Plan Review Details - Permit 01120670
Plan Review Stops For Permit 01120670
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2002-04-05 Cont ID  
Sent By dpalmer Date 2002-04-05 Time 14:09 Rev Time 0.00
Received By dpalmer Date 2002-04-05 Time 11:21 Sent To B
Notes
2002-04-05 00:00:00************** PROVISO/REVISION ********
  
 1)NOTE: PLEASE NOTE LOAD CALCULATIONS
 NEED TO MEET ART 220 OF THE NEC.
 PLEASE NOTE THAT PANEL SCHEDULE "B" IS
 SHOWING LOAD FOR PANEL "C" AT 4800VA.
 PLEASE NOTE THE PANEL "C`S" LOAD IS
 SHOWN AT 19,800VA?? PLEASE CORRELATE.
  
 PLEASE REVISE LOAD CALCULATIONS AND
 SUBMIT REVISED PLAN FOR REVIEW BEFORE
 ROUGH ELECTRICAL INSPECTION IS CALLED IN
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2002-03-01 Cont ID  
Sent By dpalmer Date 2002-03-01 Time 13:03 Rev Time 0.00
Received By dpalmer Date 2002-03-01 Time 13:03 Sent To B
Notes
2002-03-01 00:00:00*************** UNSAT *****************
  
 PLEASE NOTE THAT NOT ALL NOTES FROM
 FIRST REVIEW WERE ADDRESSED.
 THERE ARE SOME NOTES DUE TO OTHER
 CHANGES MADE.
  
 1)NOTE: PLEASE NOTE THAT ON FIRST
 REVIEW LOAD EXCEEDED PANEL "B" (200A)
 AND NOW PANEL WAS INCREASED TO 250A.
 PLEASE NOTE CONDUCTORS ARE STILL SHOWN
 AT 3/0`S. PLEASE SEE 310-15(B)(6) FOR
 SIZING.
  
 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
 NONE WERE SUBMITTED.
  
 3)NOTE: PLEASE NOTE THAT SOME LOADS/
 BKRS/AND OCP STILL DO NOT CORRELATE.
 PLEASE NOT SOME LOADS EXCEEDRATINGS OF
 BRKRS/WIRE.
  
 4)NOTE: PLEASE NOTE PLANS ARE SHWOING
 EQUIPMENT GROUNDINGCONDUCTORS BETWEEN
 GUTTER AND MAIN DISC`S? PLEASE NOTE
 THAT THIS IS PARALLELING THE NEUTRAL?
 PLEASE NOTE THAT AN EQUIPMENT GROUND IS
 ONLY INSTALLED AFTER THE FIRST MEANS
 OF DISCONNECT.
  
 5)NOTE: PLEASE CLARIFY PLANS SHOWING
 A 1/0 BOND?? INSTALLED BETWEEN METER
 AND MAIN GUTTER? PLEASE CLARIFY THAT
 SERVICE IS SINGLE PHASE AND ALREADY
 SHOWS 2 HOTS AND A NEUTRAL??
  
 6)NOTE: PLEASE NOTE MISSING BLDG/FOOTER
 STEEL PER 250-50
  
 7)NOTE: PLEASE NOTE STILL MISSING SOME
 OUTLETS PER 210-52. SEE SECOND FLOOR
 OPEN AREA AND BR#4.
  
 8)NOTE: PLEASE NOTE PLANS ONLY SHOW ONE
 MAIN DISC NEXT TO METER? PLEASE SHOW
 BOTH. GROUPED PER 230-72
  
 9)NOTE: PLEASE CLARIFY WHAT APPEARS TO
 BE A A/C CU OUTSIDE CABANA BATH?
 PLEASE NOTE THAT IF HEAT PUMP,/ CLARIFY
 HEAT PUMP AS IT IS SHOWN AT ONLY AT 2P-
 20A.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-01-02 Cont ID  
Sent By dpalmer Date 2002-01-02 Time 11:22 Rev Time 0.00
Received By dpalmer Date 2002-01-02 Time 11:21 Sent To  
Notes
2002-01-02 00:00:00***************** UNSAT ***************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 3) NOTE: PLEASE SHOW ALL OUTLET SPACING
 TO MEET 2`,6`,12` RULE PER 210-52.
 ONLY A FEW LOCATIONS.
  
