE
 RIOR OPENINGS, SKYLIGHTS ETC..
  
 4) F102.2.6: THIS PROPOSED STRUCTURE IS
 LOCATED IN A FIRE DISTRICT, EXTERIOR
 WALLS OF A TYPE IV BUILDING SHALL HAVE
 A FIRE RESISTANCE RATING OF 2 HRS. OR
 MORE WHEN SUCH WALLS ARE LOCATED WITH-
 IN 30'-0" OF A COMMON PROPERTY LINE OR
 AN ASSUMED PROPERTY LINE BETWEEN 2 BUILD
 INGS/ SAME LOT.
  
 5) SEC. 411.4 ENCLOSED PARKING GARAGES:
 (2) A MECHANICAL SYSTEM FOR THE REMOVAL
 OF THE COMBUSTION SHALL BE PROVIDED IN
 ENCLOSED AUTOMOBILE GARAGES. THE MECHANI
 CAL SYSTEM SHALL BE CAPABLE OF PROVIDING
 AT LEAST 6 AIR CHANGES PER HR. FOR EACH
 LEVEL.
 6) PROVIDE STORM PANEL INFORMATION WITH
 INSTALLATION SCHEDULE AND KEY PLAN WITH
 SPECIFIC ANCHORS AND MOUNTING TO BE USED
 FOR ALL NON-IMPACT GLAZING.
 FBC 1606.1.4.
  
 7) FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
  
 8) PROVIDE 2 CURRENT COPIES OF SIGNED &
 SEALED SURVEYS WITH PROPOSED IMPROVEMENT
 TO BE COMPLETED. THIS PROPERTY MAY BE
 LOCATED IN A FLOOD ZONE.
  
 9) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 10)BEFORE A PERMIT TO CONSTRUCT CAN BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH CO.,THE PERMIT PLANS STAMPED BY
 THEM AND THE RECEIPT ATTACHED TO THE
 PERMIT APPLICATION.
  
 CALCULATED VALUE OF STRUCTURE:
 $312,000.00
 PERMIT, ADDITIONAL FEES $613.42
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDEN-
 TIFYING THE SHEET OR SPECIFICATION PAGE
 WHERE THE CHANGES CAN BE FOUND, WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
 JIM WITMER
 PLAN REVIEW
 TEL: (561)659-8096 EX.8412
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-01-02 Cont ID  
Sent By jwitmer Date 2002-01-02 Time 13:48 Rev Time 2.50
Received By jwitmer Date 2002-01-02 Time 13:48 Sent To  
Notes
2002-01-02 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01120694
 2901 TUXEDO AV
 CONT: E.O. KOCH CONSTRUCTION
 TEL: (863) 385-8649
  
 SBC= 1997 STANSARD BUILDING CODE
 SBC*= AMENDMENTS STANDARD BUILDING CODE
  
 TYPE IV BUILD, UNPROTECTED MODEL:LRFM1
 ******
 AMERICAN BUILDING CO. PRODUCT APPROVAL
 REPORT LISTED FOR SBCCI # 8966.12 NO
 LONGER IS A CURRENT REPORT. SBCCI DOES
 SHOW THIS COMPANY WITH A CURRENT REPORT
 # 94100 WHICH DOES HAVE PORTIONS USED
 FROM THE PREVIOUS ACCEPTED REPORT.
 ******
 THIS BUILDING IS LOCATED IN A DESIGNATED
 "FIRE DISTRICT".
  
 F102.2.6: EXTERIOR WALLS OF TYPE IV
 BUILDINGS SHALL HAVE A FIRE RESISTANCE
 OF 2 HRS OR MORE WHEN SUCH WALLS ARE
 LOCATED WITHIN 30' OF A COMMON PROPERTY
 LINE OR AN ASSUMED PROPERTY LINE
 BETWEEN 2 BUILDINGS/ SAME LOT.
  
 SBC FIGURE 1606 BASIC WIND SPEEDS, IN-
 DICATES THAT THIS BUILDING REQUIRES
 A DESIGN FOR 110MPH WIND ZONE. THE SBCCI
 TEST:
 WIND LOAD: MAXIMUM WIND SPEED 100 MPH.
  
