| 2002-01-31 00:00:00 | *************BUILDING DENIED************ |
| | |
| | 1) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 2) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 3) PROVIDE ENERGY CALCULATIONS |
| | AS REQUIRED BY THE 1997 FLORIDA ENERGY |
| | EFFICIENCY CODE FOR BUILDING |
| | CONSTRUCTION. |
| | |
| | 4)PROVIDE (2) CURRENT AND COMPLETE |
| | COPIES OF SBCCI OR METRO-DADE PRODUCT |
| | APPROVALS FOR: |
| | - ROOF TILE (EXPIRED 6-25-01) |
| | - MULLIONS (EXPIRED 4-9-01) |
| | - FRENCH DOORS (EXPIRED 11-22-01) |
| | - GARAGE DOORS (NEED COMPLETE REPORT FOR |
| | BOTH SIZES OF GARAGE DOORS USED) |
| | - STORM PANELS FOR ANY GLAZED OPENINGS |
| | NOT OF IMPACT RESISTANT GLASS |
| | - SLIDING GLASS DOORS |
| | - AWNING WINDOWS |
| | - FRONT DOOR (DOUBLE DOORS W/SIDELITES) |
| | - CASEMENT WINDOWS |
| | |
| | 5) INDICATE ATTIC ACCESS ON SECOND FLOOR |
| | PER 2309.6. |
| | |
| | 6) PROVIDE LISTING INFORMATION FOR BBQ |
| | ON COVERED PORCH. |
| | |
| | 7) PROVIDE CITY OF WEST PALM BEACH SITE |
| | SPECIFIC ENGINEERING FORM AND ENGINEERED |
| | DRAWINGS FOR BUTT GLASS WINDOWS. FORM |
| | MUST BE SIGNED AND SEALED BY THE |
| | ENGINEER AND THE ARCHITECT. |
| | |
| | 8) THE GUARDRAIL DETAIL ON A-3 SHOWS |
| | INCORRECT SPACING FOR INTERMEDIATE RAILS |
| | CODE STATES THAT A 4" SPHERE SHALL NOT |
| | PASS BETWEEN THEM PER 1015.3. |
| | |
| | 9) PROVIDE SAFETY GLASS IN BATHROOMS PER |
| | 2405.2.1. |
| | |
| | 10) NOTES ON HANDRAILS/GUARDRAILS ON A-3 |
| | CONTAIN INCORRECT INFORMATION. SEE |
| | CORRECTIONS ON PLAN. |
| | |
| | 11) THE SOIL REPORT STATES THAT BOTTOM |
| | OF FOOTERS SHOULD BE A MINIMUM OF 18" |
| | BELOW ADJACENT GRADE AND CITY AMENDMENTS |
| | REQUIRE THE FLOOR ELEVATION AT HABITABLE |
| | AREAS TO BE A MINIMUM OF 4" ABOVE FINISH |
| | GRADE. THEREFORE, THE EXTERIOR FOOTERS |
| | MUST BE A MINIMUM OF 22" THICK. PLEASE |
| | CORRECT. |
| | |
| | 12) ONE PAIR OF THE PEDESTALS IN THE |
| | GARAGE DO NOT SHOW THE TWO 4FT. #5 BARS |
| | INDICATED AT THE OTHER PEDESTALS. |
| | |
| | 13) THE WALL SECTION ON A-8 DIFFERS ON |
| | LEDGER ATTACHMENT WITH DETAIL H AND THE |
| | LEDGER SCHEDULE. |
| | |
| | 14) STUCCO INFO ON A-8 WALL SECTION IS |
| | INCORRECT 3 COATS TOTALING 7/8" IS |
| | REQUIRED, SEE 2504.2.1 AND ASTM C 926. |
| | |
| | 15) DETAIL J/A-8 LISTED ON SHEET A-7 IS |
| | NOT INDICATED ON SHEET A-8. |
| | |
| | 16) PROVIDE A DETAILED WALL SECTION OF |
| | THE 2X6 EXTERIOR WALL AT SECOND FLOOR |
| | INDICATING SPECIFIC ANCHORS USED TO |
| | CONNECT WALL TO FLOOR AND ROOF GIRDERS. |
| | |
| | 17) REVIEW THE GARAGE DOOR BUCKS ON A-8, |
| | THE ANCHORS SHOULD EMBED INTO FILLED |
| | CELL CONCRETE. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)659-8096 EXT.8202 |