 4)NOTE: PLEASE NOTE THAT THERE ARE MANY
 LOCATIONS ON PANEL SCHEDULES WHERE THE
 WIRE SIZE/BRKR/ AND LOADS DO NOT
 CORRELATE.
 PLEASE NOTE THAT SOME LOADS EXCEED WIRE
 AND BRKR RATING, SOME OCP IS SHOWN AT
 60A FOR 5KW LOAD?
  
 5)NOTE: PLEASE NOTE PLANS ARE SHOWING
 A WASHER AND DRYER UPSTAIRS ALSO, BUT
 DO NOT SHOW ANY INFORMATION ON PANEL
 SCHEDULES? PLEASE CLARIFY.
  
 6)NOTE: PLEASE NOTE THAT LOAD CALCULATIO
 NS SEEM TO HAVE BEEN MISPRINTED. PLEASE
 NOTE THAT SHOWS VOLTAGE AS 140 INSTEAD
 OF 240 AND SHOWS AMPS INSTEAD OF VOLTS
 PLEASE CORRECT.
  
 7)NOTE: PLEASE NOTE THAT WIRE SIZE FOR
 MAIN SERICE IS NOT LARGE ENOUGH.
 PLEASE NOTE THAT 350MCM IS ONLY RATED
 FOR A 350A SERVICE. 310-15
 PLEASE NOTE LOAD SHOWN EXCEEDS 350AMPS.
 PLEASE CORRECT.
  
 8)NOTE: PLEASE NOTE THAT THE LOAD SHOWN
 FOR PANEL "B" EXCEEDS THE RATING OF
 THE 200A DISCONNECT FEEDING PANEL "B"
 PLEASE CORRELATE.
  
 9)NOTE: PLEASE NOTE MISSING LIGHTING AND
 RECEPT PER 210-70/210-63 FOR AHU IN
 ATTICS/ATTIC ACCESS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-09-08 Cont ID  
Sent By csiegber Date 2003-09-08 Time 12:20 Rev Time 0.00
Received By csiegber Date 2003-09-08 Time 12:19 Sent To P
Notes
2003-09-08 00:00:00TO KS BOX/REV

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2003-07-21 Cont ID  
Sent By pkrauss Date 2002-04-09 Time 16:25 Rev Time 0.40
Received By hmoser Date 2002-04-09 Time 16:03 Sent To B
Notes
2002-04-09 00:00:00 
 PROVISO:
  
 PROVIDE MANUFACTURER SUBMITTAL DATA &
 INSTALLATION INSTRUCTIONS FOR THE
 BARBECUE GRILL, HOOD & DUCT AS WELL AS
 SUBMITTAL DATA & INSTALLATION
 INSTRUCTIONS FOR THE GAS RANGE.
 PROVIDE THE ABOVE INFORMATION AT THE
 TIME OF ROUGH INSPECTION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2003-07-21 Cont ID  
Sent By hmoser Date 2002-02-23 Time 08:49 Rev Time 0.75
Received By hmoser Date 2002-02-23 Time 08:49 Sent To  
Notes
2002-02-23 00:00:00PLAN DENIED
 #1 NEED MANUFACTURE INSOLATION
 ON KITCHEN DOWNDRAFT
 #2 NEED TO SHOW TERMINATION OUTSIDE
 FOR DOWNDRAFT
 #3 NEED MANUFACTURE INSOLATION
 ON BABECUE HOOD
 #4 ENERGY CALCKS SHOW 3 A/C UNIOTS
 PLAN SHOW 5 A/C UNIOTS