 SBC104.2.2* ADDITIONAL INFORMATION
 REQUIRED, THIS STRUCTURE IS TO BE USED
 FOR STORAGE, WHAT TYPE OF MATERIALS ARE
 GOING TO BE STORED? PLANS INDICATE POSS-
 IBLE ENCLOSED PARKING SEE 411.4.
 THE SITE PLAN SHOWS A NATURAL GAS TANK
 NEXT TO THE BUILDING, IS THIS A ABOVE
 THE GROUND TANK? AMOUNT OF GALLONS?
 SBC 404.2.3- 404.2.7 ADDRESS PUMPS AND
 OTHER DISPENSING DEVISES.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561)659-8096 X 8412

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2002-11-15 Cont ID  
Sent By dpalmer Date 2002-11-15 Time 07:27 Rev Time 0.50
Received By dpalmer Date 2002-11-15 Time 07:27 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-06-11 Cont ID  
Sent By dpalmer Date 2002-06-11 Time 16:55 Rev Time 0.00
Received By dpalmer Date 2002-06-11 Time 16:55 Sent To  
Notes
2002-06-11 00:00:00************** NOTE ******************
  
 PLEASE NOTE REDLINED ON PLANS THAT THIS
 AREA IS SHOWN AS VEHICLE STORAGE ONLY!!
 AND MEETS MIN FOR 511-2.
 IF THERE ARE ANY CHANGES OF USE OR
 STORAGE THEN PLANS MAY NEED TO HAVE
 ELECTRICAL CHANGES MADE.
 PASSED PENDING OTHER REVIEWS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-12-26 Cont ID  
Sent By dpalmer Date 2001-12-26 Time 19:09 Rev Time 0.00
Received By dpalmer Date 2001-12-26 Time 19:09 Sent To  
Notes
2001-12-26 00:00:00**************UNSAT ****************
  
 1)NOTE: PLEASE NOTE THAT THE COVER SHEET
 SHOWS, "ME-1" FOR MECH/ELECTRICAL PLANS
 AND YET NO ME SHEETS WERE SUBMITTED??
  
 2)NOTE: PLEASE NOTE THAT AS PER OVERVIEW
 OF OTHER PLANS, PLEASE NOTE THAT ALL
 PLANS SUBMITTED MUST HAVE A TITLE BLOCK
 FOR THE ENGINEER OF RECORD PER FS/FAC
 61G15-23.002./471.025.
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2001-12-12 Cont ID  
Sent By mamini Date 2001-12-12 Time 16:07 Rev Time 2.00
Received By mamini Date 2001-12-12 Time 16:07 Sent To  
Notes
2001-12-12 00:00:00PASSED WITH PROVISOS :
 1. ALL THE NEW DRIVEWAYS WILL REQUIRE
 REQUIRE SEPARATE PERMITS THROUGH
 BUILDING DEPARTMENT,PER CITY'S STANDARD.
 2. ANY NEW CONNECTIONS TO CITY'S SERVICE
 WILL REQUIRE A SEPARATE PERMIT THROUGH
 PUBLIC UTILITIES ENGINEERING SERVICES
 DEPARTMENT, 659-8040.
 3. ALL CURB & GUTTRS,SIDEWALKS ALONG THE
 PROPERTY THAT ARE DAMAGED MUST BE
 RESTORED TO ORIGINAL CONDITIONS OR
 BETTER.
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2002-11-15 Cont ID  
Sent By mcarsill Date 2002-11-15 Time 12:20 Rev Time 0.00
Received By mcarsill Date 2002-11-15 Time 12:20 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2002-06-19 Cont ID  
Sent By mcarsill Date 2002-06-19 Time 13:04 Rev Time 0.00
Received By mcarsill Date 2002-06-19 Time 13:04 Sent To  
Notes
2002-06-19 00:00:00SEE PREVIOUS PLAN REVIEW COMMENTS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-12-13 Cont ID  
Sent By mcarsill Date 2001-12-13 Time 14:45 Rev Time 0.00
Received By mcarsill Date 2001-12-13 Time 14:45 Sent To  
Notes
2001-12-13 00:00:001) PLEASE PROVIDE MORE DETAILS ON LP
 GAS TANK SHOWN ON THE PLANS.
 2) WHAT PROVISIONS ARE GOING TO BE MADE
 FOR FIRE RESCUE TO ACCESS THE
 SECURITY GATES.
 3) WHAT WILL THE BUILDING BE USED FOR.
 IF USED FOR STORAGE, WHAT WILL BE
 STORED WITHIN IT.
 4) PLEASE INDICATE ALL ILLUMINATED
 EXIT SIGNS, AND EMERGENCY LIGHT
 FIXTURES.
 5) PLEASE PROVIDE A DOOR SCHEDULE.
 6) PLEASE INDICATE OCCUPANT LOAD
 FOR THE BUILDING WHEN IT WILL BE
 OCCUPIED.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-06-05 Cont ID  
Sent By shernand Date 2003-06-05 Time 13:58 Rev Time 0.00
Received By shernand Date 2003-06-05 Time 13:58 Sent To B
Notes
2003-06-05 00:00:00JW DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-04-11 Cont ID  
Sent By shernand Date 2003-04-11 Time 14:52 Rev Time 0.00
Received By shernand Date 2003-04-11 Time 14:52 Sent To B
Notes
2003-04-11 00:00:00JW DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-02-28 Cont ID  
Sent By btrobaug Date 2003-02-28 Time 16:21 Rev Time 0.00
Received By btrobaug Date 2003-02-28 Time 16:21 Sent To B
Notes
2003-02-28 00:00:00TO JIM./WRT

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-11-07 Cont ID  
Sent By btrobaug Date 2002-11-07 Time 18:54 Rev Time 0.00
Received By btrobaug Date 2002-11-07 Time 18:54 Sent To  
Notes
2002-11-07 00:00:00TO COMM BOARD#9./WRT

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2002-12-02 Cont ID  
Sent By pkrauss Date 2002-12-02 Time 09:02 Rev Time 0.30
Received By pkrauss Date 2002-12-02 Time 09:02 Sent To  
Notes
2002-12-02 00:00:00SUBMITTAL LETTER FROM ENG OF RECORD -
 SEQUENCE OF VENTILATION FOR THE VEHICLE
 STORAGE.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2002-11-26 Cont ID  
Sent By pkrauss Date 2002-11-26 Time 15:23 Rev Time 0.45
Received By pkrauss Date 2002-11-26 Time 14:57 Sent To  
Notes
2002-11-26 00:00:00SUBMITTAL DATA FOR ALTERNATE MATERIALS
 AND METHODS HAVE TO BE APPROVED BY THE
 BUILDING OFFICAL.PLEASE PROVIDE A
 SEQUENCE OF OPERATION SHOWING COMPLIANCE
 WITH 1997 SBC 103.7.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2002-06-11 Cont ID  
Sent By ndenmark Date 2002-06-11 Time 09:31 Rev Time 0.50
Received By ndenmark Date 2002-06-11 Time 09:31 Sent To  
Notes
2002-06-11 00:00:00DENIED PER PRIOR PLAN REVEIW NOTES:
  
 1997 SBC 411.4.2 REQUIRES A MECHANICAL
 VENTILATION SYSTEM FOR ENCLOSED GARAGES
 WITH AT LEAST 6 AIR CHANGES PER HOUR.
  
 PROVIDE CALCULATIONS SHOWING COMPLIANCE
 WITH THIS REQUIREMENT.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-12-20 Cont ID  
Sent By pkrauss Date 2001-12-20 Time 07:09 Rev Time 0.50
Received By pkrauss Date 2001-12-19 Time 15:19 Sent To  
Notes
2001-12-20 00:00:00********************DENIED**************
  
  
 PLANS INDICATE THIS FACILITY IS BEING
 USED FOR VECHICLE STORAGE.PLEASE
 INDICATE HOW MANY VECHICLES ARE BEING
 STORED AND ANY MAINTENANCE WILL BE
 TAKING PLACE.INDICATE VENTILATION
 CALCULATIONS SHOWING COMPLIANCE WITH
 1997 SBC 411.4.2 & 411.5.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 3 Status P Date 2002-12-05 Cont ID  
Sent By kstevens Date 2002-12-05 Time 11:37 Rev Time 0.50
Received By kstevens Date 2002-12-05 Time 11:37 Sent To  
Notes
2002-12-05 00:00:00PASSED/PROVISO
  
 PRIOR TO INSPECTION OF FOUNDATION A
 LETTER IS REQUIRED STATING THAT FACILIT-
 IES WILL BE AVAILABLE PER SECTION 403.4
 EXCEPTION. INDICATE TRAVEL DISTANCE AND
 THAT FACILITIES WILL BE OPEN WHEN STOR-
 AGE FACILITY IS BEING USED.
  