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-12-26 Cont ID  
Sent By hmoser Date 2001-12-26 Time 19:25 Rev Time 0.50
Received By hmoser Date 2001-12-26 Time 19:25 Sent To  
Notes
2001-12-26 00:00:00PLAN DENIED
 NO ENERGY CALCS
 104.2.1 A/C PLANS TO A/C NUMBER 3
 NOT CLEAR
 PLAN REVIEW BY HAROLD MOSER
 [561]659-8096 EXT 8390

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-09-25 Cont ID  
Sent By kstevens Date 2003-09-25 Time 18:47 Rev Time 0.50
Received By kstevens Date 2003-09-25 Time 18:47 Sent To  
Notes
2003-09-25 00:00:00REVISION OK - SANT. RISER DIAGRAM

Review Stop P PLUMBING
Rev No 1 Status P Date 2001-12-21 Cont ID  
Sent By csiegber Date 2003-09-08 Time 12:20 Rev Time 0.50
Received By kstevens Date 2001-12-21 Time 21:20 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2002-04-11 Cont ID  
Sent By rmcdouga Date 2002-04-11 Time 15:08 Rev Time 2.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-04-11 00:00:00************BUILDING PROVISO************
  
 1) PROVIDE PRODUCT TESTING REPORTS OR
 SITE SPECIFIC PRODUCT APPROVAL FORM
 COMPLETED, SIGNED, SEALED AND DATED BY
 ENGINEER AND THE DESIGN PROFESSIONAL OF
 RECORD FOR THE BUTT GLASS WINDOWS PRIOR
 TO INSTALLATION.TWO COPIES ARE REQUIRED.
  
 2)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - AWNING WINDOWS AS INDICATED ON PLANS
 - GARAGE DOORS (ONLY THE DRAWING FOR
 SBCCI REPORT #9606 WAS SUBMITTED) THE
 CURRENT SBCCI REPORT # 9606C AND THE
 APPROVED DRAWINGS ARE REQUIRED PRIOR TO
 INSTALLATION.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2002-03-18 Cont ID  
Sent By rmcdouga Date 2002-03-18 Time 09:54 Rev Time 2.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-03-18 00:00:00*************BUILDING UNSAT*************
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE DESIGN CERTIFICATION FORM FOR
 BUILDING CODE COMPLIANCE REQUIRES THE
 EMBOSSED SEAL OF THE DESIGNER OF RECORD
 IN ADDITION TO THEIR WET SIGNATURE AND
 THE DATE SIGNED. ON FUTURE SUBMITTALS
 PROVIDE THIS INFORMATION ON THE PLANS.
  
 3) PROVIDE ONE COPY OF ENERGY FORM
 600-A WITH ORIGNAL SIGNATURES AS
 REQUIRED FOR PUBLIC RECORD.
 THE FORM ONLY LISTS 3 A/C SYSTEMS AND
 THE PLANS INDICATE 5 SYSTEMS. PLEASE
 CORRECT.
  
 4) PROVIDE LISTING INFORMATION FOR BBQ
 AT COVERED PORCH.
  
 5) PROVIDE CITY OF WPB SITE SPECIFIC
 PRODUCT APPROVAL FORM AND ENGINEERED
 DRAWINGS FOR BUTT GLASS WINDOWS.THE FORM
 IS REQUIRED TO BE SIGNED, SEALED AND
 DATED BY THE ENGINEER AND THE DESIGNER
 OF RECORD.
  
 6)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - AWNING WINDOWS
 - FRONT DOOR WITH SIDELITES (UNLESS THIS
 WILL BE FRENCH DOORS WHICH WOULD BE
 COVERED UNDER THEPRODUCT APPROVAL THAT
 WAS SUBMITTED)
 - GARAGE DOORS (THE CURRENT SBCCI REPORT
 IS #9606C, REPORT AND DRAWINGS ARE
 REQUIRED) ONLY ONE PAGE OF DRAWING 9606
 WAS SUBMITTED.
  