 SEPARATE GAS PERMIT REQUIRED.
 SEPARATE IRRIGATION PERMIT REQUIRED IF
 IRR. WORK IS BEING DONE.

Review Stop P PLUMBING
Rev No 2 Status F Date 2002-06-17 Cont ID  
Sent By kstevens Date 2002-06-17 Time 11:33 Rev Time 0.00
Received By kstevens Date 2002-06-17 Time 11:33 Sent To  
Notes
2002-06-17 00:00:00DENIED
 REFERENCE: SPC-94-FACBC-97
  
 A) COMMENTS FROM LAST REVIEW NOT ADD-
 RESSED.
 1) WILL THERE BE A WATER SERVICE TO THE
 BLDG?
 2) SUBMIT CALCULATIONS FOR MINIMUM FAC-
 ILITIES PER TABLE 407
 3) BACKFLOW REQUIRED ON WATER SERVICE.
 4) N/A
 5) SHT CE-1 OF 1 SHT L-1 OF 1 SHOW AN LP
 TANK (GAS). BUT UN-NUMBERED SHEET AFTER
 SHT L-1 OF 1 SHOWS NATURAL GAS METER.
 PLEASE CLAIRFY.
 6) GAS PERMIT REQUIRED. PLEASE SEE ATT-
 ACHED GAS PERMIT APPLICATION REQUIREMENT
 SHEET FOR INFORMATION REQUIRED FOR GAS
 PERMIT TO BE ISSUED.
 7) IRRIGATION PERMIT REQUIRED. SUBMIT
 PLANS WITH IRRIGATION PERMIT APPLICATION
 PLUMBING CONTRACTOR SHALL INSTALL BACK-
 FLOW FOR IRRIGATION.
 8) PLEASE NOTE THAT ALL SHEETS THAT ARE
 SIGNED AND SEALED SHALL HAVE A TITLE
 BLOCK CONTAINING PRINTED NAME, ADDRESS,
 AND NUMBER OF ENGINEER OR ENGNEERING
 BUSINESS ON THEM PER FS61G15-23.002
 9) PLEASE ADDRESS ALL COMMENTS WITH A
 REPLY TO EXPEDITE PLAN REVIEW.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-01-05 Cont ID  
Sent By kstevens Date 2002-01-05 Time 08:19 Rev Time 1.25
Received By kstevens Date 2002-01-05 Time 08:19 Sent To  
Notes
2002-01-05 00:00:00DENIED
 REFERENCE: SPC-94-FACBC-97
  
 1) MORE INFORMATION REQUIRED. WILL THERE
 BE ANY WATER TO THE BLDG.
 2) SHOW CALCULATIONS FOR MINIMUM FACIL-
 ITIES REQUIRED IN SPC TABLE 407.
 3) BACKFLOW REQUIRED FOR WATER SERVICE
 TO BLDG.
 4) SHT CE-1 OF 1 TYPICAL DOWN SPOUTS
 SHOWN TO DRAIN ROOF, PLEASE SHOW SIZE OF
 ROOF DOWN SPOUTS.
 5) SHT CE-1 OF 1 AND SHT L-1 OF 1 SHOW
 AN LP-TANK (GAS) BUT UN-NUMBERED SHEET
 AFTER SHT L-1 OF 1 SHOWS NATURAL GAS
 METER. PLEASE CLAIRFY.
 6) GAS PERMIT REQUIRED. PLEASE SEE ATT-
 ACHED GAS PERMIT APPLICATION REQUIREMENT
 SHEET FOR INFORMATION REQUIRED FOR PER-
 MIT TO BE ISSUED.
 7) IRRIGATION PERMIT REQUIRED. PLUMBING
 CONTRACTOR TO PROVIDE BACKFLOW FOR IRR.
 8) PLEASE NOTE THAT ALL SHEETS THAT ARE
 SIGNED AND SEALED SHALL HAVE A TITLE
 BLOCK CONTAINING THE PRINTED NAME, AD-
 DRESS AND NUMBER OF THE ENGINEER OR
 ENGINEERING BUSINESS ON THEM PER FS
 61G15-23.002
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 2 Status P Date 2002-06-05 Cont ID  
Sent By sgraham Date 2002-06-05 Time 09:15 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2001-12-12 Cont ID  
Sent By mamini Date 2001-12-12 Time 15:15 Rev Time 0.25
Received By mamini Date   Time   Sent To  
Notes
***NONE***