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2002-01-31 Cont ID  
Sent By rmcdouga Date 2002-01-31 Time 13:59 Rev Time 5.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-01-31 00:00:00*************BUILDING DENIED************
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) PROVIDE ENERGY CALCULATIONS
 AS REQUIRED BY THE 1997 FLORIDA ENERGY
 EFFICIENCY CODE FOR BUILDING
 CONSTRUCTION.
  
 4)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - ROOF TILE (EXPIRED 6-25-01)
 - MULLIONS (EXPIRED 4-9-01)
 - FRENCH DOORS (EXPIRED 11-22-01)
 - GARAGE DOORS (NEED COMPLETE REPORT FOR
 BOTH SIZES OF GARAGE DOORS USED)
 - STORM PANELS FOR ANY GLAZED OPENINGS
 NOT OF IMPACT RESISTANT GLASS
 - SLIDING GLASS DOORS
 - AWNING WINDOWS
 - FRONT DOOR (DOUBLE DOORS W/SIDELITES)
 - CASEMENT WINDOWS
  
 5) INDICATE ATTIC ACCESS ON SECOND FLOOR
 PER 2309.6.
  
 6) PROVIDE LISTING INFORMATION FOR BBQ
 ON COVERED PORCH.
  
 7) PROVIDE CITY OF WEST PALM BEACH SITE
 SPECIFIC ENGINEERING FORM AND ENGINEERED
 DRAWINGS FOR BUTT GLASS WINDOWS. FORM
 MUST BE SIGNED AND SEALED BY THE
 ENGINEER AND THE ARCHITECT.
  
 8) THE GUARDRAIL DETAIL ON A-3 SHOWS
 INCORRECT SPACING FOR INTERMEDIATE RAILS
 CODE STATES THAT A 4" SPHERE SHALL NOT
 PASS BETWEEN THEM PER 1015.3.
  
 9) PROVIDE SAFETY GLASS IN BATHROOMS PER
 2405.2.1.
  
 10) NOTES ON HANDRAILS/GUARDRAILS ON A-3
 CONTAIN INCORRECT INFORMATION. SEE
 CORRECTIONS ON PLAN.
  
 11) THE SOIL REPORT STATES THAT BOTTOM
 OF FOOTERS SHOULD BE A MINIMUM OF 18"
 BELOW ADJACENT GRADE AND CITY AMENDMENTS
 REQUIRE THE FLOOR ELEVATION AT HABITABLE
 AREAS TO BE A MINIMUM OF 4" ABOVE FINISH
 GRADE. THEREFORE, THE EXTERIOR FOOTERS
 MUST BE A MINIMUM OF 22" THICK. PLEASE
 CORRECT.
  
 12) ONE PAIR OF THE PEDESTALS IN THE
 GARAGE DO NOT SHOW THE TWO 4FT. #5 BARS
 INDICATED AT THE OTHER PEDESTALS.
  
 13) THE WALL SECTION ON A-8 DIFFERS ON
 LEDGER ATTACHMENT WITH DETAIL H AND THE
 LEDGER SCHEDULE.
  
 14) STUCCO INFO ON A-8 WALL SECTION IS
 INCORRECT 3 COATS TOTALING 7/8" IS
 REQUIRED, SEE 2504.2.1 AND ASTM C 926.
  
 15) DETAIL J/A-8 LISTED ON SHEET A-7 IS
 NOT INDICATED ON SHEET A-8.
  
 16) PROVIDE A DETAILED WALL SECTION OF
 THE 2X6 EXTERIOR WALL AT SECOND FLOOR
 INDICATING SPECIFIC ANCHORS USED TO
 CONNECT WALL TO FLOOR AND ROOF GIRDERS.
  
 17) REVIEW THE GARAGE DOOR BUCKS ON A-8,
 THE ANCHORS SHOULD EMBED INTO FILLED
 CELL CONCRETE.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop Z ZONING
Rev No 1 Status P Date 2001-12-12 Cont ID  
Sent By mmclean Date 2001-12-12 Time 06:48 Rev Time 0.25
Received By mmclean Date   Time   Sent To  
Notes
***NONE***